Input Current Control - Daikin FLXS-BAVMB Service Manual

Floor / ceiling suspended dual type ba-series
Hide thumbs Also See for FLXS-BAVMB:
Table of Contents

Advertisement

SiBE05-722_B
3.5

Input Current Control

Outline
The microcomputer calculates the input current during the compressor is running, and sets the
frequency upper limit from the input current.
In case of heat pump model, this control which is the upper limit control of the frequency takes
priority to the lower limit of control of four way valve operation compensation.
Detail
Frequency control in each zone
Stop zone
Drooping zone
Keep zone
Reset zone
Limitation of current drooping and stop value according to the outdoor temperature
Function and Control
A
B
C
After 2.5 seconds in this zone, the compressor is stopped.
The upper limit of the compressor frequency is defined as operation frequency – 2 Hz.
After this, the output frequency is pulled down by 2 Hz every second until it reaches the keep
zone.
The present maximum frequency goes on.
Limit of the frequency is canceled.
RK(X)S25E2V1B
Cooling
Heating
A
(A)
9.25
B
(A)
6.0
7.5
C
(A)
5.25
6.75
RK(X)S35E2V1B
RK(X)S35G2V1B
Cooling
Heating
A
(A)
9.25
B
(A)
7.25
8.25
C
(A)
6.5
7.5
The current droops when outdoor temperature becomes higher than a certain level
(depending on the model).
Compressor Stop
RK(X)S25G2V1B9
RK(X)S25G2V1B
Cooling
Heating
Cooling
9.25
6.5
7.5
6.25
5.75
6.75
5.5
RK(X)S35G2V1B9
RXS35J2V1B
Cooling
Heating
9.25
8.25
7.5
Control Specification
Stop Zone
Drooping Zone
Keep Zone
Reset Zone
(R13572)
RXS25J2V1B
Heating
9.25
7.5
6.75
42