Model FDC100VN
Item
Power source
Nominal cooling capacity
( 1)
Nominal heating capacity
( 1)
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
Refrigerant equipment
compressor type & Q' ty
Starting method
Crankcase heater
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
Defrost control
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air flow(Standard)
Shock & vibration absorber
Safety equipment
Installation data
Refrigerant piping size
Connecting method
Drain
Insulation for piping
Accessories
Notes
(1) The cooling and heating capabilities imply the values when the indoor unit of rated capacity is connected under the condition specified in ISO-T1.
(2) The refrigerant quantity in the connecting pipe is not included. Charge it additionally at the site.
(3) Values in [
~
] show the minimum and maximum capacities.
Model
kW
kW
dB(A)
mm
kg
W
kg
W
CMM
mm(in)
-
FDC100VN
1 Phase, 220-240V 50Hz/220V 60Hz
10.0 [4.0~11.2]
11.2 [4.0~12.5]
49
845
970
74
RMT5126MDE2 1
Direct line start
20
Straight fin & inner grooved tubing
Electronic expansion valve
R410A
3.8 (Pre-charged up to the piping length of 30m)
0.9 (M-MA68)
Microcomputer controlled de-icer
Propeller fan 1
86 1
Direct line start
Cooling: 75, Heating: 73
Rubber sleeve (for compressor)
Internal thermostat for fan motor.
Anomalous discharge temperature protection.
Liquid line: 9.52 (3/8")
Flare piping
Hole size 20 3pcs.
Necessary (both Liquid & Gas lines)
Edging
336
-
370
Gas line: 15.88 (5/8")