Discharge Pipe Temperature Control - Daikin FLXS-BAVMB Service Manual

Floor / ceiling suspended dual type ba-series
Hide thumbs Also See for FLXS-BAVMB:
Table of Contents

Advertisement

SiBE05-722_B

4.14 Discharge Pipe Temperature Control

F3
Remote
Controller
Display
Method of
An error is determined with the temperature detected by the discharge pipe thermistor.
Malfunction
Detection
Malfunction
Decision
Conditions
Stop temperatures
(1) above 45 Hz (rising), above 40 Hz (dropping)
(2) 30 ~ 45 Hz (rising), 25 ~ 40 Hz (dropping)
(3) below 30 Hz (rising), below 25 Hz (dropping)
Supposed
Causes
Troubleshooting
Check No.04
Refer to P.104
Check No.06
Refer to P.106
Check No.11
Refer to P.108
Service Diagnosis
If the temperature detected by the discharge pipe thermistor rises above A°C, the
compressor stops.
The error is cleared when the discharge pipe temperature has dropped below B°C.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Defective discharge pipe thermistor
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
Defective electronic expansion valve or coil
Refrigerant shortage
Defective four way valve
Water mixed in refrigerant
Defective stop valve
Defective outdoor unit PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check No. 06
Check the thermistors.
OK
Check No. 04
Check the electronic
expansion valve.
OK
Check No. 11
Check the refrigerant
line.
OK
A (°C)
110
105
99
NG
Discharge pipe thermistor
Outdoor heat exchanger thermistor
Outdoor temperature thermistor
NG
NG
Refrigerant shortage
Four way valve
Water mixed
Stop valve
Troubleshooting
B (°C)
97
92
86
Replace the
defective
thermistor.
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB.
(R7141)
84

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents