Toshiba MMU-AP0072H2UL Engineering Data Book page 32

208/230 v, 60 hz; 460 v, 60 hz
Hide thumbs Also See for MMU-AP0072H2UL:
Table of Contents

Advertisement

4
Wiring Design
4-2-2. Heat pump
Outdoor unit data
208/230 V model
Unit type Capacity
Model name
type
MMY-
072
MAP0724HT9UL
096
MAP0964HT9UL
114
MAP1144HT9UL
144
AP1444HT9UL
168
AP1684HT9UL
192
AP1924HT9UL
228
AP2284HT9UL
460 V model
Capacity
Model name
Unit type
type
MMY-
072
MAP0724HT6UL
096
MAP0964HT6UL
114
MAP1144HT6UL
144
AP1444HT6UL
168
AP1684HT6UL
192
AP1924HT6UL
228
AP2284HT6UL
Notes
MCA: Minimum Circuit Amps (minimum circuit Amps requires for power supply design.)
MOCP: Maximum Overcurrent Protection (Amps)
Power supply
Min.
Phase and
Nominal
frequency
Voltage
3 ~ 60 Hz
208/230 V
3 ~ 60 Hz
208/230 V
3 ~ 60 Hz
208/230 V
3 ~ 60 Hz
208/230 V
3 ~ 60 Hz
208/230 V
3 ~ 60 Hz
208/230 V
3 ~ 60 Hz
208/230 V
Power supply
Min.
Phase and
Nominal
frequency
Voltage
3 ~ 60 Hz
460 V
3 ~ 60 Hz
460 V
3 ~ 60 Hz
460 V
3 ~ 60 Hz
460 V
3 ~ 60 Hz
460 V
3 ~ 60 Hz
460 V
3 ~ 60 Hz
460 V
31
Voltage Range
Compressor
Max.
Unit No.1 Unit No.2
(V)
(V)
(kW)
187
253
2.3 × 2
187
253
2.1 × 3
187
253
2.5 × 3
187
253
2.3 × 2
187
253
2.1 × 3
187
253
2.1 × 3
187
253
2.5 × 3
Voltage Range
Compressor
Max.
Unit No.1 Unit No.2
(V)
(V)
(kW)
414
506
2.3 × 2
414
506
2.1 × 3
414
506
2.5 × 3
414
506
2.3 × 2
414
506
2.1 × 3
414
506
2.1 × 3
414
506
2.5 × 3
Fan
MCA
Motor
(kW)
(kW)
(A)
1.0
36
1.0
50
1.0
52
2.3 × 2
1.0 × 2
36 + 36
2.3 × 2
1.0 × 2
50 + 36
2.1 × 3
1.0 × 2
50 + 50
2.5 × 3
1.0 × 2
52 + 52
Fan
MCA
Motor
(kW)
(kW)
(A)
1.0
18
1.0
23
1.0
24
2.3 × 2
1.0 × 2
18 + 18
2.3 × 2
1.0 × 2
23 + 18
2.1 × 3
1.0 × 2
23 + 23
2.5 × 3
1.0 × 2
24 + 24
MOCP
(A)
40
60
60
40 + 40
60 + 40
60 + 60
60 + 60
MOCP
(A)
20
25
25
20 + 20
25 + 20
25 + 25
25 + 25

Hide quick links: