Toshiba MMU-AP0072H2UL Engineering Data Book page 163

208/230 v, 60 hz; 460 v, 60 hz
Hide thumbs Also See for MMU-AP0072H2UL:
Table of Contents

Advertisement

6
Indoor unit
2.
Dimensions
MMD-AP0074BH2UL, AP0094BH2UL, AP0124BH2UL, AP0154BH2UL, AP0184BH2UL, AP0214BH2UL,
AP0244BH2UL, AP0304BH2UL, AP0364BH2UL, AP0424BH2UL, AP0484BH2UL
Air filter slot
12"(300) or less
Drain-up piping
Model
AP0074BH2UL, AP0094BH2UL,
AP0124BH2UL
AP0154BH2UL, AP0184BH2UL
AP0214BH2UL, AP0244BH2UL,
AP0304BH2UL, AP0364BH2UL,
AP0424BH2UL, AP0484BH2UL
Hanging bolt pitch A
0.3"
Unit external dimension B
Air discharge flange outside
C
Hanging bolt 4-M0.4"(10)
(locally procured)
Air intake flange outside
D
Z view
Space required for installation and servicing
Reserve space required for maintenance the indoor unit and service work.
Unit width B
Air discharge
Ceiling opening size E
Ceiling
Air discharge
5.9"(150) or more
Check port B
17.7"X17.7"
(450X450)
Space required for attaching or
Electrical control box
detaching the filter F
Notes)
* Set check port A for maintaining the electrical control box, filter, drain pump, drain pipe, and refrigerant pipe.
* Replace the filter through check port A or B.
(If you pull out the filter in the opposite direction of the electrical control box, check port B is required.)
Reserve space F required for attaching or detaching the filter.
Otherwise, the filter cannot be replaced.
* When pulling the refrigerant pipe, drain pipe, etc, avoid the filter port. Otherwise,the filter cannot be replaced.
* The indoor unit is not equipped with an air filter. Procure and install with locally.
* Set a ceiling opening port for maintaining the fan, fan motor, etc. Otherwise, they cannot be maintained.
MMD-
A
24.3"
(616)
42"
(1066)
55.7"
(1416)
Drain pipe connecting port
VP25(Polyvinyl chloride tube:
External Dia,1-1/4" Internal Dia,1")
1"(25)
1.6"(41)
5.5"(140)
1.7"(44)
1.9"(49)
Air discharge
side
Refrigerant pipe
connecting port G
(Gas side)
Refrigerant pipe
connecting port H
(Liquid side)
Air discharge
side
Electrical control box
Electrical
control box
31.5"(800)
5.9"(150)
Ceiling opening size
Ceiling
38.6"(980)
Drain pan / Drain
pump check cover
*1 In the case of under air intake type.
: 17.7"(450)(Min.)
Ceiling opening size
Air filter
5.9"(150) or more
(locally procured)
Check port A
17.7"X17.7"
(450X450)
Space required for attaching or
detaching the filter F
B
C
D
21.7"
13.9"
18.6"
(550)
(351.6)
(471.6)
39.4"
31.6"
36.3"
(1000)
(801.6)
(921.6)
53.2"
45.4"
50.1"
(1350)
(1151.6)
(1271.6)
162
Unit external dimension 31.5"(800)
Hanging bolt pitch 27.6"(700)
2"(50)
25.1"(638)
19.6"(498)
15.1"(384)
1"(26) Hole for control wire
and remote control wiring
7/8"(22.2) Hole for power supply cable
<Under air intake type>
For air intake from under air intake, be sure to attach a separately-sold fan guard.
9.6"(243.2)
12.6"(320)
Air intake
side
Air filter
(locally procured)
Air intake
1.2"(30)
E
F
G
23.6"
23.6"
Ø3/8"
(550)
(550)
(9.5)
41.3"
23.6"
Ø1/2"
(1050)
(550)
(12.7)
55.1"
40.5"
Ø5/8"
(1400)
(1030)
(15.9)
2.2"(57)
2.4"(59)
1.2"(30)
Air filter slot
Z
Air intake
side
Air filter slot
Air intake flange
6.3"(159)
3.6"(91)
Unit: in (mm)
H
Ø1/4"
(6.4)
Ø1/4"
(6.4)
Ø3/8"
(9.5)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents