Mitsubishi Heavy Industries FDTC50ZHXV Technical Manual page 87

Hide thumbs Also See for FDTC50ZHXV:
Table of Contents

Advertisement

Model FDU250VSV
Item
Nominal cooling capacity
(1)
Nominal heating capacity
(1)
Power source
Cooling power consumption
Running current (Cooling)
Power factor (Cooling)
Heating power consumption
Running current (Heating)
Power factor (Heating)
Inrush current (L.R.A) <Max. running current>
Noise level
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q'ty
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
Defrost control
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air flow
Available static pressure
Outside air intake
Air filter, Q'ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
Notes (1) The data are measured at the following conditions.
Operation
Cooling
Heating
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 "UNITARY AIR-CONDITIONERS"
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
(5) Be sure to use the accessory pipe to connect service valve on the gas side with the field pipe.(Refer to the 1.5.3).
Model
kW
kW
kW
A
%
kW
A
%
A
dB(A)
mm
kg
Louver fin & inner grooved tubing
kg
r
W
CMM
Pa
W
Wired remote control switch (Optional : RC-E3)
Wireless kit (Optional : RCN-KIT3-E)
Internal thermostat for fan motor.
mm
(in)
Connectable with VP25 (I.D. 25mm, O.D. 32mm)
Indoor air temperature
Item
DB
27˚C
20˚C
FDU250VSV
FDU250V
25.0 [10.0~28.0]
28.0 [9.5~31.5]
3 Phase, 380–415V 50Hz/380V 60Hz
Hi: 51
360 × 1570 × 830
92
Microcomputer controlled de-icer
Centrifugal fan × 4
270 × 2
Direct line start
Hi: 68/80
Standard:100, Max:200
Possible (on return duct)
Installed on site
Rubber sleeve (for fan motor)
Thermostat by electronics
Frost protection thermostat.
Liquid line: φ12.7 (1/2ʺ) Gas line: φ22.22 (7/8ʺ)
Brazing piping (Outdoor liquid piping: Flare)
Necessary (both Liquid & Gas lines)
Reducer kit (Please see 1.5.3), Accessory pipe (Please see 1.5.3)
Outdoor air temperature
WB
DB
19˚C
35˚C
7˚C
86
-
-
FDC250VS
9.91/10.21
15.7/17.0
91/91
8.50/8.22
14.4/14.7
85/85
5 <27>
Cooling:57, Heating:58
1505 × 970 × 370
140
GTC5150ND70K × 1
Direct line start
Straight fin & inner grooved tubing
Electronic expansion valve
R410A
7.2 [Pre-charged up to the piping length of 30m]
1.45 (M-MA32R)
Propeller fan × 2
86 × 2
Direct line start
Cooling:150, Heating:145
Rubber sleeve (for compressor)
33 (Crank case heater)
– (Indoor unit side)
Internal thermostat for fan motor.
Anomalous discharge temperature protection.
(6)
Holes size φ20 × 3 pcs
WB
24˚C
6˚C
Standards
ISO-T1

Hide quick links: