Applied Control For Outdoor Unit - Toshiba MMU-AP0072H2UL Engineering Data Book

208/230 v, 60 hz; 460 v, 60 hz
Hide thumbs Also See for MMU-AP0072H2UL:
Table of Contents

Advertisement

5
Outdoor unit

5-8. Applied control for outdoor unit

5-8-1. Outdoor fan high static pressure shift
Purpose / characteristics
This function is used when connecting a duct to the discharge port of an outdoor unit (as part of, for example, unit
installation on the floor by floor installation.)
Setup
Turn ON the DIP switch [SW10, Bit 2] provided on the interface P.C. board of the outdoor unit.
This function must be enabled with every discharge duct connected outdoor unit for both of the header and follower
units.
Specification
Increase the speed of the propeller fan units on the outdoor fan to allow the installation of a duct with a maximum
external static pressure not greater than specified in the table below. If a discharge duct with a resistance greater
than 0.06 InWG (15 Pa) is to be used, enable this function. The maximum external static pressures of base units are
shown below (Table 1, 3).
Table 1: Maximum External Static Pressures of Base Outdoor Units
Model
Heat
Maximum external static pressure
recovery
(*) Outdoor unit air flow
(*) Calculate duct resistance from outdoor unit air flow.
Table 2: Maximum External Static Pressures for Combined Use of Base Units
Model name
Capacity
type
208/230 V model
072
MAP0724FT9UL
096
MAP0964FT9UL
120
MAP1204FT9UL
144
AP1444FT9UL
168
AP1684FT9UL
192
AP1924FT9UL
216
AP2164FT9UL
240
AP2404FT9UL
288
AP2884FT9UL
312
AP3124FT9UL
Heat
recovery
336
AP3364FT9UL
460 V model
072
MAP0724FT6UL
096
MAP0964FT6UL
120
MAP1204FT6UL
144
AP1444FT6UL
168
AP1684FT6UL
192
AP1924FT6UL
216
AP2164FT6UL
240
AP2404FT6UL
288
AP2884FT6UL
312
AP3124FT6UL
336
AP3364FT6UL
MMY-
(CFM)
MMY-
Unit 1
MAP0724FT9UL
MAP0964FT9UL
MAP1204FT9UL
MAP0724FT9UL
MAP0964FT9UL
MAP0964FT9UL
MAP1204FT9UL
MAP1204FT9UL
MAP0964FT9UL
MAP1204FT9UL
MAP1204FT9UL
MAP0724FT6UL
MAP0964FT6UL
MAP1204FT6UL
MAP0724FT6UL
MAP0964FT6UL
MAP0964FT6UL
MAP1204FT6UL
MAP1204FT6UL
MAP0964FT6UL
MAP0964FT6UL
MAP1204FT6UL
MAP0724FT9UL/6UL
MAP0964FT9UL/6UL
0.20 InWG
5120
Combination of outdoor units
Unit 2
MAP0724FT9UL
MAP0724FT9UL
MAP0964FT9UL
MAP0964FT9UL
MAP1204FT9UL
MAP0964FT9UL
MAP0964FT9UL
MAP1204FT9UL
MAP0724FT6UL
MAP0724FT6UL
MAP0964FT6UL
MAP0964FT6UL
MAP1204FT6UL
MAP0964FT6UL
MAP0964FT6UL
MAP1204FT6UL
83
MAP1204FT9UL/6UL
0.16 InWG
0.16 InWG
7060
Maximum external
static pressure (in WG)
Unit 3
MAP0964FT9UL
MAP0964FT9UL
MAP0964FT9UL
MAP0964FT6UL
MAP0964FT6UL
MAP0964FT6UL
7620
0.20
0.16
0.16
0.20
0.16
0.16
0.16
0.16
0.16
0.16
0.16
0.20
0.16
0.16
0.20
0.16
0.16
0.16
0.16
0.16
0.16
0.16