Mitsubishi Heavy Industries FDTC50ZHXV Technical Manual page 263

Hide thumbs Also See for FDTC50ZHXV:
Table of Contents

Advertisement

◆ Model: FDUM, FDDU, FDEN series
①Set an appropriate address and Master/Slave setting by using dip switches.
Set the same setting with the PCB removed from the unit.
②Set to an appropriate capacity by using the model selector switch(SW6).
 Select the same capacity with the PCB removed from the unit.
SW6
-1
-2
-3
-4
40V
50V
60V
71V
〇:ON -:OFF
③Replace the PCB
1. Fix the PCB so as not to pinch the wirings.
2. Be sure to connect the connectors with same color of the PCB connectors.
3. Be sure not to pass the wirings on the surface of PCB (especially CPU).
④Control PCB
The parts mounted on PCB are different with respect to each PCB.
CNW1(White)
Primary transformer
SW5 Master/Slave
setting
CNM3(White)
Fan motor
CNJ2(Blue)
Louver motor
CNR(White)
Drain pump
CNJ(White)
Lover motor
Pulse
SW6
-1
-2
-3
-4
100V
200V
125V
250V
140V
Part number
CNE(White)
RAM checker
item
switch
Address
SW2
Master /Slave
SW5-1
setting
SW5-2
Test run
SW7-1
SW6
SW6
-1
-2
-3
-4
Example setting for 50V
SW2 (Blue)
CNW0(Red)
Address setting
Power source
CNG(Blue)
SW7
SW6
254
Content of control
Plural indoor units control by 1 remote controller
Master
Slave1
Operation check/drain motor test run
〇:ON -:OFF
ON
1
2
3
4
Slave2
Slave3
Normal
CNW2(Black)
Secondary
transformer
CNB(White)
Remote
controller

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents