Toshiba MMU-AP0072H2UL Engineering Data Book page 93

208/230 v, 60 hz; 460 v, 60 hz
Hide thumbs Also See for MMU-AP0072H2UL:
Table of Contents

Advertisement

5
Outdoor unit
Model
Appearance
name
Size: 2.87 × 3.11 (in)
Application
* Install the optional
PCB in the inverter
assembly of the
outdoor header unit.
[3] Operating Rate Output
Function
The state of operation is available to check remotely as the signal of
system operation rate enable to output.
Operation
As shown in the table, each of the output terminals turns ON (relay
closes) and OFF (relay opens) depending on the system operating rate.
Functions
SW16
OUTPUT1 OUTPUT2 OUTPUT3 Operating rate FA
OFF
ON
OFF
ON
System
OFF
ON
1
2 3 4
operating
OFF
rate output bit 1: ON
ON
bit 2: OFF
OFF
ON
Wiring example
Header outdoor unit
Optional PCB
Outdoor unit
interface PCB
C2
SW16
CN514
PJ20
ON
OFF
1
2 3 4
C2
Attached connection cable 2 (5wires)
CN514
Connector on interface side (green)
K1, K2, K3
Relays
MONITOR
Monitoring device
OUTPUT1
Output terminal for each function
OUTPUT2
Output terminal for each function
OUTPUT3
Output terminal for each function
PJ20
Connector on optional PCB side
TB1
Terminal block
92
Function
OFF
OFF
FA = 0%
OFF
OFF
0% < FA < 20%
20% ≤ FA < 35%
ON
OFF
35% ≤ FA < 50%
ON
OFF
50% ≤ FA < 65%
OFF
ON
65% ≤ FA < 80%
OFF
ON
80% ≤ FA < 95%
ON
ON
95% ≤ FA
ON
ON
OFF=relay open ON=relay closed
Locally procured
TB1
1
K1
OUTPUT1
2
3
K2
OUTPUT2
MONITOR
4
5
K3
OUTPUT3
6
Shield
wire