Page 66
94
Header sensor
fault
95
Stack sensor
fault
96
Outdoor sensor
fault
97
Internal Fault:
A2D mismatch.
98
Internal Fault:
Exceeded
VSNSR voltage
tolerance
99
Internal Fault:
Exceeded
28V voltage
tolerance
100
Pressure Sensor
Fault
105
Flame detected
out of sequence
106
Flame lost in
MFEP
107
Flame lost early
in run
108
Flame lost in run
H
1. Check wiring and correct any possible errors.
2. Replace the header sensor.
3. If previous steps are correct and fault persists, replace the module.
H
1. Check wiring and correct any possible errors.
2. Replace the stack sensor.
3. If previous steps are correct and fault persists, replace the module.
H
1. Check wiring and correct any possible errors.
2. Replace the outdoor sensor.
3. If previous steps are correct and fault persists, replace the module.
L
Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
L
Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
L
Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
H
1. Verify the Pressure Sensor is a 4-20 ma source.
2. Check wiring and correct any possible errors.
3. Test Pressure Sensor for correct operation.
4. Replace the Pressure sensor.
5. If previous steps are correct and fault persists, replace the module.
H or L
1. Check that fl ame is not present in the combustion chamber. Correct
any errors.
2. Make sure that the fl ame detector is wired to the correct terminal.
3. Make sure the F & G wires are protected from stray noise pickup.
4. Reset and sequence the module, if code reappears, replace the fl ame detector.
5. Reset and sequence the module, if code reappears, replace the module.
L
1. Check main valve wiring and operation - correct any errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, fl ame detector, fl ame detector
siting or fl ame rod position.
5. If steps 1 through 4 are correct and the fault persists, replace the module.
L
1. Check main valve wiring and operation - correct any errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, fl ame detector, fl ame detector
siting or fl ame rod position.
5. If steps 1 through 4 are correct and the fault persists, replace the module.
L
1. Check main valve wiring and operation - correct any errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, fl ame detector, fl ame detector
siting or fl ame rod position.
5. If steps 1 through 4 are correct and the fault persists, replace the module.
B
W
RADFORD
HITE