8.10.2 – Adjusting CO
See Section 8.10
GAS TYPE
HIGH FIRE, CO
Natural
8.8 to 9.8%
Propane
9.8 to 10.2%
Table 14. (Residential, sizes 150 - 285 Mbtu)
CO
Range and Differential Pressure
2
GAS TYPE
HIGH FIRE, CO
Natural
8.8 to 9.0%
Propane
9.8 to 10.0%
Table 15. ( Commercial, sizes 399 - 850 Mbtu)
CO
Range and Manifold Pressure
2
Figure 41. Brute Gas Valves (ALL)
2
LOW FIRE, CO
DIFFRNTL PRESSURE
2
2
(inches wc)
0.5% lower than
3.6" to 3.9"
high fire setting
LOW FIRE, CO
MANIFOLD
2
2
PRESSURE
0.5% lower than
-.005" to
high fire setting
-.015" wc