Toshiba MMU-AP0072H2UL Engineering Data Book page 112

208/230 v, 60 hz; 460 v, 60 hz
Hide thumbs Also See for MMU-AP0072H2UL:
Table of Contents

Advertisement

6
Indoor unit
6.
Electrical current characteristics
Type
Model
MMU-AP0072H2UL
MMU-AP0092H2UL
MMU-AP0122H2UL
MMU-AP0152H2UL
4-Way
MMU-AP0182H2UL
Cassette
MMU-AP0212H2UL
type
MMU-AP0242H2UL
MMU-AP0302H2UL
MMU-AP0362H2UL
MMU-AP0422H2UL
MCA: Minimum Circuit Amps
MOCP: Maximum Overcurrent Protection (Amps)
Voltage Range
Nominal Voltage
(V-Ph-Hz)
Min
208/230-1-60
187
208/230-1-60
187
208/230-1-60
187
208/230-1-60
187
208/230-1-60
187
208/230-1-60
187
208/230-1-60
187
208/230-1-60
187
208/230-1-60
187
208/230-1-60
187
FLA: Full Load Amps
111
Power
(V)
consumption
Max
kW
253
0.021
253
0.021
253
0.023
253
0.026
253
0.026
253
0.036
253
0.036
253
0.043
253
0.088
253
0.112
FLA
MCA
MOCP
A
A
A
0.6
0.8
15
0.6
0.8
15
0.6
0.8
15
0.6
0.8
15
0.6
0.8
15
0.8
1.0
15
0.8
1.0
15
0.8
1.0
15
1.0
1.3
15
1.0
1.3
15

Hide quick links: