Toshiba MMU-AP0072H2UL Engineering Data Book page 123

208/230 v, 60 hz; 460 v, 60 hz
Hide thumbs Also See for MMU-AP0072H2UL:
Table of Contents

Advertisement

6
Indoor unit
11-4 Auxiliary fresh air flange (TCB-FF101URUL)
Installation
1. Using the knockout of the indoor unit main body, as a
marker, cut off the flange with the heat insulator
(styrol) with cutting pliers or cutter.
Cut off the steel plate
with cutting pliers or
the like (4 places).
NOTE
When cutting off the styrol inside, be careful not to insert
the cutter blade deeper than 1.2" (30mm). (Damage to
the drain pan inside can cause water leakage.)
Wear safety globes to carry out these works. Do not
attempt with bare hands.
2. A gap between the styrol and steel plate may cause
a trouble such as condensation. Be sure to attach
the attached heat insulator A first with it aligned to
the screw hole, and then attach B, according to the
right figure.
3. Install the auxiliary fresh air flange to the indoor unit
main body with attached 4 fixing screws.
Auxiliary
Seal heat
fresh air
insulator A
flange
Indoor unit
Seal heat
insulator A
Dimension
3.1" (80)
2.2" (57)
Fixing hole of indoor unit
Cut off the heat
insulator (styrol) with a
cutter (circumference)
Seal heat
Steel plate
insulator B
Styrol
Attach the heat
insulator.
Make sure it is
glued properly.
Seal heat
insulator B
Installation status of indoor unit
122
Duct fan
In order to take fresh air, provide the duct fan
separately.
1. Install the filter for fresh air
2. Provide the check port beneath the duct fan for
maintenance.
3. Connect the duct fan and the indoor unit with inter-
lock wiring.
4. Provide the silencer to prevent the effect of noise.
Silencer (Chamber)
Check port
Indoor unit
Duct fan
Treated
fresh air
Filter for fresh air
Unit : in (mm)
0.1" (3)
3.5" (90)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents