T ECHNI CAL M A N U A L
Col l ect i on da ta
PACKAGED AIR-CONDITIONER
(Split system, Air to air heat pump type)
CEILING RECESSED COMPACT TYPE
FDTCVA151HEN1R
FDTCVA302HENP1R
201HEN1R
CEILING RECESSED TYPE
FDTVA151HEN1R
FDTVA302HENP1R
201HEN1R
251HEN1R
302HEN1R
402HEN2R
402HES2R
502HEN2R
502HES2R
602HEN2R
602HES2R

WALL MOUNTED TYPE

FDKNVA151HEN1R
FDKNVA302HENP1R
201HEN1R
251HEN1R
MULTI-TYPE (V-MULTI)
PACKAGED AIR-CONDITIONER
(OUTDOOR UNIT)
FDCVA302HENR
402HENAR
402HESAR
502HENAR
502HESAR
602HENAR
602HESAR
802HESAR
1002HESAR
FDTCVA602HENT2R
402HENP2R
602HEST2R
402HESP2R
FDTVA602HENT2R
402HENP2R
602HEST2R
402HESP2R
802HEST2R
502HENP2R
502HESP2R
FDTVA802HESD2R
602HENP2R
1002HESD2R
602HESP2R
802HESP2R
1002HESP2R
FDKNVA602HENT2R
402HENP2R
602HEST2R
402HESP2R
502HENP2R
502HESP2R
(INDOOR UNIT)
FDTCA151R
201R
CEILING SUSPENDED TYPE
FDENVA151HEN1R
201HEN1R
251HEN1R
302HEN1R
402HEN2R
402HES2R
502HEN2R
502HES2R
602HEN2R
602HES2R
SATELLITE DUCTED TYPE
FDUMVA201HEN2R
251HEN2R
302HEN2R
402HEN2R
402HES2R
502HEN2R
502HES2R
602HEN2R
602HES2R

HIGH STATIC PRESSURE DUCT TYPE

FDUVA802HES2R
1002HES2R
FDEN A 151R
FDTA151R
201R
201R
251R
251R
301R
301R
401R
401R
501R
501R
Manual No. '07·PAC-T-115
updated 3,October,2008
FDENVA302HENP1R
FDENVA602HENT2R
402HENP2R
402HESP2R
502HENP2R
502HESP2R
602HENP2R
602HESP2R
802HESP2R
1002HESP2R
FDUMVA402HENP2R
FDUMVA602HENT2R
402HESP2R
502HENP2R
502HESP2R
602HENP2R
602HESP2R
802HESP2R
1002HESP2R
FDKNA151R
201R
251R
602HEST2R
802HEST2R
602HEST2R
802HEST2R
FDUMA202R
252R
302R
402R
502R

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Heavy Industries FDTCVA151HEN1R

  • Page 1: Wall Mounted Type

    T ECHNI CAL M A N U A L Col l ect i on da ta PACKAGED AIR-CONDITIONER (Split system, Air to air heat pump type) CEILING RECESSED COMPACT TYPE CEILING SUSPENDED TYPE FDTCVA151HEN1R FDTCVA302HENP1R FDTCVA602HENT2R FDENVA151HEN1R FDENVA302HENP1R FDENVA602HENT2R 201HEN1R...
  • Page 2: Packaged Air-Conditioner .................................................................................... 2

    TABLE OF CONTENTS 1. PACKAGED AIR-CONDITIONER ..................2 2. MULTI-TYPE (V MULTI) PACKAGED AIR-CONDITIONER ........291 3. WIRELESS KIT (OPTIONAL PARTS) ................318...
  • Page 3: Table Of Contents

    1. PACKAGED AIR-CONDITIONER CONTENTS 1.1 GENERAL INFORMATION ................... 4 1.1.1 Specifi c features ...................... 4 1.1.2 How to read the model name ................... 4 1.2 SELECTION DATA ......................5 1.2.1 Specifications ......................5 (1) Ceiling recessed compact type (FDTC) ..............5 (2) Ceiling recessed type (FDT) ..................
  • Page 4 (4) Operation control function by the outdoor controller ..........166 ♦ Models FDCVA151 ~ 251 ..................166 ♦ Models FDCVA302 ~ 1002 ................... 172 1.5 APPLICATION DATA ....................184 1.5.1 Installation of indoor unit ..................185 (1) Ceiling recessed compact type (FDTC) ............... 185 (2) Ceiling recessed type (FDT) ................
  • Page 5: General Information

    (3) Energy labeling “Class A” MHI models have cleared the class A standard, the highest energy saving level, with their high COP (coeffi cient of performance). (4) The microcomputer chip is installed in the indoor unit and outdoor unit. There is no need for the unit to communicate between the outdoor and indoor units so the unit is more resistant to electromagnetic noise thus the incidence of microcomputer malfunction has been reduced.
  • Page 6: Selection Data

    SELECTION DATA 1.2.1 Specifications (1) Ceiling recessed compact type (FDTC) (a) Single type Model FDTCVA151HEN1R FDTCVA151HEN1R Model Item FDTCA151R FDCVA151HENR Nominal cooling capacity 4.0 [1.8~4.7] Nominal heating capacity 4.5 [2.0~5.4] Power source 1 Phase, 220-240V 50Hz/220V 60Hz 1.22/1.22 Cooling power consumption Running current (Cooling) 5.4/5.6...
  • Page 7 Model FDTCVA201HEN1R FDTCVA201HEN1R Model Item FDTCA201R FDCVA201HENR Nominal cooling capacity 5.0 [2.2~5.6] Nominal heating capacity 5.4 [2.5~6.3] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 1.62 /1.62 Running current (Cooling) 7.1/7.5 Power factor (Cooling) 99/98 Heating power consumption 1.53/1.53 6.7/7.0 Running current (Heating)
  • Page 8 (b) Twin type Model FDTCVA302HENP1R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDTCVA302HENP1R Model Item FDTCA151R FDCVA302HENR Nominal cooling capacity 7.1[3.9~8.0] Nominal heating capacity 8.0[4.0~9.0] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 1.91/1.91 Running current (Cooling) 8.3/8.8 Power factor (Cooling) 99/99...
  • Page 9 Model FDTCVA402HENP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDTCVA402HENP2R Model Item FDTCA201R FDCVA402HENAR Nominal cooling capacity 10.0 [6.1~11.2] Nominal heating capacity 11.2 [5.6~12.5] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 2.84/2.84 Running current (Cooling) 12.4/13.0 Power factor (Cooling) 99/99 Heating power consumption...
  • Page 10 Model FDTCVA402HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDTCVA402HESP2R Model Item FDTCA201R FDCVA402HESAR Nominal cooling capacity 10.0 [6.1~11.2] Nominal heating capacity 11.2 [5.6~12.5] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 2.84/2.84 Running current (Cooling) 4.2/4.4 Power factor (Cooling) 98/98 Heating power consumption...
  • Page 11 (c) Triple type Model FDTCVA602HENT2R (Indoor unit: 3 units, Outdoor unit: 1 unit) FDTCVA602HENT2R Model Item FDTCA201R FDCVA602HENAR Nominal cooling capacity 14.0 [6.7~14.8] Nominal heating capacity 16.0 [6.3~16.8] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 4.64/4.64 Running current (Cooling) 20.4/21.3 Power factor (Cooling) 99/99...
  • Page 12 Model FDTCVA602HEST2R (Indoor unit: 3 units, Outdoor unit: 1 unit) FDTCVA602HEST2R Model Item FDTCA201R FDCVA602HESAR Nominal cooling capacity 14.0 [6.7~14.8] Nominal heating capacity 16.0 [6.3~16.8] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 4.64/4.64 Running current (Cooling) 6.8/7.1 Power factor (Cooling) 98/99 Heating power consumption...
  • Page 13: Ceiling Recessed Type (Fdt)

    (2) Ceiling recessed type (FDT) (a) Single type Model FDTVA151HEN1R FDTVA151HEN1R Model Item FDTA151R FDCVA151HENR Nominal cooling capacity 4.0 [1.8~4.7] Nominal heating capacity 4.5 [2.0~5.4] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 1.22/1.23 Running current (Cooling) 5.4/5.7 Power factor (Cooling) 98/98 Heating power consumption...
  • Page 14 Model FDTVA201HEN1R FDTVA201HEN1R Model Item FDTA201R FDCVA201HENR Nominal cooling capacity 5.0 [2.2~5.6] Nominal heating capacity 5.4 [2.5~6.3] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 1.42 /1.43 Running current (Cooling) 6.3/6.6 Power factor (Cooling) 98/98 Heating power consumption 1.49/1.49 6.6/6.9 Running current (Heating)
  • Page 15 Model FDTVA251HEN1R FDTVA251HEN1R Model Item FDTA251R FDCVA251HENR Nominal cooling capacity 5.6 [2.8~6.3] Nominal heating capacity 6.7 [3.1~7.1] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 1.64/1.65 Running current (Cooling) 7.3/7.6 Power factor (Cooling) 98/99 Heating power consumption 1.78/1.79 Running current (Heating) 7.9/8.4 Power factor (Heating)
  • Page 16 Model FDTVA302HEN1R FDTVA302HEN1R Model Item FDTA301R FDCVA302HENR Nominal cooling capacity 7.1[3.9~8.0] Nominal heating capacity 8.0[4.0~9.0] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 1.90/1.91 Running current (Cooling) 8.3/8.8 Power factor (Cooling) 99/99 Heating power consumption 2.07/2.08 9.0/9.6 Running current (Heating) Power factor (Heating) 99/98 Inrush current (L.R.A)
  • Page 17 Model FDTVA402HEN2R FDTVA402HEN2R Model Item FDTA401R FDCVA402HENAR Nominal cooling capacity 10.0 [6.1~11.2] Nominal heating capacity 11.2 [5.6~12.5] Power source 1 Phase, 220-240V 50Hz Cooling power consumption 2.88 Running current (Cooling) 12.6 Power factor (Cooling) Heating power consumption 3.12 13.7 Running current (Heating) Power factor (Heating) Inrush current (L.R.A) Powerful mode Hi:46 Me:43 Lo:41...
  • Page 18 Model FDTVA402HES2R FDTVA402HES2R Model Item FDTA401R FDCVA402HESAR Nominal cooling capacity 10.0 [6.1~11.2] Nominal heating capacity 11.2 [5.6~12.5] Power source 3 Phase, 380-415V 50Hz Cooling power consumption 2.97 Running current (Cooling) Power factor (Cooling) Heating power consumption 2.92 Running current (Heating) Power factor (Heating) Inrush current (L.R.A) Powerful mode Hi:46 Me:43 Lo:41...
  • Page 19 Model FDTAV502HEN2R FDTVA502HEN2R Model Item FDTA501R FDCVA502HENAR Nominal cooling capacity 12.5 [6.5~14.0] Nominal heating capacity 14.0 [6.2~16.0] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 4.05/4.05 Running current (Cooling) 17.7/18.6 Power factor (Cooling) 99/99 Heating power consumption 3.97/3.97 17.4/18.2 Running current (Heating) Power factor (Heating)
  • Page 20 Model FDTAV502HES2R FDTVA502HES2R Model Item FDTA501R FDCVA502HESAR Nominal cooling capacity 12.5 [6.5~14.0] Nominal heating capacity 14.0 [6.2~16.0] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 4.05/4.05 Running current (Cooling) 5.9/6.3 Power factor (Cooling) 99/98 Heating power consumption 3.97/3.97 5.8/6.3 Running current (Heating) Power factor (Heating)
  • Page 21 Model FDTVA602HEN2R FDTVA602HEN2R Model Item FDTA601R FDCVA602HENAR Nominal cooling capacity 14.0 [6.7~14.8] Nominal heating capacity 16.0 [6.3~16.8] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 4.65/4.65 Running current (Cooling) 20.4/21.3 Power factor (Cooling) 99/99 Heating power consumption 4.54/4.54 20.0/20.9 Running current (Heating) Power factor (Heating)
  • Page 22 Model FDTVA602HES2R FDTVA602HES2R Model Item FDTA601R FDCVA602HESAR Nominal cooling capacity 14.0 [6.7~14.8] Nominal heating capacity 16.0 [6.3~16.8] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 4.65/4.65 Running current (Cooling) 6.8/7.3 Power factor (Cooling) 99/97 Heating power consumption 4.54/4.54 Running current (Heating) 6.7/7.4 Power factor (Heating)
  • Page 23 (b) Twin type Model FDTVA302HENP1R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDTVA302HENP1R Model Item FDTA151R FDCVA302HENR Nominal cooling capacity 7.1[3.9~8.0] Nominal heating capacity 8.0[4.0~9.0] Power source 1 Phase, 220-240V 50Hz/220V 60Hz 1.85/1.87 Cooling power consumption 8.0/8.6 Running current (Cooling) 99/99 Power factor (Cooling) 1.99/1.99...
  • Page 24 Model FDTVA402HENP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDTVA402HENP2R Model Item FDTA201R FDCVA402HENAR Nominal cooling capacity 10.0 [6.1~11.2] Nominal heating capacity 11.2 [5.6~12.5] Power source 1 Phase, 220-240V 50Hz Cooling power consumption 2.94/2.96 Running current (Cooling) 12.9/13.7 Power factor (Cooling) 99/98 Heating power consumption 3.09/3.09...
  • Page 25 Model FDTVA402HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDTVA402HESP2R Model Item FDTA201R FDCVA402HESAR Nominal cooling capacity 10.0 [6.1~11.2] Nominal heating capacity 11.2 [5.6~12.5] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 2.94/2.96 Running current (Cooling) 4.3/4.6 Power factor (Cooling) 99/98 Heating power consumption...
  • Page 26 Model FDTVA502HENP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDTVA502HENP2R Model Item FDTA251R FDCVA502HENAR Nominal cooling capacity 12.5 [6.5~14.0] Nominal heating capacity 14.0 [6.2~16.0] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 4.29/4.31 Running current (Cooling) 18.9/20.0 Power factor (Cooling) 99/98 Heating power consumption...
  • Page 27 Model FDTVA502HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDTVA502HESP2R Model Item FDTA251R FDCVA502HESAR Nominal cooling capacity 12.5 [6.5~14.0] Nominal heating capacity 14.0 [6.2~16.0] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 4.29/4.31 Running current (Cooling) 6.3/6.7 Power factor (Cooling) 98/98 Heating power consumption...
  • Page 28 Model FDTVA602HENP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDTVA602HENP2R Model Item FDTA301R FDCVA602HENAR Nominal cooling capacity 14.0 [7.0~14.5] Nominal heating capacity 16.0 [6.3~16.5] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 4.69/4.71 Running current (Cooling) 20.5/21.6 Power factor (Cooling) 99/99 Heating power consumption...
  • Page 29 Model FDTVA602HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDTVA602HESP2R Model Item FDTA301R FDCVA602HESAR Nominal cooling capacity 14.0 [7.0~14.5] Nominal heating capacity 16.0 [6.3~16.5] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 4.69/4.71 Running current (Cooling) 6.9/7.2 Power factor (Cooling) 98/99 Heating power consumption...
  • Page 30 Model FDTVA802HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDTVA802HESP2R Model Item FDTA401R FDCVA802HESAR Nominal cooling capacity 20.0 [7.0~22.4] Nominal heating capacity 22.4 [7.6~25.0] Power source 3 Phase, 380-415V 50Hz Cooling power consumption 6.60 Running current (Cooling) Power factor (Cooling) Heating power consumption 6.46 Running current (Heating)
  • Page 31 Model FDTVA1002HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDTVA1002HESP2R Model Item FDTA501R FDCVA1002HESAR Nominal cooling capacity 25.0 [10.6~28.0] Nominal heating capacity 28.0 [9.5~31.5] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 8.12/8.12 Running current (Cooling) 12.2/12.8 Power factor (Cooling) 96/96 Heating power consumption...
  • Page 32 (c) Triple type Model FDTVA602HENT2R (Indoor unit: 3 units, Outdoor unit: 1 unit) FDTVA602HENT2R Model Item FDTA201R FDCVA602HENAR Nominal cooling capacity 14.0 [7.0~14.5] Nominal heating capacity 16.0 [6.3~16.5] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 4.74/4.77 Running current (Cooling) 20.8/22.1 Power factor (Cooling) 99/98...
  • Page 33 Model FDTVA602HEST2R (Indoor unit: 3 units, Outdoor unit: 1 unit) FDTVA602HEST2R Model Item FDTA201R FDCVA602HESAR Nominal cooling capacity 14.0 [7.0~14.5] Nominal heating capacity 16.0 [6.3~16.5] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 4.74/4.77 Running current (Cooling) 6.9/7.4 Power factor (Cooling) 99/98 Heating power consumption...
  • Page 34 Model FDTVA802HEST2R (Indoor unit: 3 units, Outdoor unit: 1 unit) FDTVA802HEST2R Model Item FDTA301R FDCVA802HESAR Nominal cooling capacity 20.0 [7.0~22.4] Nominal heating capacity 22.4 [7.6~25.0] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 6.72/6.75 Running current (Cooling) 10.0/10.8 Power factor (Cooling) 97/95 Heating power consumption...
  • Page 35 (d) Double twin type Model FDTVA802HESD2R (Indoor unit: 4 units, Outdoor unit: 1 unit) FDTVA802HESD2R Model Item FDTA201R FDCVA802HESAR Nominal cooling capacity 20.0 [7.0~22.4] Nominal heating capacity 22.4 [7.6~25.0] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 6.75/6.79 Running current (Cooling) 10.1/11.0 Power factor (Cooling)
  • Page 36 Model FDTVA1002HESD2R (Indoor unit: 4 units, Outdoor unit: 1 unit) FDTVA1002HESD2R Model Item FDTA251R FDCVA1002HESAR Nominal cooling capacity 25.0 [10.6~28.0] Nominal heating capacity 28.0 [9.5~31.5] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 8.86/8.90 Running current (Cooling) 13.3/14.3 Power factor (Cooling) 96/95 Heating power consumption...
  • Page 37: Ceiling Suspended Type (Fden)

    (3) Ceiling suspended type (FDEN) (a) Single type Model FDENVA151HEN1R FDENVA151HEN1R Model Item FDENA151R FDCVA151HENR Nominal cooling capacity 3.8 [1.8~4.7] Nominal heating capacity 4.5 [2.0~5.4] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 1.18/1.18 Running current (Cooling) 5.3/5.5 Power factor (Cooling) 97/98 Heating power consumption...
  • Page 38 Model FDENVA201HEN1R FDENVA201HEN1R Model Item FDENA201R FDCVA201HENR Nominal cooling capacity 5.0 [2.2~5.6] Nominal heating capacity 5.4 [2.5~6.3] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 1.54/1.54 Running current (Cooling) 6.9/7.2 Power factor (Cooling) 97/97 Heating power consumption 1.57/1.57 7.0/7.3 Running current (Heating) Power factor (Heating)
  • Page 39 Model FDENVA251HEN1R FDENVA251HEN1R Model Item FDENA251R FDCVA251HENR Nominal cooling capacity 5.6 [2.8~6.3] Nominal heating capacity 6.7 [3.1~7.1] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 1.74/1.74 Running current (Cooling) 7.8/8.2 Power factor (Cooling) 97/96 Heating power consumption 1.87/1.87 8.3/8.7 Running current (Heating) Power factor (Heating)
  • Page 40 Model FDENVA302HEN1R FDENVA302HEN1R Model Item FDENA301R FDCVA302HENR Nominal cooling capacity 7.1[3.5~8.0] Nominal heating capacity 8.0[4.0~9.0] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 2.06/2.06 Running current (Cooling) 9.1/9.5 Power factor (Cooling) 98/99 Heating power consumption 2.21/2.21 9.8/10.2 Running current (Heating) Power factor (Heating) 98/98 Inrush current (L.R.A)
  • Page 41 Model FDENVA402HEN2R FDENVA402HEN2R Model Item FDENA401R FDCVA402HENAR Nominal cooling capacity 10.0 [6.1~11.2] Nominal heating capacity 11.2 [5.9~12.5] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 2.85/2.85 Running current (Cooling) 12.5/13.1 Power factor (Cooling) 99/99 Heating power consumption 2.97/2.97 13.0/13.6 Running current (Heating) Power factor (Heating)
  • Page 42 Model FDENVA402HES2R FDENVA402HES2R Model Item FDENA401R FDCVA402HESAR Nominal cooling capacity 10.0 [6.1~11.2] Nominal heating capacity 11.2 [5.9~12.5] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 2.85/2.85 Running current (Cooling) 4.2/4.4 Power factor (Cooling) 98/98 Heating power consumption 2.97/2.97 Running current (Heating) 4.3/4.6 Power factor (Heating)
  • Page 43 Model FDENVA502HEN2R FDENVA502HEN2R Model Item FDENA501R FDCVA502HENAR Nominal cooling capacity 12.5 [6.5~14.0] Nominal heating capacity 14.0 [6.2~16.0] Power source 1 Phase 220-240V 50Hz/220V 60Hz Cooling power consumption 4.35/4.35 Running current (Cooling) 19.2/20.1 Power factor (Cooling) 99/98 Heating power consumption 3.95/3.95 Running current (Heating) 17.3/18.1 Power factor (Heating)
  • Page 44 Model FDENVA502HES2R FDENVA502HES2R Model Item FDENA501R FDCVA502HESAR Nominal cooling capacity 12.5 [6.5~14.0] Nominal heating capacity 14.0 [6.2~16.0] Power source 3 Phase 380-415V 50Hz/380V 60Hz Cooling power consumption 4.35/4.35 Running current (Cooling) 6.4/6.7 Power factor (Cooling) 98/99 Heating power consumption 3.95/3.95 5.8/6.1 Running current (Heating) Power factor (Heating)
  • Page 45 Model FDENVA602HEN2R FDENVA602HEN2R Model Item FDENA601R FDCVA602HENAR Nominal cooling capacity 14.0 [6.7~14.5] Nominal heating capacity 16.0 [6.3~16.5] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 4.95/4.95 Running current (Cooling) 21.7/22.7 Power factor (Cooling) 99/99 Heating power consumption 4.69/4.69 Running current (Heating) 20.5/21.5 Power factor (Heating)
  • Page 46 Model FDENVA602HES2R FDENVA602HES2R Model Item FDENA601R FDCVA602HESAR Nominal cooling capacity 14.0 [6.7~14.5] Nominal heating capacity 16.0 [6.3~16.5] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 4.95/4.95 Running current (Cooling) 7.2/7.6 Power factor (Cooling) 99/99 Heating power consumption 4.69/4.69 6.8/7.2 Running current (Heating) Power factor (Heating)
  • Page 47 (b) Twin type Model FDENVA302HENP1R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDENVA302HENP1R Model Item FDENA151R FDCVA302HENR Nominal cooling capacity 7.1[3.5~8.0] Nominal heating capacity 8.0[4.0~9.0] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 1.74/1.74 Running current (Cooling) 7.6/8.0 Power factor (Cooling) 99/99...
  • Page 48 Model FDENVA402HENP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDENVA402HENP2R Model Item FDENA201R FDCVA402HENAR Nominal cooling capacity 10.0 [6.1~11.2] Nominal heating capacity 11.2 [5.9~12.5] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 2.78/2.78 Running current (Cooling) 12.2/12.8 Power factor (Cooling) 99/99 Heating power consumption...
  • Page 49 Model FDENVA402HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDENVA402HESP2R Model Item FDENA201R FDCVA402HESAR Nominal cooling capacity 10.0 [6.1~11.2] Nominal heating capacity 11.2 [5.9~12.5] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 2.78/2.78 Running current (Cooling) 4.1/4.3 Power factor (Cooling) 98/98 Heating power consumption...
  • Page 50 Model FDENVA502HENP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDENVA502HENP2R Model Item FDENA251R FDCVA502HENAR Nominal cooling capacity 12.5 [6.5~14.0] Nominal heating capacity 14.0 [6.2~16.0] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 4.23/4.23 Running current (Cooling) 18.5/19.4 Power factor (Cooling) 99/99 Heating power consumption...
  • Page 51 Model FDENVA502HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDENVA502HESP2R Model Item FDENA251R FDCVA502HESAR Nominal cooling capacity 12.5 [6.5~14.0] Nominal heating capacity 14.0 [6.2~16.0] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 4.23/4.23 Running current (Cooling) 6.2/6.5 Power factor (Cooling) 98/99 Heating power consumption...
  • Page 52 Model FDENVA602HENP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDENVA602HENP2R Model Item FDENA301R FDCVA602HENAR Nominal cooling capacity 14.0 [6.7~14.5] Nominal heating capacity 16.0 [6.3~16.5] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 4.84/4.84 Running current (Cooling) 21.2/22.2 Power factor (Cooling) 99/99 Heating power consumption...
  • Page 53 Model FDENVA602HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDENVA602HESP2R Model Item FDENA301R FDCVA602HESAR Nominal cooling capacity 14.0 [6.7~14.5] Nominal heating capacity 16.0 [6.3~16.5] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 4.84/4.84 Running current (Cooling) 7.1/7.4 Power factor (Cooling) 98/99 Heating power consumption...
  • Page 54 Model FDENVA802HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDENVA802HESP2R Model Item FDENA401R FDCVA802HESAR Nominal cooling capacity 20.0 [7.0~22.4] Nominal heating capacity 22.4 [7.6~25.0] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 6.47/6.47 Running current (Cooling) 9.7/10.1 Power factor (Cooling) 96/97 Heating power consumption...
  • Page 55 Model FDENVA1002HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDENVA1002HESP2R Model Item FDENA501R FDCVA1002HESAR Nominal cooling capacity 25.0 [10.6~28.0] Nominal heating capacity 28.0 [9.5~31.5] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 9.01/9.01 Running current (Cooling) 13.5/14.1 Power factor (Cooling) 96/97 Heating power consumption...
  • Page 56 (c) Triple type Model FDENVA602HEN T2R (Indoor unit: 3 units, Outdoor unit: 1 unit) FDENVA602HENT2R Model Item FDENA201R FDCVA602HENAR Nominal cooling capacity 14.0 [6.7~14.5] Nominal heating capacity 16.0 [6.3~16.5] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 4.85/4.85 Running current (Cooling) 21.2/22.2 Power factor (Cooling)
  • Page 57 Model FDENVA602HEST2R (Indoor unit: 3 units, Outdoor unit: 1 unit) FDENVA602HEST2R Model Item FDENA201R FDCVA602HESAR Nominal cooling capacity 14.0 [6.7~14.5] Nominal heating capacity 16.0 [6.3~16.5] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 4.85/4.85 Running current (Cooling) 7.1/ 7.5 Power factor (Cooling) 99/98 Heating power consumption...
  • Page 58 Model FDENVA802HEST2R (Indoor unit: 3 units, Outdoor unit: 1 unit) FDENVA802HEST2R Model Item FDENA301R FDCVA802HESAR Nominal cooling capacity 20.0 [7.0~22.4] Nominal heating capacity 22.4 [7.6~25.0] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 6.40/6.40 Running current (Cooling) 9.6/10.0 Power factor (Cooling) 96/97 Heating power consumption...
  • Page 59: Satellite Ducted Type (Fdum)

    (4) Satellite ducted type (FDUM) (a) single type Model FDUMVA201HEN2R FDUMVA201HEN2R Model Item FDUMA202R FDCVA201HENR Nominal cooling capacity 5.0 [2.2~5.6] Nominal heating capacity 5.4 [2.5~6.3] Power source 1 Phase, 220-240V, 50Hz/220V, 60Hz Cooling power consumption 1.53/1.53 Running current (Cooling) 6.8/7.1 Power factor (Cooling) 98/98 Heating power consumption...
  • Page 60 Model FDUMVA251HEN2R FDUMVA251HEN2R Model Item FDUMA252R FDCVA251HENR Nominal cooling capacity 5.6 [2.8~6.3] Nominal heating capacity 6.4 [3.1~7.1] Power source 1 Phase, 220-240V, 50Hz/220V, 60Hz Cooling power consumption 1.66/1.66 Running current (Cooling) 7.3/7.6 Power factor (Cooling) 99/99 Heating power consumption 1.82/1.82 8.3/8.7 Running current (Heating) Power factor (Heating)
  • Page 61 Model FDUMA302HEN2R FDUMA302HEN2R Model Item FDUMA302R FDCVA302HENR Nominal cooling capacity 7.1 [3.5~8.0] Nominal heating capacity 8.0 [4.0~9.0] Power source 1 Phase, 220-240V, 50Hz/220V, 60Hz Cooling power consumption 2.08/2.08 Running current (Cooling) 9.2/9.6 Power factor (Cooling) 98/98 Heating power consumption 2.21/2.21 10.2/10.7 Running current (Heating) Power factor (Heating)
  • Page 62 Model FDUMVA402HEN2R FDUMVA402HEN2R Model Item FDUMA402R FDCVA402HENAR Nominal cooling capacity 10.0 [6.1~11.2] Nominal heating capacity 11.2 [6.0~12.5] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 2.80/2.80 Running current (Cooling) 12.5/13.1 Power factor (Cooling) 97/97 Heating power consumption 2.77/2.80 12.4/13.0 Running current (Heating) Power factor (Heating)
  • Page 63 Model FDUMVA402HES2R FDUMVA402HES2R Model Item FDUMA402R FDCVA402HESAR Nominal cooling capacity 10.0 [6.1~11.2] Nominal heating capacity 11.2 [6.0~12.5] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 2.80/2.80 Running current (Cooling) 4.2/4.4 Power factor (Cooling) 96/97 Heating power consumption 2.77/2.80 4.1/4.3 Running current (Heating) Power factor (Heating)
  • Page 64 Model FDUMVA502HEN2R FDUMVA502HEN2R Model Item FDUMA502R FDCVA502HENAR Nominal cooling capacity 12.5 [6.7~14.0] Nominal heating capacity 14.0 [6.2~16.0] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 4.03/4.03 Running current (Cooling) 18.3/19.1 Power factor (Cooling) 96/96 Heating power consumption 3.80/3.85 17.0/18.1 Running current (Heating) Power factor (Heating)
  • Page 65 Model FDUMVA502HES2R FDUMVA502HES2R Model Item FDUMA502R FDCVA502HESAR Nominal cooling capacity 12.5 [6.7~14.0] Nominal heating capacity 14.0 [6.2~16.0] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 4.03/4.03 Running current (Cooling) 6.1/6.4 Power factor (Cooling) 95/96 Heating power consumption 3.80/3.85 5.7/6.0 Running current (Heating) Power factor (Heating)
  • Page 66 Model FDUMVA602HEN2R FDUMVA602HEN2R Model Item FDUMA602R FDCVA602HENAR Nominal cooling capacity 14.0 [6.7~14.5] Nominal heating capacity 16.0 [6.3~16.5] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 4.95/4.95 Running current (Cooling) 22.3/23.3 Power factor (Cooling) 97/97 Heating power consumption 4.75/4.91 21.7/22.5 Running current (Heating) Power factor (Heating)
  • Page 67 Model FDUMVA602HES2R FDUMVA602HES2R Model Item FDUMA602R FDCVA602HESAR Nominal cooling capacity 14.0 [6.7~14.5] Nominal heating capacity 16.0 [6.3~16.5] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 4.95/4.95 Running current (Cooling) 7.4/ 7.7 Power factor (Cooling) 97/98 Heating power consumption 4.75/4.91 7.2/ 7.6 Running current (Heating)
  • Page 68 (b)Twin type Model FDUMVA402HENP2R(Indoor unit: 2 units, Outdoor unit: 7 units) FDUMVA402HENP2R Model Item FDUMA202R FDCVA402HENAR Nominal cooling capacity 10.0 [6.1~11.2] Nominal heating capacity 11.2 [6.0~12.5] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 3.12/3.12 Running current (Cooling) 13.6/14.3 Power factor (Cooling) 99/99...
  • Page 69 Model FDUMVA402HESP2R(Indoor unit: 2 units, Outdoor unit: 1 unit) FDUMVA402HESP2R Model Item FDUMA202R FDCVA402HESAR Nominal cooling capacity 10.0 [6.1~11.2] Nominal heating capacity 11.2 [6.0~12.5] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 3.12/3.12 Running current (Cooling) 4.6/4.8 Power factor (Cooling) 98/99 Heating power consumption 3.27/3.27...
  • Page 70 Model FDUMVA502HENP2R(Indoor unit: 2 units, Outdoor unit: 1 unit) FDUMVA502HENP2R Model Item FDUMA252R FDCVA502HENAR Nominal cooling capacity 12.5 [6.7~14.0] Nominal heating capacity 14.0 [6.2~16.0] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 4.47/4.47 Running current (Cooling) 19.7/20.6 Power factor (Cooling) 99/99 Heating power consumption 4.51/4.51...
  • Page 71 Model FDUMVA502HESP2R(Indoor unit: 2 units, Outdoor unit: 1 unit) FDUMVA502HESP2R Model Item FDUMA252R FDCVA502HESAR Nominal cooling capacity 12.5 [6.7~14.0] Nominal heating capacity 14.0 [6.2~16.0] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 4.47/4.47 Running current (Cooling) 6.6/6.9 Power factor (Cooling) 98/98 Heating power consumption 4.51/4.51...
  • Page 72 Model FDUMVA602HENP2R(Indoor unit: 2 units, Outdoor unit: 1 unit) FDUMVA602HENP2R Model Item FDUMA302R FDCVA602HENAR Nominal cooling capacity 14.0 [6.7~14.5] Nominal heating capacity 16.0 [6.3~16.5] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 5.00/5.00 Running current (Cooling) 22.0/23.0 Power factor (Cooling) 99/99 Heating power consumption 4.80/4.80...
  • Page 73 Model FDUMVA602HESP2R(Indoor unit: 2 units, Outdoor unit: 1 unit) FDUMVA602HESP2R Model Item FDUMA302R FDCVA602HESAR Nominal cooling capacity 14.0 [6.7~14.5] Nominal heating capacity 16.0 [6.3~16.5] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 5.00/5.00 Running current (Cooling) 7.3/7.7 Power factor (Cooling) 99/99 Heating power consumption 4.80/4.80...
  • Page 74 Model FDUMVA802HESP2R(Indoor unit: 2 units, Outdoor unit: 1 unit) FDUMVA802HESP2R Model Item FDUMA402R FDCVA802HESAR Nominal cooling capacity 20.0 [7.0~22.4] Nominal heating capacity 22.4 [7.6~25.0] Power source 3 Phase, 380–415V 50Hz/380V 60Hz Cooling power consumption 6.86/6.86 Running current (Cooling) 9.9/10.5 Power factor (Cooling) 99/99 Heating power consumption 6.72/6.72...
  • Page 75 Model FDUMVA1002HESP2R(Indoor unit: 2 units, Outdoor unit: 1 unit) FDUMVA1002HESP2R Model Item FDUMA502R FDCVA1002HESAR Nominal cooling capacity 25.0 [10.6~28.0] Nominal heating capacity 28.0 [9.5~31.5] Power source 3 Phase, 380–415V 50Hz/380V 60Hz Cooling power consumption 9.31/9.31 Running current (Cooling) 13.6/14.3 Power factor (Cooling) 99/99 Heating power consumption 8.35/8.35...
  • Page 76 (c) Triple type Model FDUMVA602HENT2R(Indoor unit: 3 units, Outdoor unit: 1 unit) FDUMVA602HENT2R Model Item FDUMA202R FDCVA602HENAR Nominal cooling capacity 14.0 [6.7~14.5] Nominal heating capacity 16.0 [6.3~16.5] Power source 1 Phase, 220-240V 50Hz/220V 60Hz 5.09/5.09 Cooling power consumption Running current (Cooling) 22.4/23.4 99/99 Power factor (Cooling)
  • Page 77 Model FDUMVA602HEST2R(Indoor unit: 3 units, Outdoor unit: 1 unit) FDUMVA602HEST2R Model Item FDUMA202R FDCVA602HESAR Nominal cooling capacity 14.0 [6.7~14.5] Nominal heating capacity 16.0 [6.3~16.5] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 5.09/5.09 Running current (Cooling) 7.4/7.8 Power factor (Cooling) 99/99 Heating power consumption 4.89/4.89...
  • Page 78 Model FDUMVA802HEST2R(Indoor unit: 3 units, Outdoor unit: 1 unit) FDUMVA802HEST2R Model Item FDUMA302R FDCVA802HESAR Nominal cooling capacity 20.0 [7.0~22.4] Nominal heating capacity 22.4 [7.6~25.0] Power source 3 Phase, 380–415V 50Hz/380V 60Hz Cooling power consumption 6.88/6.88 Running current (Cooling) 9.9/10.6 Power factor (Cooling) 99/99 Heating power consumption 6.74/6.74...
  • Page 79: High Static Pressure Duct Type (Fdu)

    (5) High static pressure duct type (FDU) (a) Single type Model FDUVA802HES2R FDUVA802HES2R Model Item FDUA801R FDCVA802HESAR Nominal cooling capacity 20.0 [7.0~22.4] Nominal heating capacity 22.4 [7.6~25.0] Power source 3 Phase, 380–415V 50Hz Cooling power consumption 6.50 Running current (Cooling) 10.5 Power factor (Cooling) Heating power consumption...
  • Page 80 Model FDUVA1002HES2R FDUVA1002HES2R Model Item FDUA1001R FDCVA1002HESAR Nominal cooling capacity 25.0 [10.6~28.0] Nominal heating capacity 28.0 [9.5~31.5] Power source 3 Phase, 380–415V 50Hz Cooling power consumption 9.05 Running current (Cooling) 14.8 Power factor (Cooling) Heating power consumption 8.22 14.0 Running current (Heating) Power factor (Heating) Inrush current (L.R.A) Noise level...
  • Page 81: Wall Mounted Type (Fdkn)

    (6) Wall mounted type (FDKN) (a) Single type Model FDKNVA151HEN1R FDKNVA151HEN1R Model Item FDKNA151R FDCVA151HENR Nominal cooling capacity 4.0 [1.8~4.7] Nominal heating capacity 4.5 [2.0~5.4] Power source 1 Phase, 220–240V 50Hz/220V 60Hz Cooling power consumption 1.30/1.30 Running current (Cooling) 5.8/6.1 Power factor (Cooling) 97/97 Heating power consumption...
  • Page 82 Model FDKNVA201HEN1R FDKNVA201HEN1R Model Item FDKNA201R FDCVA201HENR Nominal cooling capacity 5.0 [2.2~5.6] Nominal heating capacity 5.4 [2.5~6.3] Power source 1 Phase, 220–240V 50Hz/220V 60Hz Cooling power consumption 1.66/1.66 Running current (Cooling) 7.4/7.7 Power factor (Cooling) 98/98 Heating power consumption 1.58/1.58 7.1/7.4 Running current (Heating) Power factor (Heating)
  • Page 83 Model FDKNVA251HEN1R FDKNVA251HEN1R Model Item FDKNA251R FDCVA251HENR Nominal cooling capacity 5.6 [2.8~6.0] Nominal heating capacity 6.3 [3.1~7.1] Power source 1 Phase, 220–240V 50Hz/220V 60Hz Cooling power consumption 1.99/1.99 Running current (Cooling) 8.9/9.3 Power factor (Cooling) 97/97 Heating power consumption 1.85/1.85 8.2/8.6 Running current (Heating) Power factor (Heating)
  • Page 84 (b) Twin type Model FDKNVA302HENP1R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDKNVA302HENP1R Model Item FDKNA151R FDCVA302HENR Nominal cooling capacity 7.1 [3.5~8.0] Nominal heating capacity 8.0 [4.0~9.0] Power source 1 Phase, 220–240V 50Hz/220V 60Hz Cooling power consumption 1.67/1.67 Running current (Cooling) 7.3/7.7 Power factor (Cooling) 99/99...
  • Page 85 Model FDKNVA402HENP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDKNVA402HENP2R Model Item FDKNA201R FDCVA402HENAR Nominal cooling capacity 10.0 [6.1~11.2] Nominal heating capacity 11.2 [5.6~12.5] Power source 1 Phase, 220–240V 50Hz/220V 60Hz Cooling power consumption 2.90/2.90 Running current (Cooling) 12.8/13.4 Power factor (Cooling) 99/98 Heating power consumption...
  • Page 86 Model FDKNVA402HESP2R(Indoor unit: 2 units, Outdoor unit: 1 unit) FDKNVA402HESP2R Model Item FDKNA201R FDCVA402HESAR Nominal cooling capacity 10.0 [6.1~11.2] Nominal heating capacity 11.2 [5.6~12.5] Power source 3 Phase, 380–415V 50Hz/380V 60Hz Cooling power consumption 2.90/2.90 Running current (Cooling) 4.3/4.5 Power factor (Cooling) 97/98 Heating power consumption 3.24/3.24...
  • Page 87 Model FDKNVA502HENP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDKNVA502HENP2R Model Item FDKNA251R FDCVA502HENAR Nominal cooling capacity 12.5 [6.5~14.0] Nominal heating capacity 14.0 [6.2~16.0] Power source 1 Phase, 220–240V 50Hz/220V 60Hz Cooling power consumption 4.14/4.14 Running current (Cooling) 18.1/19.0 Power factor (Cooling) 99/99 Heating power consumption...
  • Page 88 Model FDKNVA502HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) FDKNVA502HESP2R Model Item FDKNA251R FDCVA502HESAR Nominal cooling capacity 12.5 [6.5~14.0] Nominal heating capacity 14.0 [6.2~16.0] Power source 3 Phase, 380–415V 50Hz/380V 60Hz Cooling power consumption 4.14/4.14 Running current (Cooling) 6.1/6.4 Power factor (Cooling) 98/98 Heating power consumption...
  • Page 89 (c) Triple type Model FDKNVA602HENT2R (Indoor unit: 3 units, Outdoor unit: 1 unit) FDKNVA602HENT2R Model Item FDKNA201R FDCVA602HENAR Nominal cooling capacity 14.0 [6.5~14.5] Nominal heating capacity 16.0 [6.3~16.5] Power source 1 Phase, 220–240V 50Hz/220V 60Hz Cooling power consumption 4.82/4.82 Running current (Cooling) 21.1/22.1 Power factor (Cooling) 99/99...
  • Page 90 Model FDKNVA602HES T2R (Indoor unit: 3 units, Outdoor unit: 1 unit) FDKNVA602HEST2R Model Item FDKNA201R FDCVA602HESAR Nominal cooling capacity 14.0 [6.5~14.5] Nominal heating capacity 16.0 [6.3~16.5] Power source 3 Phase, 380–415V 50Hz/380V 60Hz Cooling power consumption 4.82 /4.82 Running current (Cooling) 7.0/ 7.4 Power factor (Cooling) 99/99...
  • Page 91: Range Of Usage & Limitations

    1.2.2 Range of usage & limitations Models 151, 201, 251 302~602 802, 1002 Item Indoor return air temperature (Upper, lower limits) Refer to the selection chart Please see the next page. (see page 126) Outdoor air temperature (Upper, lower limits) Operating temperature When used under -5˚C, install a snow hood (option).
  • Page 92 Models 302~1002 only Cooling Range of cooling usage Indoor air W.B. temperature (˚CW.B.) Heating Range of heating usage Outdoor air W.B. temperature (˚CW.B.) Height and length restrictions for refrigerant piping Models 302~602 One-way pipe length (m) L +ra +rb Twin type 10, ra 20, rb Branch pipe length (m)
  • Page 93 Double-twin type Outdoor unit Indoor unit Models 802, 1002 One-way pipe length (m) L +ra 70, L +rb 70, L +rc 70, L +rd 10, Ira – rc I 10, Irb – rc I Branch pipe length (m) Ira –rb I 10, Irb –...
  • Page 94: Exterior Dimensions

    1.2.3 Exterior dimensions (1) Indoor unit (a) Ceiling recessed compact type (FDTC) Models FDTCA151R, 201R Unit:mm 660 (Ceiling hole size) Outside air opening for Decorative Panel 530 Suspension bolts pitch ducting Air return Control Air supply grille Drain hose piece Opening for (Accessory) exit wiring...
  • Page 95 (b) Ceiling recessed type (FDT) Models FDTA151R, 201R, 251R Unit : mm Decorative Panel Outside air 860~890(Ceiling hole size) opening for 780(Suspension bolts pitch) ducting Control box Exhaust air opening for ducting Liquid piping Air supply φ6.35(1/4") Air return grille VIEW A Gas piping Drain hose piece...
  • Page 96 Model FDTA301R Unit : mm Decorative Panel Outside air 860~890(Ceiling hole size) opening for 780(Suspension bolts pitch) ducting Control box Exhaust air opening for ducting Liquid piping Air supply φ9.52(3/8") Air return grille VIEW A Gas piping Drain hose piece φ15.88(5/8") (Accessory) (Installed at site)
  • Page 97 Model FDTA401R Unit : mm Decorative Panel Outside air 860~890 (Ceiling hole size) opening for 780 (Suspension bolts pitch) ducting Control box Exhaust air opening for ducting Liquid piping φ9.52 (3/8") Air return grille Air supply Gas piping VIEW A φ15.88 (5/8") Drain hose piece (Accessory)
  • Page 98 Models FDTA501R, 601R Unit : mm Decorative Panel Outside air 860~890 (Ceiling hole size) opening for 780 (Suspension bolts pitch) ducting Control box Exhaust air opening for ducting Liquid piping φ9.52 (3/8") Air supply Air return grille Gas piping VIEW A φ15.88 (5/8") Drain hose piece (Accessory)
  • Page 99 (c) Satellite ducted type (FDUM) Model FDUMA202R Unit : mm 786 (Suspension bolts pitch) Hole of 80.5 tapping screws (4-φ4) φ149 Control box Drain hose piece (Accessory) (Installed at site) φ170 φ170 Liquid piping 6.35(1/4") Fresh air opening Outlet air opening for ducting for ducting Gas piping (Knock out)
  • Page 100 Models FDUMA252R, 302R Unit : mm 986 (Suspension bolts pitch) 80.5 Control box Holes of φ149 tapping screws 4-φ4 Drain hose piece (Accessory) (Installed at site) φ170 φ170 Liquid piping 252:ø6.35(1/4") Fresh air opening 302:ø9.52(3/8") for ducting Outlet air opening for ducting (Knock out) (Knock out) Gas piping...
  • Page 101 Models FDUMA402R, 502R, 602R Unit : mm 1406 (Suspension bolts pitch) 1370 Holes of 80.5 tapping screws Control box φ149 (4-φ4) Drain hose piece (Accessory) (Installed at site) φ170 φ170 Fresh air opening Liquid piping for ducting Outlet air opening for ducting ø9.52(3/8") (Knock out) (Knock out)
  • Page 102 (d) High static pressured duct type (FDU) Models FDUA801R, 1001R 794 (Suspension bolts pitch) Holes for screw (M5 × 20 pcs.) Air return duct 6 × 200 = 1200 1500 (Duct dimension) Control box VIEW A Gas piping Liquid piping φ25.4 (1") 801: φ9.52 (3/8") 1001: φ12.7 (1/2")
  • Page 103 (e) Ceiling suspended type (FDEN) Models FDENA151R, 201R Unit : mm Holes for suspension bolts 290(Suspension bolts pitch) (M8 to M10×4pcs.Not included) 1022(Suspension bolts pitch) Liquid piping Gas piping Drain hose piece connection(1) (VP20) Air supply Indication board Note(1) The slope of drain piping inside the unit is able to take incline of 10mm.
  • Page 104 Models FDENA401R, 501R, 601R Unit : mm Holes for suspension bolts 290(Suspension bolts pitch) (M8 to M10×4pcs.Not included) 1572(Suspension bolts pitch) Liquid piping Gas piping 1540 Drain hose piece connection(1) 1620 (VP20) Air supply Indication board Note(1) The slope of drain piping inside the unit is able to take incline of 10mm.
  • Page 105 Model FDKNA251R Unit : mm Installation position diagram and installation space, from the front. Service Mounting plate space Unit Service 4−12×18 space 5073.5 73.5 long hole 207.5 182.5 14.5 3 60 63.5 Hole on wall for rear connection 387.5 53.5 (φ65) 457.5 Drain hose piece...
  • Page 106: Remote Controller (Optional Parts)

    (2) Remote controller (Optional parts) (a) Wired remote controller Unit : mm Installation with wiring exposed Installation with wiring recessed Wall 0.3mm , 3cores (O.D.ø5.6) Wire (Recessed) LCD display Electrical box (Locally Purchased) Remote controller mounting dimensions Cut off with a knife or the like thin walled parts intend- Remote controller ed for screw holes, and then...
  • Page 107 (b) Wireless remote controller Unit: mm...
  • Page 108: Outdoor Unit

    (3) Outdoor unit Models FDCVA151HENR, 201HENR Unit: mm 471.5 286.4 Holes for anchor bolt Holes for drain 43.1 (M10×4 pcs.) (φ20×5 pcs.) 17.5 Terminal block 90.6 29.7 Liquid piping: φ6.35 (1/4") (Flare connecting) Gas piping: φ12.7 (1/2") (Flare connecting) Piping, wiring outlet Required space for maintenance and air fl...
  • Page 109 Model FDCVA251HENR Unit: mm 471.5 286.4 Holes for anchor bolt Holes for drain 43.1 (M10×4 pcs.) (ø20×5 pcs.) 17.5 Terminal block 90.6 29.7 Liquid piping: φ6.35 (1/4") (Flare connecting) Gas piping: φ15.88 (5/8") (Flare connecting) Piping, wiring outlet Required space for maintenance and air fl ow Minimum allowable space to the obstacles Unit:mm Installation...
  • Page 110 Model FDCVA302HENR Unit: mm Holes for anchor bolt (M10×4 pcs.) Holes for drain (φ20×3 pcs.) Terminal block Liquid piping φ9.52(3/8") (Flare connecting) Piping,wiring outlet 165.5 Gas piping φ15.88(5/8") (Flare connecting) Required space for maintenance and air fl ow Minimum allowable space to the obstacles Unit:mm Air inlet Installation...
  • Page 111 Models FDCVA402HENAR, 502HENAR, 602HENAR 402HESAR, 502HESAR, 602HESAR Unit : mm Gas piping: φ15.88(5/8") Liquid piping: φ9.52(3/8") (Flare connecting) (Flare connecting) Terminal block Liquid piping: φ9.52(3/8") (Flare connecting) Gas piping: φ15.88(5/8") (Flare connecting) Opening for electric wiring Opening for Opening for piping piping and and electric wiring electric wiring...
  • Page 112 Model FDCVA802HESAR Liquid piping : φ9.52(3/8") Unit: mm (Flare connecting) Gas piping : φ19.05(3/4") (Flare connecting) Gas piping : φ25.4(1") (Brazing connecting) Terminal block Liquid piping : φ9.52(3/8") (Flare connecting) Gas piping : φ19.05(3/4") (Flare connecting) Gas piping : φ25.4(1") (Brazing connecting) Opening for Opening for...
  • Page 113 Model FDCVA1002HESAR Liquid piping : φ9.52(3/8") Unit: mm (Flare connecting) Gas piping : φ19.05(3/4") (Flare connecting) Gas piping : φ25.4(1") (Brazing connecting) Terminal block Liquid piping : φ9.52(3/8") (Flare connecting) Gas piping : φ19.05(3/4") (Flare connecting) Gas piping : φ25.4(1") (Brazing connecting) Opening for electric wiring...
  • Page 114: Inside View

    1.2.4 Inside view (1) Outdoor unit Models FDCVA151HENR, 201HENR, 251HENR Electronic expansion valve Control box 4-way valve Receiver (Heating) Receiver (Cooling) Service valve (Liquid side) Service valve (Gas side) Compressor Model FDCVA302HENR Control box 4way valve High pressure switch (63H1) Low pressure sensor (PSL)
  • Page 115 Models FDCVA402HENAR, 502HENAR, 602HENAR 402HESAR, 502HESAR, 602HESAR Control box High pressure switch (63H1) Electronic expansion valve (cooling) (SM1) Electronic expansion valve (heating) (SM2) Compressor Service valve Lower pressure sensor (Liquid side) Service valve (LPT) (Gas side) Model FDCVA802HESAR Control box High pressure switch (63H1) Lower pressure sensor...
  • Page 116 Model FDCVA1002HESAR Control box High pressure switch (63H1) Lower pressure sensor (LPT) Electronic expansion valve (cooling) (SM1) Service valve (Liquid side) Service valve (Gas side) Electronic expansion valve (heating) (SM2) Compressor Solenoid valve (SV2)
  • Page 117: Exterior Appearance

    1.2.5 Exterior appearance (1) Indoor unit (a) Ceiling recessed compact type (FDTC) Plaster white (b) Ceiling suspended type (FDT) Plaster white (c) Ceiling suspended type (FDEN) Light gray Light gray (Vertical louver) Plaster white Plaster white (Horizontal louver) (Side panel) (Front panel) Plaster white (Front panel)
  • Page 118 (d) Wall mounted type (FDKN) Cool white (e) Satellite ducted type (FDUM) ......... Cromatofre steel plate High static pressure duct type (FDU) ....Cromatofre steel plate (2) Outdoor unit Models FDCVA151HENR, 201HENR, 251HENR Model FDCVA302HENR Stucco white Stucco white Models FDCVA402HENAR, 502HENAR, 602HENAR Model FDCVA802HESAR 402HESAR, 502HESAR, 602HESAR Polar white...
  • Page 119 Model FDCVA1002HESAR Polar white...
  • Page 120: Piping System

    1.2.6 Piping system (1) Single type Models 152, 202, 252 Indoor unit Outdoor unit Cooling cycle Heating cycle Gas line Check joint Check joint 15, 20:φ12.7 25:φ15.88 Service valve (Flare connecting) Heat exchanger Heat exchanger 4way valve Muffler Thermistor Thermistor Thermistor Discharge Compressor...
  • Page 121 Models 402, 502, 602 Indoor unit Outdoor unit Cooling cycle Heating cycle Check joint 4way valve Thermistor Gas line (φ15.88) Service valve (Flare connecting) Check joint Heat exchanger Heat exchanger High pressure Check switch valve Thermistor 63H1 Muffler Lower pressure sensor Thermistor Thermistor (LPT)
  • Page 122 (2) Twin type Model 302 Outdoor unit Indoor unit Indoor unit Cooling cycle Heating cycle Gas branch pipe Check joint Thermistor (φ12.7) Check joint Gas line Low pressure Muffler (φ15.88) sensor (PSL) 4way valve Service valve (Flare connecting) Thermistor Flare connecting High pressure switch Thermistor...
  • Page 123 Models 802, 1002 Gas branch pipe (φ15.88) Outdoor unit Indoor unit Indoor unit Cooling cycle Heating cycle Check joint 4way valve Thermistor Gas line (φ25.4) Muff Service valve Flare connecting (Flare connecting) Check joint High pressure Lower pressure switch Heat exchanger sensor Check (LPT)
  • Page 124 Model 802 Gas branch pipe (φ15.88) Indoor unit Indoor unit Indoor unit Outdoor unit Cooling cycle Heating cycle Check joint 4way valve Thermistor Gas line (φ25.4) Muff Flare connecting Service valve (Flare connecting) Check joint High pressure Heat exchanger Lower pressure switch sensor Check...
  • Page 125 (4) Double twin type Models 802, 1002 2nd branch pipe of gas (φ15.88) Outdoor unit Cooling cycle Heating cycle 1st branch Indoor unit Indoor unit pipe of gas Check joint 4way valve Thermistor Gas line (φ15.88) (φ25.4) Muff Service valve (Flare connecting) Branch pipe Check joint...
  • Page 126 Preset point of the protective devices Equipped Parts name Mark 152, 202, 252 model 302, 402, 502, 602 model 802, 1002 model unit Thermistor OFF 63˚C (for protection over- ON 56˚C loading in heating) Indoor unit Thermistor OFF 1.0˚C (for frost prevention) ON 10˚C Thermistor OFF 105˚C...
  • Page 127: Selection Chart

    1.2.7 Selection chart Correct the cooling and heating capacity in accordance with the conditions as follows. The net cooling and heating capacity can be obtained in the following way. Net capacity = Capacity shown on specifi cation × Correction factors as follows. (1) Models 152~252 Coeffi...
  • Page 128 (2) Models 302~1002 Caution: In case that the operation during low ambient temperature below -5°C is expected, install the outdoor unit where it is not influenced by natural wind. Otherwise protection control by low pressure will be activated much more frequently and it will cause insufficient capacity or breakdown of the compressor in worst case.
  • Page 129 3) Models 802, 1002 Indoor air 1.30 temperature 24˚CW.B 1.20 1.10 Indoor air temperature 19˚CW.B 1.00 0.90 0.80 Indoor air temperature 16˚CW.B 0.70 Indoor air temperature 12˚CW.B 0.60 -15 -13 Ambient air temperature (˚CDB) (b) Heating 1) Model 302 1.50 Ambient air temperature 18.5˚CW.B 1.40...
  • Page 130 2) Models 402~602 Ambient air 1.10 temperature 18.5˚CW.B 1.00 Ambient air Ambient air temperature 6˚CW.B temperature 10˚CW.B 0.90 Ambient air temperature 1˚CW.B 0.80 Ambient air 0.70 temperature 0˚CW.B Ambient air temperature -10˚CW.B 0.60 0.50 Indoor air temperature (˚CD.B) 3) Models 802, 1002 Models FDCVA802,1002 Ambient air 1.20...
  • Page 131 (2) Power consumption correction factor (a) Cooling 1) Model 302 1.40 1.30 1.20 Indoor air temperature 24˚CW.B 1.10 1.00 Indoor air 0.90 Indoor air temperature 16˚CW.B temperature 19˚CW.B 0.80 0.70 Indoor air 0.60 temperature 12˚CW.B 0.50 0.40 -15 -13 Ambient air temperature (˚CDB) 2) Models 402~602 Indoor air 1.10...
  • Page 132 3) Models 802,1002 1.10 Indoor air temperature 24˚CW.B 1.00 0.90 Indoor air 0.80 temperature 19˚CW.B 0.70 Indoor air temperature 16˚CW.B 0.60 0.50 Indoor air temperature 12˚CW.B 0.40 0.30 Ambient air temperature (˚CDB) (b) Heating 1) Model 302 1.50 Ambient air temperature 18.5˚CW.B 1.40 Ambient air...
  • Page 134 (3) Sensible heat factor (a) Cooling 1) Model 302 1.05 1.00 Indoor air Indoor air temperature 12˚CW.B temperature 16˚CW.B 0.95 0.90 0.85 Indoor air temperature 19˚CW.B 0.80 Indoor air temperature 24˚CW.B 0.75 0.70 0.65 0.60 -15 -13 Ambient air temperature (˚CDB) 2) Models 402~602 1.10 1.00...
  • Page 135 3) Models 802, 1002 1.10 Indoor air temperature 16˚CW.B 1.00 Indoor air temperature 12˚CW.B 0.90 Indoor air 0.80 temperature 24˚CW.B Indoor air temperature 19˚CW.B 0.70 0.60 0.50 -15 -13 Ambient air temperature (˚CDB) (3) Correction of cooling and heating capacity in relation to air fl ow rate control (fan speed) Coeffi...
  • Page 136 (ii) Models 302 ~ 602 ± Ambient air temperature 5°C or more Equivalent piping length Heating 0.998 0.998 0.993 0.993 0.988 0.988 302 model 0.954 0.947 0.940 0.933 0.996 0.989 0.982 0.975 0.968 0.961 402 model 0.991 0.978 0.964 0.951 0.937 0.924 0.910...
  • Page 137 ± Ambient air temperature -5°C Equivalent piping length Heating 0.998 0.995 0.991 0.988 0.984 0.981 0.977 0.974 0.970 0.967 0.963 0.960 0.956 0.953 802 model 0.993 0.979 0.965 0.950 0.936 0.922 0.908 0.894 0.880 0.866 0.852 0.838 0.824 0.810 φ25.4 1002 model 0.991 0.974 0.958 0.941 0.925 0.908 0.891 0.875 0.858 0.841 0.825...
  • Page 138: Characteristics Of Fan

    1.2.8 Characteristics of fan (2) Satellite ducted type (FDUM) • External static pressure table How to interpret the blower characteristics table Unit : Pa Example : Case of FDUMA252R Duct specs. 1 spot Standard Square duct closing Air flow /min) Stan- High Stan-...
  • Page 139 FDUMA302R FDUMA402R 3-spot blower internal resistance [Standard] 4-spot blower internal resistance 2-spot blower internal resistance [Standard] 3-spot blower internal resistance Square duct blower internal resistance Square duct blower internal resistance Lower Upper Lower Upper limit limit limit limit Air flow(m /min) Air flow(m /min)
  • Page 140 (2) High static pressure ducted type (FDU) (a) Standard (Factory Settings) Model FDUA801R Model FDUA1001R • Condition of standard rating • Condition of standard rating rated air volume: 100Pa rated air volume: 100Pa Example Example of duct of duct 38 40 85 87 Lower Upper...
  • Page 141: Noise Level

    1.2.9 Noise level Notes (1) The data are based on the following conditions. Ambient air temperature: Indoor unit 27˚C DB, 19˚C WB. Outdoor unit 35˚C DB. Notes (2) The data in the chart are measured in an anechoic room. Notes (3) The noise levels measured in the field are usually higher than the data because of reflection.
  • Page 142 (c) Ceiling suspended type (FDEN) Unit Measured based on JIS B 8616 Mike position as pen drawing Mike (in front & below unit) Models FDENA151R, 201R Models FDENA251R, 301R Model FDENA401R Noise level 42 dB (A) at HIGH Noise level 44 dB (A) at HIGH Noise level 46 dB (A) at HIGH 39 dB (A) at MEDIUM 41 dB (A) at MEDIUM...
  • Page 143 Models FDUMA502R, 602R Noise level 38 dB (A) at HIGH 36 dB (A) at MEDIUM 33 dB (A) at LOW 1000 2000 4000 8000 Mid Octave Band Frequency (Hz) (e) High static pressure duct type (FDU) Measured based on JIS B 8616 Unit 1.5 m Mike position as pen drawing...
  • Page 144: Outdoor Unit

    (2) Outdoor unit Measured based on JIS B 8616 Mike position: at highest noise level in position as mentined below Distance from front side 1m Height Models FDCVA151HENR, 201HENR, Model FDCVA302HENR Model FDCV402HENAR 251HENR Noise level 48 dB (A) 402HESAR Noise level 48 dB (A) Noise level 50 dB (A) 1000...
  • Page 145: Electrical Data

    ELECTRICAL DATA 1.3.1 Electrical wiring (1) Indoor unit (a) Ceiling recessed compact type (FDTC) Models All models...
  • Page 146 (b) Ceiling recessed type (FDT) Models FDTA151R, 201R, 251R, 301R, 401R...
  • Page 147 Model FDTA501R, 601R...
  • Page 148 (c) Ceiling suspended type (FDEN) Models All models...
  • Page 149 (d) Satellite ducted type (FDUM) Models All models...
  • Page 150 (e) High static pressure ducted type (FDU) Models All models...
  • Page 151 Wall mounted type (FDKN) Models All models...
  • Page 152: Outdoor Unit

    (2) Outdoor unit Models FDCA151HENR,201HENR,251HENR t˚ t˚ t˚ t˚...
  • Page 153 Model FDCVA302HENR t˚ t˚ t˚ t˚ t˚...
  • Page 154 Models FDCVA402HENAR, 502HENAR, 602HENAR t˚ t˚ t˚ t˚ t˚...
  • Page 155 Models FDCVA402HESAR, 502HESAR, 602HESAR...
  • Page 156 Models FDCVA802HESAR, 1002HESAR t˚ t˚ t˚ t˚ t˚ t˚ t˚...
  • Page 157: Outline Of Operation Control By Microcomputer

    OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER (1) Remote controller (a) Wired remote controller The fi gure below shows the remote controller with the cover opened. Note that all the items that may be displayed in the liquid crystal display area are shown in the fi gure for the sake of explanation. Characters displayed with dots in the liquid crystal display area are abbreviated.
  • Page 158: Operation Section

    (b) Wireless remote controller Indication section AIR FLOW indicator ROOM TEMP. indicator Indicates the condition of swing fl ap. Indicates set temperature. OPERATION MODE indicator FAN SPEED indicator ± Indicates selected operation with lamp. Indicates the selected blow rate. FILTER indicator ON-TIMER indicator Indicates for 2 seconds when FILTER button Indicated when ON-TIMER is set.
  • Page 159: Operation Control Function By The Indoor Controller

    (2) Operation control function by the indoor controller (a) Room temperature control (Differential of thermostat) Heating operation Cooling operation Set temp.by thermostat Set temp.by thermostat Temperature difference between thermostat set Temperature difference between thermostat set temp. and return air temp. (Detected by Th temp.
  • Page 160 (d) Dehumidifying operation (“THERMAL DRY”) The compressor, the indoor fan motor and the outdoor fan Operation block motor are operated intermittently under thermistor (Th control according to the appropriate operation block, to provide cooling operation for the dehumidifying. High Set temp. by thermostat Pattern of operation CM, FM : ON...
  • Page 161 Weekly Timer Each day, it is possible to set this timer’s operation up to 4 times (On timer, or Off timer). Possible joint use timer operation setting combinations Simple Timer Off Timer On Timer Weekly Timer × × Simple Timer ×...
  • Page 162 (h) Room temperature sensing temperature compensation during heating When the J4 (SW7-4) on the indoor PCB is open (OFF), the condition for thermostat ON/OFF is offset by +3°C. In case the warm air is accumulated on the ceiling and the indoor unit is turned into thermostatic OFF easily, it is possible to extend thermostatic ON period by this fuction.
  • Page 163 (k) Condensate pump motor (DM) Control [FDT and FDUM models only] Drain motor is started no sooner than the compressor is turned ON during cooling or dehumidifying operation. The drain motor continues to operate for 5 minutes after the stop of unit operation, stop with the error stop, thermostat stop and at switching from cooling or dehumidifying operation to blowing or heating operation.
  • Page 164 (q) Using 1 remote controller to control multiple units (indoor units - up to 16 units) Function A single remote control switch can be used for group control of multiple units (indoor units - up to 16 units). All indoor units which are connected to the remote controller can be operated/stopped with the selected mode in order of the unit number.
  • Page 165 a) At shipping from factory J1 (SW7-1) on PCB is closed (ON). • Input signal to CnT OFF ON [Edge input] ... Air conditioner ON • Input signal to CnT ON OFF [Edge input] ... Air conditioner OFF Note (1) The ON at the * mark indicates ON CnT Input using the remote control switch, etc.
  • Page 166: Operation Control Function By The Wired Remote Controller

    (3) Operation control function by the wired remote controller (a) Remote controller operation mode switch switching sequence COOL HEAT AUTO (b) CPU reset If the “GRILL” button and “CHECK” button on the remote controller are pressed at the same time, this function is activated. The system will behave as same way as power supply reset.
  • Page 167: Operation Control Function By The Outdoor Controller

    (4) Operation control function by the outdoor controller ♦ Models FDCVA151 ~ 251 (a) Deciding the compressor speed The indoor unit’s return air temperature and the set temperature are used to carry out fuzzy calculations, then the required speed is decided. After that compressor speed adjustment by any protection control is taken into account the actual compres- sor speed is decided.
  • Page 168 3) Compressor protective start III When the following conditions are satisfi ed, compressor start III is implemented. a) Less than 6 hours have passed since the power was turned ON, and this is the 1st cumulative compressor start since the power was turned ON. The compressor starts synchronous operation 5 seconds after thermostat ON.
  • Page 169 FDCVA251 Compressor speed (rps) less than 46 46 to less than 66 66 to less than 80 80 or more Cooling Outdoor unit fan speed 4th speed (520 rpm) 5th speed (570 rpm) 6th speed (685 rpm) 7th speed (740 rpm) Compressor speed (rps) less than 62 62 to less than 82...
  • Page 170 Defrosting 1) Defrosting start conditions Defrosting operation starts when all the following conditions are satisfi ed. a) If 45 (35) minutes of cumulative compressor operating time have passed since defrosting ended and 30 minutes of cumulative compressor operating time have passed since heating operation started. (Remote controller: ON) b) 5 minutes passes after the compressor start- —...
  • Page 171 2) Anomalous discharge pipe temperature a) If the discharge pipe temperature rises to 105°C or higher, the compressor is stopped [the outdoor unit fan motor stops 1 minute later. If the temperature drops to 80°C or lower, the compressor restarts automatically. Compressor stops Compressor operates Discharge pipe temperature (˚C)
  • Page 172 (h) Inverter protection control 1) Current cut control This prevents overcurrent at the inverter. If the current exceeds the set value, the compressor is stopped. It restarts automati- cally 3 minutes later, but if the current is cut 3 times within a period of 20 minutes, an anomalous stop (E42) occurs. 2) Power transistor overheating protection If the power transistor temperature rises to 82°C or higher, the compressor speed is reduced.
  • Page 173: Models Fdcva302 ~ 1002

    (n) Low voltage protection control If a power supply voltage of 176 V or lower is detected while the compressor is stopped, or if a power supply voltage of 176 V or lower is detected for 3 minutes during compressor operation, the compressor is stopped. (o) Test operation 1) It is possible to operate the outdoor unit using SW9 and SW5-4 on the outdoor unit PCB.
  • Page 174 b) After starting for 30 seconds, the compressor will run at fi xed frequency within 2~4 minutes with Brps as the target speed. Model Operation mode A rps B rps C rps Cooling, dehumidying Heating 402 ~ 602 Cooling, dehumidying Heating 802, 1002 Cooling, dehumidying...
  • Page 175 Models FDCVA402~1002 ± 1) Conditions of control When the starting times of compressor are accumulated as the fi rst startup after the power breaker is switched ON. 2) Contents of control Choose the following startup modes according to the conditions of operation mode and ambient temperature (Tho-A). 3) Low-speed operation control in heating and drying a) Basic conditions This is the 1st cumulative compressor startup time after the power is turned on.
  • Page 176 (ii) Fan speed control when the unit started 1) During heating and defrosting fan control a) The outdoor unit’s fan is started in 4th speed simultaneously with the start of compressor operation. b) After 20 seconds of operation in 4th speed, outdoor fan control in item (iii) is executed. 2) During cooling, dehumidifying a) When the ambient air temperature (Tho-A) is 20°C or higher, the outdoor unit fan starts simultaneously with the compressor.
  • Page 177 3) Snow protection fan control In case the DIP switch (SW3-2) on the outdoor unit control PCB is ON, when in the stop mode or the anomalous stop mode, the outdoor unit fan runs at 4th speed for 30 seconds every ten minutes in accordance with the ambient air temperature (detected by Tho-A).
  • Page 178 (e) Outdoor unit fan control during cooling when the outdoor air temperature is low ( i) When cooling or dehumidifying, if the ambient air temperature (Tho-A) is in Zone B and when the outdoor unit fan has run for 20 seconds since starting and is running at 1st speed, the outdoor unit fan speed is controlled in accordance with the outdoor heat exchanger temperature (Tho-R1, R2).
  • Page 179 Defrosting Model FDCVA 302~1002 (i ) Defrosting start conditions If all the following defrosting conditions A or B are satisfi ed, defrosting operation starts. 1) Defrosting conditions A a) When cumulative operating time of the compressor elapses 45 minutes or more after the previous defrosting operation ends, Defrosting operation start or 30 minutes or more after the heating...
  • Page 180 (iii) Defrosting end conditions If any of the following conditions is satisfi ed, the defrosting operation fi nishes. 1) 8 minutes and 20 seconds have passed since defrosting started. (In models 302, 802 and 1002, 10 minutes and 20 seconds have passed.) 2) When the outdoor heat exchanger temperature (sensed by Tho-R1, R2, whichever one senses the lower temperature) is 12°C or higher continuously for 10 seconds.
  • Page 181 (iii) Current safe control 1) If the inverter primary current (CT current) becomes higher than the Set value (A) Model following set value, the compressor speed is reduced. If the current is still above the set value after the speed is reduced, the speed is 402, 502, 602 reduced again.
  • Page 182 2) Low pressure error detection a) If either of the following conditions is satisfi ed, the compressor is stopped. If the low pressure is 0.079 MPa or lower continuously for 15 seconds after the compressor starts. If the low pressure is 0.15 MPa after 10 minutes have passed since the compressor started and superheating at 30°C continues for 60 seconds.
  • Page 183 ± Outdoor heat exchanger thermistor : -50°C or lower ± Ambient air temperature thermistor : -30°C or lower ± Low pressure sensor: 0 V or lower, or 3.49 V or higher. (ii) Discharge pipe temperature thermistor, suction pipe temperature thermistor, under-dome temperature thermistor. (models 802, 1002 only) After the compressor goes ON, if the following is detected for 5 seconds continuously between 10 minutes and 10 minutes 20 seconds after the compressor goes ON, the compressor stops.
  • Page 184 (m) Pump down control If the pump down button SW1 (SW9) is kept on pressing for 2 seconds during an operation stop and anomalous stop (not including when the thermostat is OFF), pump down operation starts. (It is disabled during indoor unit operation. It is enabled during an anomalous stop of the indoor unit and during power OFF.) Make sure the service valve on the liquid line is closed before starting pump down operation.
  • Page 185: Application Data

    APPLICATION DATA SAFETY PRECAUTIONS • Please read these “Safety Precautions” fi rst then accurately execute the installation work. • Though the precautionary points indicated herein are divided under two headings, WARNING and CAUTION , those points which are related to the strong possibility of an installation done in error resulting in death or serious injury are listed in the WARNING section.
  • Page 186: Installation Of Indoor Unit

    1.5.1 Installation of indoor unit (1) Ceiling recessed compact type (FDTC) (a) Selection of installation location 1) Select location where the space above ceiling is larger than those mentioned below and perfect draining can be assured. 2) With the customer’s consent, select a location with following suitable conditions. a) Where cool air or hot air can easily pass through.
  • Page 187 (c) Suspension • Please arrange four sets of a suspension bolt (M10 or M8), a nut matching the bolt, a fl at washers and a spring washer on the installation site. When suspension from the ceiling This unit is designed for installation on a 2 × 2 grid ceiling. If necessary, please detach the T bar temporarily before you install it.
  • Page 188 3) Care must be taken so as not to allow an adhesive to run into the drain hose. When it is hardened, it can cause a breakage of a fl exible part, if the fl exible part receives stress. 4) Use VP-25 general-purpose hard PVC pipes for drain piping. 5) Insert the drain hose supplied as an accessory (soft PVC end) to the stepped part Stepped Drain hose piece...
  • Page 189 ♦ Setup from a remote controller side. Drain pump operation from a recomte controller unit is possible. Operate a remote controller unit by following the steps de- scribed below. To start a forced drain pump operation. Press the TEST button for three seconds or longer. The display will change from “...
  • Page 190 7) A panel is hooked on two bolts (± mark ) [Figure 4] [Figure 5] [Figure 4] 8) Please rotate a hook, put in the slot on the panel, and carry out fixing the panel temporarily. [Figure 5] 9) Tighten the two bolts used for fixing the panel temporarily and the other two. 10) Please open the lid of a control box.
  • Page 191: Ceiling Recessed Type (Fdt)

    (2) Ceiling recessed type (FDT) (a) Selection of installation location 1) Select location where the space above ceiling is larger than those mentioned right Model Space above ceiling (h) side and perfect draining can be assured. FDT151R, 201R, 251R, 301R Over 290mm 2) With the customer’s consent, select a location with following suitable conditions.
  • Page 192 (c) Suspension • Please arrange four sets of a suspension bolt (M10 or M8), a nut matching the bolt, a fl at washers and a spring washer on the installation site. When suspension from the ceiling 1) In the case of the standard series: Cut and opening of 860 ~ 890.
  • Page 193 Give the drain piping a descending grade (1/50-1/100) and never create Suspension 1.5 m ~ 2 m bolts a bump to go over or a trap. In connecting drain pipes, care must be taken so as not to apply force to the unit side piping and fix the pipe at a point as close to the unit as Insulation Desceding slope...
  • Page 194 ♦ Setup from a remote controller side. Drain pump operation from a remote controller unit is possible. Operate a remote controller unit by following the steps de- scribed below. To start a forced drain pump operation. Press the TEST button for three seconds or longer. The display will change from “...
  • Page 195 4) Removing the air return grille Raise up the notched portion of the air return grille and open it. With the air return grille open, remove the air return grille hinge from the decorator panel. 5) Removing the corner panel •...
  • Page 196 Connect the (white, 5p) louver motor con- nector. Place each of the connectors inside the con- trol box. Note (1) : If the air outlet louver does not operate using the remote controller, check the connector’s connection, then turn the main power supply OFF for 10 seconds or longer and turn the power ON again.
  • Page 197: Ceiling Suspended Type (Fden)

    8) Corner panel installation Hook the corner panel strap to the pin on the decorator panel as shown in the figure. Insert part on the corner panel in part on the decorator panel, then fit the 2 claws and fasten the corner panel screw.
  • Page 198 6) This unit uses a microcomputer as a control device. Therefore avoid installing the unit near the equipment that generates strong electromagnetic waves and noise. (b) Wireless remote control unit operation distance. 1) Standard signal receiving range. [Condition] Illuminance at the recelver area: 360 lux. (When no lighting fixture is located with in 1 m of indoor unit in an ordinary office) Ceiling sur face (Top view)
  • Page 199 3) Remove the suspension lug. Take out the screws, then loosen the installation bolt. Suspension lug screws (M4) Loosening Indoor unit margin 8~12 mm Suspension Lug for lug mounting suspension bolt (M8) 4) Suspension bolt position Lug for Using the paper pattern supplied as an accessory suspension as a criterion, select suspension bolt positions and piping hole positions, then install the suspension...
  • Page 200 3) In order to make it easier for water to drain out, install the unit so that the water drain side slopes down- ward. Front-rear direction Left-right direction ± ± (The figure shows the case where the drain hose is on the right side.) (If the connection is on the left side, reverse the slope.) If the slope is reversed, there is danger of water leaking out.
  • Page 201: Wall Mounted Type (Fdkn)

    WARNING Use the fitting supplied with the unit to connect the drain hose, fastening it at the lowest point so that there is no slack, and establishing a 10 mm drain slope. * Keep electrical wiring from running beneath the drain hose. Drain hose Drain hose Hose Clamp...
  • Page 202 Relation between illumination at receiver Caution item for close installation of unit and operating distance multiple units [Top view] [Top view] Receivalle range Receivalle range 60° [Condition] Illumination at suction grill face 800 lux 2) Cautions for operation Orient the remote control switch properly toward the receiver of the unit. Operating distance is as shown above but it may vary largely depending on the conditions.
  • Page 203 2) Cautions for left take-out and rear take-out case a) Looking down b) The piping can be taken out from the rear, left, left rear, right and down. For left running horizontal piping For right running horizontal piping For left rear take-out piping For right rear take-out piping Right For left running horizontal piping...
  • Page 204: Satellite Ducted Type (Fdum)

    (5) Satellite ducted type (FDUM) Selection of installation location 1) Avoid installation and use at those places listed below. a) Places exposed to oil splashes or steam (e.g. kitchens and machine plants). Installation and use at such places will incur deteriorations in the performance or corrosion with the heat exchanger or damage in molded synthetic resin parts.
  • Page 205 Suspension bolt M10 Suspension bolt M10 nuts M10 Washer Indoor unit Indoor unit M10 Spring washer Adjusting the unit’s levelness Adjust the out-levelness using a level vial or by the following method. • Make adjustment so that the relation between the lower surface of the indoor unit proper and water level in the hose becomes given below.
  • Page 206 Return air port • When shipped, the return air port lies on the back. • When connecting the duct to the return air port, remove the air filte if it is fitted to return air port. • When placing the return air port to carry out suction from the bottom side, use the following procedure to replace the return air duct joint and the bottom plate.
  • Page 207 • There is a possibility that the supply air volume may exceed the allowable range of operation due to the capacity of ventilation fan or strength of wind blowing against external air louver so that drainage from be heat exchanger may fail to reach the drain pan leak outside (e.g.
  • Page 208 When connecting the drain pipe to the unit, pay sufficient attention not to apply excess force to the piping on the unit side. Also, fix the piping at a point as close as possible to the unit. Level difference part For drain pipe, use hard PVC general purpose pipe VP-25 Drain socket Drain hose...
  • Page 209 Forced drain pump operation ♦ Setup from a unit side. Turn power on after selecting the emergency operation mode with a setting on the indoor unit control PCB (SW9-3 ON) and disconnecting the CnB connector on the board. Then, the drain pump will start a continuous operation 15 seconds later. (Note: The blower will also start operation in tandem) When a drain test is completed, reinstate the setting to cancel the emergency operation mode (SW9-3 OFF) and plug in the CnB connector on the board.
  • Page 210: High Static Pressure Duct Type (Fdu)

    (6) High static pressure duct type (FDU) (a) Selection of installation location Install the unit at a place as shown below and which meets the conditions as shown by the following table. Unit : mm Service Front view Top view space When the conditions as shown at All Series...
  • Page 211 (b) Installation <Packing hardware> <Securing of Hanging Bolt> <Delivery> Four pieces of packing hardware are When delivering the package, move Secure the hanging bolts by either one used. the package to the installation as close of following methods. as possible. Discard them after unpacking.
  • Page 212 <Simplifi ed method for determination of duct dimensions> In the following method, it is assumed that the friction resistance per unit length of duct is <Table of simplified selection of duct dimensions> 1 Pa/m (0.1 mm Aq/m) and a side of duct is 250 mm. Air volume rating is assumed to be FDUA1001R.
  • Page 213 F2•i6.3A•j F1•i6.3A•j...
  • Page 216: Installation Of Wired Remote Controller

    1.5.2 Installation of wired remote controller The length of each wire that should be left after a sheath is removed is as follows: (1) Selection of installation location Avoid the following locations Length of the (a) Direct sunlight. section where a sheath is removed (b) Close to heating device.
  • Page 217: Installation Of Outdoor Unit

    1.5.3 Installation of outdoor unit Notabilia as a unit designed for R410A • Do not use any refrigerant other than R410A. R410A will rise to pressure about 1.6 times higher than that of a conventional refrigerant. • A unit designed for R410A has adopted a different size indoor unit service valve charge port and a different size check joint provided in the unit to prevent the charging of a wrong refrigerant by mistake.
  • Page 218 1) Place the unit outlet pipe perpendicular to the wind direction. Over 500 mm 2) Please install so the direction of the air from the blowing outlet will be perpendicular to the direction of the wind. Wind direction Wind direction Wind direction Wind direction 3) When the foundation is not level, use wires to tie down the unit.
  • Page 219: Refrigerant Piping Work

    (2) Refrigerant piping work Select the piping specifi cation to fi t the specifi cation of indoor unit and installation location. (a) Decision of piping specifi cation (i) Single type Height difference Indoor unit • When the position of outdoor unit is higher than that of the indoor unit, keep the difference H=30 m or less.
  • Page 220 • The branch piping (both gas and liquid lines) should always be arranged to have a level or perpendicular branch. < 2-Way Branch > Floor Floor Floor Mount sections Mount sections level with the floor. perpendicular to the floor. < 3-Way Branch > Floor Floor Floor...
  • Page 221 (iv) Double twin type Models FDCVA802, 1002 [Branch pipe set : DIS-WA1 × 2set, DIS-WB1 × 1set] Indoor unit DIS-WA1 DIS-WB1 Gas line Outdoor unit Liquid line DIS-WA1 Item Liquid pipe Gas pipe Indoor unit combinations Main pipe 1st branch pipe 2nd branch pipe Main pipe 1st branch pipe...
  • Page 222 (c) Points for attention in installing refrigerant piping 1) Use pipes made of the following material Wires for connecting Material: Phosphorus deoxidized copper seamless pipes (C1220T, JIS indoor and outdoor H3300) units Exterior tape 2) Please dress the refrigerant piping (both gas and liquid pipes) with a heat Gas piping insulating material for prevention of dew condensation.
  • Page 223 How to remove the side cover • Models FDCVA151 ~ 302 First unscrew four screws holding the side cover in place, pull down the cover toward the direction indicated by the arrow, and then pull it toward you to remove it from the casing. Models FDCVA151, 201, 251 Model FDCVA302 •...
  • Page 224 2) Firstly, use the accessory pipe to assemble the connecting pipe assembly outside the outdoor unit. As shown in the fi gures of installation examples applicable to the connecting direction (chain double dashed line), braze the accessory pipe and the parts prepared in the above 1). Installation example Installation example Accessory pipe A...
  • Page 225: Air Tightness Test And Air Purge

    After connection of the connecting pipe assembly to the operation valve on the gas side, braze the connecting pipe assembly and the field pipe. Branching pipe set can be used by using the accessory pipe B. When φ22.22(OD) size of the indoor unit gas pipe is used, ±...
  • Page 226: Refrigerant Charge

    When a vacuum air purge is completed, remove the valve rod cap nuts and open the service valves (both liquid and gas sides) as illustrated below. After you have made sure that the valves are in the full-open position, lighten the cap nuts (for the valve rods and charge ports).
  • Page 227: Drain Piping Work

    (b) Charging refrigerant 1) Since R410A refrigerant must be charged in the liquid phase, you should charge it, keeping the container cylinder upside down or using a refrigerant cylinder equipped with a siphon tube. 2) Charge refrigerant always from the liquid side service port with the service valve shut. When you fi nd it diffi cult to charge a required amount, fully open the outdoor unit valves on both liquid and gas sides and charge refrigerant from the gas (suction) side service port, while running the unit in the cooling mode.
  • Page 228 Power cable, indoor-outdoor connecting wires Earth leakage breaker Earth leakage breaker (Harmonic resistant type) (Harmonic resistant type) Always perform grounding system installation work ± Switchgear or circuit breaker Switchgear or circuit breaker with the power cord unplugged. Outdoor unit Outdoor unit CAUTION Indoor unit Indoor unit...
  • Page 229 5) Set the same address for the master and slave indoor units as the communications address for the remote controller using rotary switch SW2 on the indoor units’ control PCB. 6) Set slave a, slave b and slave c using DIP switch SW5-1 and SW5-2 on the control PCB of the respective indoor slave units. 7) Be sure to press the AIR CON No.
  • Page 230: Setting Functions Using The Wired Remote Controller

    (7) Setting functions using the wired remote controller (a) The default settings of this unit’s functions are as follows: If you want to charge a setting, follow the pro- cedure found in the installation manual and set to your desired setting. For the method of setting, please refer to the installation manual of a remote controller.
  • Page 231 Indoor unit functions (I/U FUNCTION Function Default Function description B Setting C number A setting STANDARD (Mild mode) Hi CEILING SET Hi CEILING 1 (Powerful mode) NO DISPLAY AFTER 180H FILTER SIGN SET AFTER 600H AFTER 1000H 1000H→STOP FIX (1 OF 4) (4 positiion stop) Louver control POSITION setting...
  • Page 232 (b) Function setting method Operating guide message 1) Stop the air conditioner Function description: B , Settting: C Function number: A 2) Press the SET and MODE buttons simultaneously for 3 seconds or longer. The screen display will be switched as follows: Confirm Button “...
  • Page 233 When “I/U FUNCTION ” is selected. The screen display will be switched as follows: “ I/U SELECT” “ SET” “I/U No.00” (blinking) I/U No.00 Press either button. Select the indoor unit number that you want to change settings. If only one indoor unit is connected, the indoor unit number will not charge, so please proceed to Step If “ALL I/U ”...
  • Page 234 (c) Changing the remote control set temperature range 1) It is possible to change the set temperature range using the remote control. a) The upper and lower set temperature limits can be set from the remote control. Upper limit value setting: Effective during heating. The temperature can be set within a range of 20~30ºC. Lower limit value setting: Effective when running in modes other than the heating mode (AUTO, COOL, FAN, DRY): The temperature can be set within a range of 18~26ºC.
  • Page 235: Checking Operation Data

    • If the RESET button is pressed during a setting operation, the display returns to the previously displayed setting screen. However, settings which have not been fi xed become invalid, so exercise caution. * If “NO DISP CHANGE” is selected in No. 12, “TEMP RANGE SET” of the remote controller’s functions, of the func- tion setting modes, the remote controller’s display does not change even if the temperature range has been changed.
  • Page 236 Number Data item (Operation mode) SET TEMP RETURN AIR I/U HEAT EXCH 1 (Indoor unit heat exchanger temperature 1) I/U HEAT EXCH 2 (Indoor unit heat exchanger temperature 2) (Indoor unit fan speed) I/U FAN TOTAL I/U RAN (Indoor unit operation hours) OUTDOOR (Outside air temperature) O/U HEAT EXCH 1...
  • Page 237 ± Models FDCVA302 ~ 1002 WARNING • Before conduct a test run, do not fail to make sure that the service valves are not closed. A failure to observe • Turn on power 6 hours prior to a test run to energize the crank case heater. these instructions •...
  • Page 238: Test Run

    5) The state of the electronic expansion valve. The following table illustrates the steady states of the electronic expansion valve. When the unit comes to a normal stop When the unit comes to an anomalous stop When power is turned on During a During a During a...
  • Page 239: Maintenance Data

    MAINTENANCE DATA 1.6.1 Servicing (1) Evacuation The evacuation is a procedure to purge impurities, such as noncondensable gas, air, moisture from the refrigerant equipment by using a vacuum pump. Since the refrigerant R410A is very insoluble in water, even a small amount of moisture left in the refriger- ant equipment will freeze, causing what is called ice clogging.
  • Page 240: Trouble Shooting For Refrigerant Circuit

    (2) Refrigerant charging After the evacuation shown in the above, change the connection of the charge hose to the refrigerant cylinder. (b) Purge air from the charge hose First loosen the connecting portion of the charge hose at the gauge manifold side and open valve 3 for a few seconds, and then immediately retighten it after observing that gas has blown out from loosened connecting portion.
  • Page 241: Diagnosing Of Microcomputer Circuit

    1.6.3 Diagnosing of microcomputer circuit...
  • Page 243 (b) Display sequence of error, inspection display lamp 1) In case an error occurs Display corresponding to the error is shown. 2) In case several errors occur Section Display section • Displays the error of higher priority (When plural errors are persisting) Error code of remote controller ···········...
  • Page 244: Procedures Of Trouble Diagnosis

    4) Recording and reset of error Error display Memory Reset Error code of remote • Saves the error code with higher • Stop the unit operation by pressing the ON/OFF button of remote controller priority in memory controller. • Operation can be started again if the error has been restored. Indoor unit inspection lamp •...
  • Page 245 Parts layout on the indoor unit PCB Model: FDTC series PCB power supply Remote controller Float switch DPI switch connector (SW5) (Secondary side) CNW2 DPI switch Fan motor (SW9) J5~J7 (SW8) J1~J4 (SW7) SW10 Fan motor DPI switch LED2 (SW10) LED1 Heat exchanger thermistor,Return...
  • Page 246 Model: FDT series Fan motor To power supply (151~401) (CNW7) To power supply PCB (501, 601) (CNW9) CNW7 Louver motor CNM3 Fan motor CNW9 (501, 601) 52X8-1 52X7 52X6 52X1 52X2 52X3 PC2 PC1 52X4 Power supply PCB (CNW8) IC12 IC11 Remote LED2 LED1...
  • Page 247 Model: FDEN series PCB power supply connector (Primary side) Power supply CNW1 CNW0 CNM1 PCB power supply connector (Secondary side) Remote controller Fan motor DIP switch (SW5) J5~J7 SW10 (SW8) CNH CNN1 J1~J4 (SW7) DIP switch (SW9) Address switch Connector J9~J11 (SW2) (CNT)
  • Page 248 Model: FDKN series Heat exchanger thermistor, Return air thermistor Remote controller Heat exchanger thermistor (Thl-R1, Thl-A) (Thl-R2) TB,3 Dip switch (SW5) CNN1 TB,2 J9~J11 SW10 TB,1 (SW10) Dip switch (SW9) J5~J8 CNW1 (SW8) PCB power supply connector J1~J4(SW7) R151 (Primary side) C104 Adress switch IC10...
  • Page 249 Model: FDUM, FDU series Heat exchanger thermistor, Return air thermistor Address swith (Thl-R1, Thl-A) (SW2) (SW8) Heat exchanger thermistor DIP switch DIP switch (Thl-R2) (SW5) (SW9) Float switch Remote controller J10~J11 J1~J4 Connector (SW10) (SW7) (CNT) CNN1 CNN2 SW10 Drain motor LED2 LED1 52X3...
  • Page 250 (c) Check method when the error code is display Remote controller or LCD: Inspection LED, error code Indoor unit PCB: Red LED (inspection display), Green LED (CPU. normal display) Outdoor unit PCB: Red LED (inspection display), Green LED (CPU. normal display) Error display : No display [Power supply line error] LCD display : No display...
  • Page 251 Indoor unit Outdoor unit Red LED 3 time flash Red LED Stays OFF Keeps flashing Keeps flashing Green LED Green LED Is the wiring for remote Modify the connection. controller connected correctly? Approximately Remote controller wire Reset the power supply. disconnection? Normal? 10 ~ 11 V between...
  • Page 252 Indoor – outdoor communications trouble ” Error display “ WAIT Initial (when the power is turned on) If the power supply breaker is turned on again in a short Indoor unit Outdoor unit time (within 1 minute) the message “ WAIT ”...
  • Page 253 Models 302~1002 ± The “ WAIT ” display remains the same in the remote controller’s LCD ever 2 minutes Diagnosis if the has passed since the power supply was turned inverter PCB LED is OFF Turn OFF the power supply once and ON Is the LED on the outdoor again 3 minute later.
  • Page 254 ± Indication example in case of wrong interconnection Wrong connection example Indication Item and 2/N reversing Remote Control: “ WAIT ” Indoor: Green LED keeps flashing. Red LED stays OFF. Outdoor: Green LED keeps flashing. Red LED 2 time flash. Outdoor Unit Indoor Unit reversing...
  • Page 255 [Communication error between the remote controller and the Indoor unit] Error display Indoor unit Outdoor unit Red LED Stays OFF Red LED Stays OFF Green LED Keeps flashing Green LED Keeps flashing Voltage between X and Z Replace the Remove the remote controller approximately remote controller.
  • Page 256 Error display [Defective indoor unit heat exchanger thermistor] Indoor unit Outdoor unit Stays OFF Red LED 1 time flash Red LED Keeps flashing Green LED Keeps flashing Green LED Return air thermistor (Th Indoor unit heat exchanger thermistor R1, R2) Resistance-temperature characteristics Defective indoor unit control PCB Replace-ment (Defective indoor unit...
  • Page 257 Error display [Heating overload] Indoor unit Outdoor unit Stays OFF Red LED 1 time flash Red LED Keeps flashing Green LED Keeps flashing Green LED Notes (1) Check if the overload state exists or not using the following check points. Is there a short circuit? Clean it.
  • Page 258 [Control of 1 remote controller VS multiple units Error display : Excessive number of units (more than 17 units) ] Indoor unit Outdoor unit Stays OFF Red LED Stays OFF Red LED Keeps flashing Green LED Keeps flashing Green LED Are more than 17 units connected Reduce to 16 units...
  • Page 259 [Fan motor abnormalities] Error display Indoor unit Outdoor unit Stays OFF Red LED 3 time flash Red LED Keeps flashing Green LED Keeps flashing Green LED Only case of FDTA501, 601 types Check the operation data by the remote controller. Reset the error code and operate the fan in fan mode with Lo fan speed.
  • Page 260 Only in case of FDKN Check the operation data by the remote controller. Reset the error code and operate the fan in fan mode with Lo fan speed. Does the fan operate? 3 (Black) is GND. Check the Is the error Replace the indoor 1 and 3 (Red - Black) circumstances.
  • Page 261 Error display : [Defective remote controller thermistor.] Indoor unit Outdoor unit Red LED Stays OFF Red LED Stays OFF Green LED Keeps flashing Green LED Keeps flashing Are characteristics of Is the remote controller Remote controller thermistor is remote controller therm- thermistor connector co- defect.
  • Page 262: Error Diagnosis Procedures At The Outdoor Unit Side

    (4) Error diagnosis procedures at the outdoor unit side At the error diagnosis related to the outdoor unit, fi rst of all check the error code on the remote controller and the illumination patterns of norma1 and inspection display lamps in the same manner as the case of indoor unit. Then estimate the outline, the cause and the location of failure based on the pattern and proceed to the inspection and repair.
  • Page 263 Parts layout on the outdoor unit PCB Models FDCVA151HENR, 201HENR, 251HENR Sub PCB (Noise filter) Reactor Fan motor Stepping motor CNV1 CNI2 CNI3 Outdoor air temp. thermistor, Outdoor heat exchanger thermistor, Discharge pipe thermistor (Tho-A, Tho-R, Tho-D) DIP switch DIP switch Power transistor thermistor (SW6) (SW7)
  • Page 264 Model FDCVA302HENR Thermistor (Tho-R1,Tho-D,Tho-S,Tho-A) CNTH Thermistor (Tho-IP) CNPS CNEEV1 CNEEV2 CNFAN Lower pressure High pressure switch sensor Fan motor (63H1) (PSL) Electronic Solenoid valve Crank case heater expansion valve (SV1) 4way valve (EEVC,EEVH) Function of DIP switch (SW3, 5, 7, 8) ±...
  • Page 265 Models FDCVA402HENAR, 502HENAR, 602HENAR FDCVA402HESAR, 502HESAR, 602HESAR, 802HESAR, 1002HESAR (This fi gure shows FDCVA402~602 model. The component layout of FDCVA802 and 1002 models are basically the same except for partial arrangement.) Expansion valve Model setting switch High pressure switch Outdoor unit (SM1, 2) JSW1 power supply...
  • Page 266 Parts layout on the outdoor unit inverter PCB Model FDCVA302HENR JSW11 Match to the PCB conditions LED1 that existed before replacement. JSW10 Match to the PCB conditions that existed before replacement. Notes (1) Apply the silicone grease supplied with the component uniformly to the surface of the power transistor on the new PCB, then mount it on the PCB. If the grease is not applied, the power transistor may be damaged.
  • Page 267 Models FDCVA402HESAR, 502HESAR, 602HESAR Match to the PCB conditions that existed before replacement. JSW10 JSW11 Match to the PCB conditions that existed before replacement. Notes (1) Apply the silicone grease supplied with the component uniformly to the surface of the power transistor on the new PCB, then mount it on the PCB. If the grease is not applied, the power transistor may be damaged.
  • Page 270 –...
  • Page 273 Error display : [Communications error during operation] Indoor unit Outdoor unit 2 time flash Red LED 2 time flash Red LED Keeps flashing Green LED Keeps flashing Green LED Is the connection Is the connection See the diagnosis flowchart for “...
  • Page 274 Error display : [Power supply open phase] [Only case of 302~1002 models] Indoor unit Outdoor unit 1 time flash Red LED Stays OFF Red LED Keeps flashing Green LED Keeps flashing Green LED Measure the power supply voltage. Is the voltage between the phases Check the power supply.
  • Page 275 Error display : [Cooling overload operation] Indoor unit Outdoor unit 1 time flash Red LED Stays OFF Red LED Keeps flashing Green LED Keeps flashing Green LED ± Models FDCVA151~251 Check the unit side. • Is there a short circuit in the outdoor unit? •...
  • Page 276 ± Models FDCVA302~1002 Check the unit side. Are the • Is there a short circuit in the outdoor unit? characteristics of Is there cooling overload • Is the installation space proper? the outdoor heat exchanger operation? • Is it overcharged? thermistor •...
  • Page 277 Error display : [Discharge temperature error] Indoor unit Outdoor unit 1 time flash Red LED Stays OFF Red LED Keeps flashing Green LED Keeps flashing Green LED Is the Check the unit side. Anomalous discharge Check the unit side. discharge pipe ther- temperature? •...
  • Page 278 Error display : [Defective outdoor unit heat exchanger thermistor] Indoor unit Outdoor unit 1 time flash Red LED Stays OFF Red LED Keeps flashing Green LED Keeps flashing Green LED Is the outdoor The outdoor unit heat exchanger Are the outdoor unit unit heat exchanger thermistor is defective.
  • Page 279 Error display : [Defective discharge pipe thermistor] Indoor unit Outdoor unit 1 time flash Red LED Stays OFF Red LED Keeps flashing Green LED Keeps flashing Green LED Is the discharge Are the discharge The outdoor unit control PCB is pipe thermistor pipe thermistor defective...
  • Page 280 Error display : [Power transistor is overheating] [Only case of 402~1002 models] Indoor unit Outdoor unit 1 time flash Red LED Stays OFF Red LED Keeps flashing Green LED Keeps flashing Green LED Is it possible to reset the Disconnect the outdoor unit’s fan Does the Replace the outdoor error code after 10 minutes...
  • Page 281 Error display : [Current cut] Indoor unit Outdoor unit 1 time flash Red LED Stays OFF Red LED Keeps flashing Green LED Keeps flashing Green LED Note (1) 0.4 low moro at 25˚C. Check the Is the high Is the power compressor's insulation Is the service pressure during operation...
  • Page 282 Error display : [Only case of 151 ~ 251, 302 models] Indoor unit Outdoor unit 1 time flash Red LED Stays OFF Red LED Keeps flashing Green LED Keeps flashing Green LED [Inverter over-voltage trouble] • Models FDCVA151 ~ 251 Is there any foreign object Remove the foreign object such as dust or dirt on the soldered...
  • Page 283 Error display : [DC Fan motor failure] Indoor unit Outdoor unit 1 time flash Red LED Stays OFF Red LED Keeps flashing Green LED Keeps flashing Green LED • Models FDCVA151~251 Is there Does some any foreign object Does the fan Is fuse F3 Replace the outdoor object obstruct...
  • Page 284 Error display : [Anomalous low pressure or low pressure sensor disconnection.] [Only case of 302 ~ 1002 models] Indoor unit Outdoor unit 1 time flash Red LED Stays OFF Red LED Keeps flashing Green LED Keeps flashing Green LED Is there any gap between actual pressure and sensed pressure by the microcomputer? Are the low pressure sensor...
  • Page 285 Error display : [Inverter, fan motor fault] [Only case of 302 ~ 1002 models] Indoor unit Outdoor unit Lights contiously Red LED Stays OFF Red LED Keeps flashing Green LED Keeps flashing Green LED Are the screws to fix the power Occurs transistor fastened tightly? Replace the outdoor...
  • Page 286 Error display : [Low pressure sensor fault] [Only case of 302~1002 models] Indoor unit Outdoor unit 1 time flash Red LED Stays OFF Red LED Keeps flashing Green LED Keeps flashing Green LED Are the low pressure sensor Correct it connector (sensor side, board side) connected properly? Does the actual pressure match...
  • Page 287 Error display : [Power transistor thermistor fault] [Only case of 151~251 models] Indoor unit Outdoor unit 1 time flash Red LED Stays OFF Red LED Green LED Keeps flashing Outdoor unit control PCB is Is the Are the power defect Replace it (Power power transistor thermistor transistor thermistor...
  • Page 288 [Anomaly in compressor starting] Error display : • Models FDCVA151~251 Indoor unit Outdoor unit 1 time, 2 time, 3 time flash Red LED Stays OFF Red LED Green LED Keeps flashing Check Inverter Check the Is the power Is the balance the compressor Replace the power transistor...
  • Page 289 [Compressor loader position detection error] Error display : [Only case of 151 ~ 251, 802, 1002 models] Indoor unit Outdoor unit 1 time flash Red LED Stays OFF Red LED Green LED Keeps flashing Keep flashing Note (1) Check if the power supply system is normal. Operate the Does it It doesn’t...
  • Page 290 Power transistor module (including the driver PCB) inspection procedure Is the power transistor module cracked or burnt? Is there a short circuit between the power transistor module ∗ terminals? Compressor operation Is there any difference in the compressor current If there is a 10% or greater difference between phases? in the current in different phases.
  • Page 291: Inspection Procedure For The Failure Which Doesn't Have An Error Code

    (5) Inspection procedure for the failure which doesn’t have an error code (a) Louver motor does not operate Inspect at the indoor unit side. Does the The indoor unit PCB is Is the LM louver move when Is the LM wire defective.
  • Page 292: Check Anomalous Operation Data With The Wired Remote Controller

    (6) Check anomalous operation data with the wired remote controller Operation data are recorded when there is an anomalous state and these data can be displayed in the remote controller by operating the remote controller buttons. (1) Press the CHECK button. FUNCTION”...
  • Page 293: Error Code

    1.6.4 Check display on wireless specifi cation models (FDEN · FDKN· FDT) (1) Indication board (a) FDEN Series Romote controller signal receiving part Backup switch TIMER CHECK Operation display light (Green) • Lights continuously: Under air conditioner operation • Keeps flashing: Under heating preparation (At the time of heating operation) •...
  • Page 294 2. MULTI-TYPE (V MULTI) PACKAGED AIR-CONDITIONER CONTENTS 2.1 GENERAL INFORMATION ..................292 2.1.1 Specifi c features ....................292 2.1.2 How to read the model name ................292 2.1.3 Table of models ....................293 2.1.4 Table of system combinations ................293 2.2 SELECTION DATA ....................
  • Page 295: General Information

    (3) Energy labeling “Class A” MHI models have cleared the class A standard, the highest energy saving level, with their high COP (coeffi cient of performance). (4) The microcomputer chip is installed in the indoor unit and outdoor unit. There is no need for the unit to communicate between the outdoor and indoor units so the unit is more resistant to electromagnetic noise thus the incidence of microcomputer malfunction has been reduced.
  • Page 296: Table Of Models

    2.1.3 Table of models Capacity Model Ceiling recessed compact type (FDTC) Ceiling recessed type (FDT) Ceiling suspended type (FDEN) Wall mounted type (FDKN) Satellite ducted type (FDUM) FDCVA302HENR FDCVA502HENAR FDCVA602HENAR FDCVA802HESAR FDCVA1002HESAR (3 Horse Power) FDCVA502HESAR FDCVA602HESAR (8 Horse Power) (10 Horse Power) Outdoor unit to be combined (FDC) FDCVA402HENAR...
  • Page 297: Selection Data

    SELECTION DATA 2.2.1 Specifi cations (1) Indoor unit (a) Ceiling recessed compact type (FDTC) Models FDTCA151R, 201R Model FDTCA151R FDTCA201R Item ( 1) Nominal cooling capacity ( 1) Nominal heating capacity Power source 1 Phase, 220-240V 50Hz / 220V 60Hz Powerful mode Hi: 46 Me : 42 Lo: 38 Noise level dB(A)
  • Page 298: (B) Ceiling Recessed Type (Fdt)

    (b) Ceiling recessed type (FDT) Models FDTA151R, 201R, 251R Model FDTA151R FDTA201R FDTA251R Item ( 1) Nominal cooling capacity ( 1) Nominal heating capacity Power source 1 Phase, 220-240V 50Hz / 220V 60Hz Powerful mode Hi: 36 Me : 33 Lo: 32 Powerful mode Hi: 38 Me : 35 Lo: 33 Noise level dB(A)
  • Page 299 Models FDTA301R, 401R Model FDTA301R FDTA401R Item ( 1) Nominal cooling capacity 10.0 ( 1) Nominal heating capacity 11.2 Power source 1 Phase, 220-240V 50Hz / 220V 60Hz Powerful mode Hi: 38 Me: 35 Lo: 33 Powerful mode Hi: 46 Me: 43 Lo: 41 Noise level dB(A) Mild mode Hi: 35 Me: 33 Lo: 31...
  • Page 300 Model FDTA501R Model FDTA501R Item ( 1) Nominal cooling capacity 12.5 ( 1) Nominal heating capacity 14.0 Power source 1 Phase, 220-240V 50Hz / 220V 60 Hz Powerful mode Hi: 48 Me: 45 Lo: 43 Noise level dB(A) Mild mode Hi: 45 Me: 43 Lo: 40 Unit:365 Exterior dimensions Height...
  • Page 301: (C) Ceiling Suspended Type (Fden)

    (c) Ceiling suspended type (FDEN) Models FDENA151R, 201R, 251R Model FDENA151R FDENA201R FDENA251R Item ( 1) Nominal cooling capacity ( 1) Nominal heating capacity Power source 1 Phase, 220-240V 50Hz / 220V 60Hz Powerful mode Hi: 42 Me : 39 Lo: 38 Powerful mode Hi: 44 Me : 41 Lo: 39 Noise level dB(A)
  • Page 302 Models FDENA301R, 401R Model FDENA301R FDENA401R Item ( 1) Nominal cooling capacity 10.0 ( 1) Nominal heating capacity 11.2 Power source 1 Phase, 220-240V 50Hz / 220V 60Hz Powerful mode Hi: 44 Me: 41 Lo: 39 Powerful mode Hi: 46 Me: 44 Lo: 41 Noise level dB(A) Mild mode Hi: 41 Me: 39 Lo: 38...
  • Page 303 Model FDENA501R Model FDENA501R Item ( 1) Nominal cooling capacity 12.5 ( 1) Nominal heating capacity 14.0 Power source 1 Phase, 220-240V 50Hz / 220V 60Hz Powerful mode Hi: 48 Me: 46 Lo: 44 Noise level dB(A) Mild mode Hi: 46 Me: 44 Lo: 43 Exterior dimensions 1620 Height...
  • Page 304: (D) Wall Mounted Type (Fdkn)

    (d) Wall mounted type (FDKN) Models FDKNA151R, 201R Model FDKNA151R FDKNA201R Item ( 1) Nominal cooling capacity ( 1) Nominal heating capacity Power source 1 Phase, 220-240V 50Hz / 220V 60Hz Powerful mode Hi: 44 Me: 42 Lo: 40 Powerful mode Hi: 47 Me: 44 Lo: 41 Noise level dB(A) Mild mode Hi: 42 Me: 40 Lo: 37...
  • Page 305 Model FDKNA251R Model FDKNA251R Item ( 1) Nominal cooling capacity ( 1) Nominal heating capacity Power source 1 Phase, 220-240V 50Hz / 220V 60Hz Powerful mode Hi: 48 Me: 45 Lo: 42 Noise level dB(A) Mild mode Hi: 45 Me: 42 Lo: 39 Exterior dimensions Height Width...
  • Page 306: (E) Satellite Ducted Type (Fdum)

    (e) Satellite ducted type (FDUM) Models FDUMA202R, 252R, 302R Models FDUMA202R FDUMA252R FDUMA302R Item Nominal cooling capacity* Nominal heating capacity* Power source 1 Phase 220-240V 50Hz/220V 60Hz Noise level dB(A) Hi: 34 Me: 31 Lo: 28 Hi: 35 Me: 32 Lo: 29 Exterior dimensions Height Width...
  • Page 307 Models FDUMA402R, 502R Models FDUMA402R FDUMA502R Item Nominal cooling capacity* 10.0 12.5 Nominal heating capacity* 11.2 14.0 Power source 1 Phase 220-240V 50Hz/220V 60Hz Noise level dB(A) Hi: 37 Me: 35 Lo: 32 Hi: 38 Me: 36 Lo: 33 Exterior dimensions 1370 Height Width...
  • Page 308: Outdoor Unit

    (2) Outdoor unit Model FDCVA302HENR Model FDCVA302HENR Item Power source 1 Phase, 220-240V 50Hz / 220V 60Hz ( 1) Nominal cooling capacity 7.1 [3.5~8.0] ( 1) Nominal heating capacity 8.1 [4.0~9.0] Noise level dB(A) Exterior dimensions 880(+88) Height Width Depth Net weight Refrigerant equipment 2YC45DXD 1...
  • Page 309 Model FDCVA402HENAR Model FDCVA402HENAR Item Power source 1 Phase, 220-240V 50Hz/220V 60Hz ( 1) Nominal cooling capacity 10.0 [6.1~11.2] ( 1) Nominal heating capacity 11.2 [5.6~12.5] Noise level dB(A) Exterior dimensions Height Width Depth Net weight Refrigerant equipment RM-B5125MDE21 1 compressor type &...
  • Page 310 Model FDCVA402HESAR Model FDCVA402HESAR Item Power source 3 Phase, 380-415V 50Hz/380V 60Hz ( 1) Nominal cooling capacity 10.0 [6.1~11.2] ( 1) Nominal heating capacity 11.2 [5.6~12.5] Noise level dB(A) Exterior dimensions Height Width Depth Net weight Refrigerant equipment RM-B5125MDE31 1 compressor type &...
  • Page 311 Models FDCVA502HENAR, 602HENAR Model FDCVA502HENAR FDCVA602HENAR Item Power source 1 Phase, 220-240V 50Hz/220V 60Hz ( 1) Nominal cooling capacity 12.5 [6.5~14.0] 14.0 [6.7~14.8] ( 1) Nominal heating capacity 14.0 [6.2~16.0] 16.0 [6.3~16.8] Noise level dB(A) Exterior dimensions Height Width Depth Net weight Refrigerant equipment RM-B5125MDE21 1...
  • Page 312 Models FDCVA502HESAR, 602HESAR Model FDCVA502HESAR FDCVA602HESAR Item Power source 3 Phase, 380-415V 50Hz/380V 60Hz ( 1) Nominal cooling capacity 12.5 [6.5~14.0] 14.0 [6.7~14.8] ( 1) Nominal heating capacity 14.0 [6.2~16.0] 16.0 [6.3~16.8] Noise level dB(A) Exterior dimensions Height Width Depth Net weight Refrigerant equipment RM-B5125MDE31 1...
  • Page 313 Model FDCVA802HESAR, 1002HESAR Model FDCVA802HESAR FDCVA1002HESAR Item Power source 3 Phase, 380-415V 50Hz/380V 60Hz ( 1) Nominal cooling capacity 20.0 [7.0~22.4] 25.0 [10.6~28.0] ( 1) Nominal heating capacity 22.4 [7.6~25.0] 28.0 [9.5~31.5] Noise level dB(A) Cooling: 57, Heating: 58 Exterior dimensions 1300 1505 Height...
  • Page 314: Operation Chart

    (3) Operation chart The Multi-Type V series is a system that allows for different models and capacities of indoor units to be connected so the individual operating characteristics of the indoor and outdoor are provided. Use the procedure shown in Item (c) to calculate the combined operating characteristics.
  • Page 315 FDUM Series (220-240V 50Hz/220V 60Hz) Model FDUMA202R FDUMA252R FDUMA302R FDUMA402R FDUMA502R Item Cooling power consumption 0.14-0.16/0.14 0.15-0.17/0.15 0.16-0.19/0.16 0.24-0.28/0.24 0.28-0.32/0.32 Heating power consumption 0.14-0.16/0.14 0.15-0.17/0.15 0.16-0.19/0.16 0.24-0.28/0.24 0.28-0.32/0.32 Cooling running current 0.63-0.67/0.63 0.68-0.71/0.68 0.73-0.79/0.73 1.07-1.17/1.07 1.28-1.32/1.28 Heating running current 0.63-0.67/0.63 0.68-0.71/0.68 0.73-0.79/0.73 1.07-1.17/1.07...
  • Page 316 Total power factor (%) × 100 . = . 99 % 4.78 × 1000 (Cooling) 21.1 × 220 4.58 × 1000 × 100 . = . 99 % (Heating) 20.2× 220 2) 3 Phase models a) Total power consumption Total power consumption (kW) = Power consumption of outdoor unit + ∑ (Power consumption of indoor unit) b) Total running current Total running current (A) = Running current of outdoor unit + [∑...
  • Page 317: Range Of Usage & Limitations

    2.2.2 Range of usage & limitations Model FDCVA302~602 FDCVA802, 1002 Item Indoor return air temperature (Upper, lower limits) Please see the next page. Outdoor air temperature (Upper, lower limits) Operating temperature When used under -5ºC, install a snow hood (option). Indoor unit atmosphere (behind ceiling) Dew point temperature: 28ºC or less, relative humidity: 80% or less temperature and humidity...
  • Page 318 Cooling Range of cooling usage Indoor air W.B. temperature (˚CW.B.) Heating Range of heating usage Outdoor air W.B. temperature (˚CW.B.) Height and length restrictions for refrigerant piping Models 302~602 One-way pipe length (m) L +ra +rb Twin type 10, ra 20, rb Branch pipe length (m) Ira –rb I...
  • Page 319 Double-twin type Outdoor unit Indoor unit Models 802, 1002 One-way pipe length (m) L +ra 70, L +rb 70, L +rc 70, L +rd 10, Ira – rc I 10, Irb – rc I Branch pipe length (m) Ira –rb I 10, Irb –...
  • Page 320: Exterior Dimensions

    2.2.3 Exterior dimensions Details are the same as in chapter 1.2.3 see page 93. 2.2.4 Inside view Details are the same as in chapter 1.2.4 see page 113. 2.2.5 Exterior appearance Details are the same as in chapter 1.2.5 see page 116. 2.2.6 Piping system Details are the same as in chapter 1.2.6 see page 119.
  • Page 321 3. WIRELESS KIT (OPTIONAL PARTS) FDT series The FDT series is an exclusive series with all wired models. However, these models can also be used as wireless units by using the optional wireless kit. Model Model FDT series all model Wireless kit model Model Paint color...
  • Page 322 (4) Wireless remote controller unit: mm (5) Attachment of wireless kit (a) Installation of the receiver 1) Preparation before installation Attachthe cover panel supplied as an accessory onto the indoor unit according to the panel installation. (Refer to 193 page) Remove the air return grille.
  • Page 323 Turn switches provided on the back of the PCB. Switches (SW1-4) provided on the receiver PCB are for setting the following. All switched are set to the ON position for shipment. Default setting Prevention of unintended ON:Normal movement caused by interference. OFF:Remote ON:Master Receiver master/slave setting...
  • Page 324 (6) Control of a plural number of indoor units with one remote controller (a) Up to 16 indoor units can be connected. Connect indoor unit’s X , Y and Z terminal Terminal block swith 3-core connecting wires (remote controller X Y Z Indoor unit Indoor unit (16)
  • Page 325: Safety Precautions

    FDTC • FDUM • FDU series This product is dedicated for heat pump unit. Never install on the unit dedicated for cooling. SAFETY PRECAUTIONS • Always read these “Safety Precautions” thoroughly before starting installation work. • These precautions describe important information related to safety. Always observe these precautions. •...
  • Page 326 Wireless remote Light detection adaptor substrate ± ± controller All switches are turned Prevention of malfunction O N : Normal SW1-1 ON when the product is from mixed signals OFF : Remote shipped from the factory. O N : Master Receiver master/slave switching SW1-2 OFF : Slave...
  • Page 327 Installation with enclosed bracket Use this method when installing onto a gypsum board (7 or 18 mm), etc. 1 Catch the two protrusion of the enclosed bracket onto the fitting as shown above, and temporarily fix with the screws. (The bracket has an up/down and front/back orientation. Confirm the top/bottom protrusion positions and the positional relation of the ø...
  • Page 328 Wireless remote controller operation distance a) When installed on ceiling standard reception distance Reception section illuminance 300 lux (When there are no lights on the ceiling within 1 m or the Conditions reception adaptor in a general office.) Relation of reception section illuminance and reception distance looking from fl at plane Relation of the reception section illuminance and reception distance when the remote controller is Conditions operated at a height of 1 m from the fl...
  • Page 329 MULTI-TYPE (V-MULTI) PACKAGED AIR-CONDITIONER Air-Conditioning & Refrigeration Systems Headquarters 16-5, 2-chome, Kounan, Minato-ku, Tokyo, 108-8215, Japan Fax : (03) 6716-5926...