Toshiba MMU-AP0072H2UL Engineering Data Book page 166

208/230 v, 60 hz; 460 v, 60 hz
Hide thumbs Also See for MMU-AP0072H2UL:
Table of Contents

Advertisement

6
Indoor unit
6.
Electrical current characteristics
Type
Model
MMD-AP0074BH2UL
MMD-AP0094BH2UL
MMD-AP0124BH2UL
MMD-AP0154BH2UL
Medium
MMD-AP0184BH2UL
Static
MMD-AP0214BH2UL
Ducted
MMD-AP0244BH2UL
type
MMD-AP0304BH2UL
MMD-AP0364BH2UL
MMD-AP0424BH2UL
MMD-AP0484BH2UL
MCA: Minimum Circuit Amps
MOCP: Maximum Overcurrent Protection (Amps)
Voltage Range
Nominal Voltage
(V-Ph-Hz)
Min
208/230-1-60
187
208/230-1-60
187
208/230-1-60
187
208/230-1-60
187
208/230-1-60
187
208/230-1-60
187
208/230-1-60
187
208/230-1-60
187
208/230-1-60
187
208/230-1-60
187
208/230-1-60
187
FLA: Full Load Amps
165
Power
(V)
consumption
Max
kW
253
0.038
253
0.038
253
0.042
253
0.091
253
0.091
253
0.091
253
0.091
253
0.106
253
0.106
253
0.142
253
0.142
FLA
MCA
MOCP
A
A
A
0.8
1.0
15
0.8
1.0
15
0.8
1.0
15
0.9
1.2
15
0.9
1.2
15
1.4
1.8
15
1.4
1.8
15
1.4
1.8
15
1.8
2.3
15
2.2
2.8
15
2.2
2.8
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents