Service Check Function
Check Method 2
1. Press the center of the TEMP button and the MODE button at the same time.
2. Press the TEMP▲ or ▼ button and change the figure until you hear the sound of "beep" or
3. Diagnose by the sound.
4. Press the MODE button.
67
The figure of the ten's place blinks.
"pi pi".
"pi" : The figure of the ten's place does not accord with the error code.
"pi pi" : The figure of the ten's place accords with the error code but the one's not.
"beep" : The both figures of the ten's and one's place accord with the error code.
(The figures indicated when you hear the "beep" sound are error code.
Refer to page 69.)
The figure of the one's place blinks.
SiBE05-722_B
(R4272)
(R4273)
(R4274)
(R4275)
(R4276)
Service Diagnosis