BOILERS AND VOLUME WATER HEATERS
62
Fan speed not
proved
63
LCI (Limit
Control Input)
OFF
64
PII (Pre-Ignition
Interlock) OFF
67
ILK (Interlock)
OFF
68
ILK (Interlock)
ON
70
Wait for leakage
test completion
78
Demand Lost in
Run
79
Outlet high limit
80
DHW (Domestic
Hot Water) high
limit
81
Delta T limit
82
Stack limit
91
Inlet sensor fault
92
Outlet sensor
fault
93
DHW (Domestic
Hot Water)
sensor fault
H
Will not be a lockout fault. Hold Only.
H
1. Check wiring and correct any faults.
2. Check Interlocks connected to the LCI to assure proper function.
3. Reset and sequence the module; monitor the LCI status.
4. If code persists, replace the module
H or L
1. Check wiring and correct any faults.
2. Check Preignition Interlock switches to assure proper functioning.
3. Check the valve operation.
4. Reset and sequence the module; monitor the PII status.
5. If code persists, replace the module.
H or L
1. Check wiring and correct any possible shorts.
2. Check Interlock (ILK) switches to assure proper function.
3. Verify voltage through the interlock string to the interlock input with a
voltmeter.
4. If steps 1-3 are correct and the fault persists, replace the module.
H or L
1. Check wiring and correct any possible shorts.
2. Check Interlock (ILK) switches to assure proper function.
3. Verify voltage through the interlock string to the interlock input with a
voltmeter.
4. If steps 1-3 are correct and the fault persists, replace the module.
H
1. Internal Fault. Reset module.
2. If fault repeats, replace module.
H
1. Check wiring and correct any possible errors.
2. If previous steps are correct and fault persists, replace the module.
H or L
1. Check wiring and correct any possible errors.
2. Replace the outlet high limit.
3. If previous steps are correct and fault persists, replace the module.
H or L
1. Check wiring and correct any possible errors.
2. Replace the DHW high limit.
3. If previous steps are correct and fault persists, replace the module.
H or L
1. Check inlet and outlet sensors and pump circuits for proper operation.
2. Recheck the Delta T Limit to confi rm proper setting.
3. If previous steps are correct and fault persists, replace the module.
H or L
1. Check wiring and correct any possible errors.
2. Replace the Stack high limit.
3. If previous steps are correct and fault persists, replace the module.
H
1. Check wiring and correct any possible errors.
2. Replace the Inlet sensor.
3. If previous steps are correct and fault persists, replace the module.
H
1. Check wiring and correct any possible errors.
2. Replace the Outlet sensor.
3. If previous steps are correct and fault persists, replace the module.
H
1. Check wiring and correct any possible errors.
2. Replace the DHW sensor.
3. If previous steps are correct and fault persists, replace the module.