Brute
BOILERS AND VOLUME WATER HEATERS
165
Block intake
OFF
172
Main relay
feedback
incorrect
174
Safety relay
feedback
incorrect
175
Safety relay
open
176
Main relay ON
at safe start
check
178
Safety relay
ON at safe start
check
184
Invalid
BLOWER/ HSI
output setting
185
Invalid Delta
T limit enable
setting
186
Invalid Delta T
limit response
setting
187
Invalid DHW
(Domestic Hot
Water) high
limit enable
setting
188
Invalid DHW
(Domestic Hot
Water) high
limit response
setting
189
Invalid fl ame
sensor type
setting
L
1. Check wiring and correct any errors.
2. Inspect the Block Intake Switch to make sure it is working correctly.
3. Reset and sequence the module.
4. During Standby and Purge, measure the voltage across the switch.
Supply voltage should be present. If not, the Block Intake Switch is
defective and needs replacing.
5. If the fault persists, replace the relay module.
L
Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
L
Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
L
Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
L
Internal Fault.
1. Reset Module.
2. If fault repeats, replace module.
L
Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.