4
Wiring Design
460 V model
Unit
Capacity
Model name
type
type
MMY-
MAP0724FT6U 3 ~ 60 Hz
72
MAP0964FT6U 3 ~ 60 Hz
96
MAP1204FT6U 3 ~ 60 Hz
120
144
AP1444FT6UL 3 ~ 60 Hz
168
AP1684FT6UL 3 ~ 60 Hz
192
AP1924FT6UL 3 ~ 60 Hz
216
AP2164FT6UL 3 ~ 60 Hz
240
AP2404FT6UL 3 ~ 60 Hz
288
AP2884FT6UL 3 ~ 60 Hz
312
AP3124FT6UL 3 ~ 60 Hz
336
AP3364FT6UL 3 ~ 60 Hz
Notes
MCA: Minimum Circuit Amps (minimum circuit Amps requires for power supply design.)
MOCP: Maximum Overcurrent Protection (Amps)
Voltage
Power supply
Phase
Min.
Rated
and
voltage
(V)
frequenc
460 V
414
460 V
414
460 V
414
460 V
414
460 V
414
460 V
414
460 V
414
460 V
414
460 V
414
460 V
414
460 V
414
Compressor
Unit
Unit
Max.
Unit No.3
(V)
(kW)
(kW)
506
2.3 × 2
506
2.1 × 3
506
2.7 × 3
506
2.3 × 2
2.3 × 2
506
2.1 × 3
2.3 × 2
506
2.1 × 3
2.1 × 3
506
2.7 × 3
2.1 × 3
506
2.7 × 3
2.7 × 3
506
2.1 × 3
2.1 × 3
2.1 × 3
506
2.7 × 3
2.1 × 3
2.1 × 3
506
2.7 × 3
2.7 × 3
2.1 × 3
30
Fan Motor
MCA
(kW)
(kW)
(A)
1.0
19
1.0
28
1.0
30
1.0 × 2
19 + 19
1.0 × 2
28 + 19
1.0 × 2
28 + 28
1.0 × 2
30 + 28
1.0 × 2
30 + 30
1.0 × 3
28 + 28 + 28 35 + 35 + 35
1.0 × 3
30 + 28 + 28 35 + 35 + 35
1.0 × 3
30 + 30 + 30 35 + 35 + 35
MOCP
(A)
25
35
35
25 + 25
35 + 25
35 + 35
35 + 35
35 + 35

Hide quick links: