Control Specification
3.4

Discharge Pipe Temperature Control

Outline
The discharge pipe temperature is used as the internal temperature of the compressor. If the
discharge pipe temperature rises above a certain level, the upper limit of frequency is set to
keep this temperature from going up further.
Detail
41
B˚C
C˚C
D˚C
Discharge pipe
temperature
Zone
Stop zone
When the temperature reaches the stop zone, the compressor stops.
Drooping zone
The timer starts, and the frequency is drooping.
Keep zone
The upper limit of frequency is kept.
Up zone
The upper limit of frequency is increased.
Reset zone
The upper limit of frequency is canceled.
A (ºC)
110
B (ºC)
105
C (ºC)
101
D (ºC)
99
E (ºC)
97
SiBE05-722_B
Stop zone
A˚C
Drooping zone
Keep zone
Up zone
E˚C