Toshiba MMU-AP0072H2UL Engineering Data Book page 106

208/230 v, 60 hz; 460 v, 60 hz
Hide thumbs Also See for MMU-AP0072H2UL:
Table of Contents

Advertisement

6
Indoor unit
2.
Dimensions
MMU-AP0072H2UL, AP0092H2UL, AP0122H2UL
Ceiling bottom
surface
Ceiling
bottom
surface
Knockout for simple OA
For
3.9"(100)
Z view
Ceiling bottom
Indoor unit
surface
Ceiling
bottom
surface
Ceiling panel
33.9" to 35.8"(860 to 910) Ceiling open dimension
33.1"(840) Unit external dimension
Z
27.2±0.8"(690) Hanging bolt pitch
37.4"(950) Panel external dimension
Ceiling panel
(Sold separately)
(
Ceiling bottom surface
Refrigerant pipe
connecting port
(Liquid) Ø 1/4"(6.4)
Electric
Refrigerant pipe
16.1"(408)
parts box
connecting port
(Gas) Ø 3/8"(9.5)
Drain pipe
connecting port
16.4"(416.5)
Hanging bolt 3/8"(M10)
(To be procured locally)
105
7.9"(200)
Check port
(
17.7"(450))
When a fresh-air inlet box is
installed, make check port
at the side of the fresh-air
inlet box.
Check port
17.7"(450))
39.4"(1000)
39.4"(1000)
or more
or more
Space required for installation
6.8"(172)
4.4"
(112)
Hole for power
2.3"
supply cable
(58)
1.7"
Conduit hole(Knockout)
(42)
Hole for remote
controller wires
1.6"
(40)
Ceiling
bottom
7.4"(189)
surface
11.8"(300)
or less
Indoor unit
Ceiling bottom
surface
Drain-up standing-up size
Unit: in (mm)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents