Thermistor Resistance Check - Daikin FLXS-BAVMB Service Manual

Floor / ceiling suspended dual type ba-series
Hide thumbs Also See for FLXS-BAVMB:
Table of Contents

Advertisement

SiBE05-722_B
5.3

Thermistor Resistance Check

Check No.06
Disconnect the connectors of the thermistors from the PCB, and measure the resistance of
each thermistor using tester.
The relationship between normal temperature and resistance is shown in the table and the
graph below.
Service Diagnosis
Thermistor temperature (°C)
–20
–15
–10
–5
0
5
10
15
20
25
30
35
40
45
50
(kΩ)
150
100
50
For the models in which the thermistor is directly mounted on the PCB, disconnect the
connector for the PCB and measure.
Resistance (kΩ)
211.0
150.0
116.5
88.0
67.2
51.9
40.0
31.8
25.0
20.0
16.0
13.0
10.6
8.7
7.2
(R25°C = 20 kΩ, B = 3950 K)
-15
0
15
30
RTH1
Tester
(R3460)
45
(˚C)
(R11905)
Tester
Resistance range
(R11906)
Check