Mitsubishi Heavy Industries SCM50ZS-W Service Manual

Mitsubishi Heavy Industries SCM50ZS-W Service Manual

Inverter multi-split system residential air-conditioners split system, air to air heat pump type outdoor indoor unit wall mounted/ceiling concealed/4-way ceiling cassette/ceiling suspended/duct connected-low/middle static pressure type
Table of Contents

Advertisement

SERVICE MANUAL
INVERTER MULTI-SPLIT SYSTEM
RESIDENTIAL AIR-CONDITIONERS
(Split system, air to air heat pump type)
(OUTDOOR UNIT)
SCM50ZS-W
60ZS-W
(INDOOR UNIT)
Wall mounted type
SRK20ZSX-W,-WB,-WT
25ZSX-W,-WB,-WT
35ZSX-W,-WB,-WT
50ZSX-W,-WB,-WT
60ZSX-W,-WB,-WT
SRK20ZS-W,-WB,-WT
25ZS-W,-WB,-WT
35ZS-W,-WB,-WT
50ZS-W,-WB,-WT
SKM20ZSP-W
25ZSP-W
35ZSP-W
Ceiling concealed type
SRR25ZM-W
35ZM-W
50ZS-W
60ZS-W
Ceiling suspended type
FDE50VH
Duct connected-Low/Middle static pressure type
FDUM50VH
Manual No.'19・SCM-SM-281
4-way ceiling cassette type
FDTC25VH
35VH
50VH
60VH

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Heavy Industries SCM50ZS-W

  • Page 1 Manual No.'19・SCM-SM-281 SERVICE MANUAL INVERTER MULTI-SPLIT SYSTEM RESIDENTIAL AIR-CONDITIONERS (Split system, air to air heat pump type) (OUTDOOR UNIT) SCM50ZS-W 60ZS-W (INDOOR UNIT) Wall mounted type Ceiling concealed type 4-way ceiling cassette type SRK20ZSX-W,-WB,-WT SRR25ZM-W FDTC25VH 25ZSX-W,-WB,-WT 35ZM-W 35VH 35ZSX-W,-WB,-WT...
  • Page 3: Table Of Contents

    '19 • SCM-SM-281 CONTENTS 1. OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER ....7 1.1 SRK, SKM and SRR series ................7 1.1.1 SRK-ZSX series ..................7 (1) Operation control function by wireless remote control .......7 (2) Unit ON/OFF button ...................8 (3) Auto restart function ..................8 (4) Installing two air-conditioners in the same room ..........8...
  • Page 4 '19 • SCM-SM-281 (11) Timer operation ..................22 (12) Silent operation ..................22 (13) Night setback operation ................22 (14) Air flow range setting ................23 (15) Display brightness adjustment ..............23 (16) Outline of dehumidifying (DRY) operation ..........24 (17) Outline of automatic operation ..............24 (18) Protective control function ................25 1.1.3 SKM-ZSP series ..................26...
  • Page 5 '19 • SCM-SM-281 (12) Outline of dehumidifying (DRY) operation ..........37 (13) Outline of automatic operation ...............37 (14) Operation permission/prohibition control ..........38 (15) External control (remote display)/control of input signal .......38 (16) Hot keep operation ................39 (17) Frost prevention control .................39 (18) Indoor fan motor protection ..............39 1.2 FDTC, FDUM and FDE series...
  • Page 6 '19 • SCM-SM-281 (24) Fan control at heating startup ..............60 (25) Room temperature detection temperature compensation during heating ....60 (26) Return air temperature compensation ............60 (27) High power operation (RC-EX3A only) .............60 (28) Energy-saving operation (RC-EX3A only) ..........60 (29) Warm-up control (RC-EX3A only) ............60 (30) Home leave mode (RC-EX3A only) ............60...
  • Page 7 '19 • SCM-SM-281 (12) Outdoor unit failure ..................72 ..72 (13) Discharge pipe temperature sensor disconnection protection control (14) Regulation of outdoor air flow ..............73 (15) Serial signal transmission error protection ..........73 (16) Rotor lock ....................73 (17) Outdoor fan motor protection ....
  • Page 8 '19 • SCM-SM-281 (2) Troubleshooting ..................109 3. ELECTRICAL WIRING ..................153 4. PIPING SYSTEM ..................161...
  • Page 9: Outline Of Operation Control By Microcomputer

    '19 • SCM-SM-281 1. OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER 1.1 SRK, SKM and SRR series 1.1.1 SRK-ZSX series (1) Operation control function by wireless remote control Transmission section Operation section ON/OFF (luminous) button OPERATION MODE select button Press to start operation, press again Each time the button is pressed, the to stop.
  • Page 10: Unit On/Off Button

    '09•SRK-DB-087D '19 • SCM-SM-281 '09•SRK-DB-087D (2) Unit ON/OFF button (2) Unit ON/OFF button wireless wireless (a) Operation (a) Operation (b) Details of operation room (b) Details of operation whether to go into the COOL or HEAT modes. Function Room temperature Fan speed Flap/Louver Timer switch setting Operation mode...
  • Page 11: Selection Of The Annual Cooling Function

    '19 • SCM-SM-281 Jumpre wire (J1) (5) Selection of the annual cooling function (a) The annual cooling control is valid from factory default setting. It is possible to disable by cutting jumper wire (J3), or changing the setting of DIP switch (SW2-4) on the interface kit (option) PCB if it is connected.
  • Page 12: Economy Operation

    '19 • SCM-SM-281 (8) Economy operation Pressing the HI POWER/ECONOMY button initiate a soft operation with the power suppressed in order to avoid an excessive cooling (a) Pressing the HI/ECO button initiates a soft operation with the power suppressed in order to avoid an excessive cooling or heating. (b) The remote control displays.
  • Page 13: Auto Operation

    Wireless remote   Angle of flap from horizontal control display '19 • SCM-SM-281 Wireless remote COOL, DRY, FAN Approx. 15° Approx. 20° Approx. 25° Approx. 30° Approx. 55° control display HEAT Approx. 30° Approx. 40° Approx. 45° Approx. 50° Approx. 55° Approx.
  • Page 14: Timer Operation

    Cooling AUTO AUTO HIGH POWER AUTO < = < = Room temp. – Setting temp. >5°C Room temp. – Setting temp. 5°C Room temp. – Setting temp. >5°C Room temp. – Setting temp. 5°C < = Cooling Cooling Setting temp. – Room temp. >5°C Setting temp.
  • Page 15: Silent Operation

    '09•SRK-DB-087D '09•SRK-DB-087D '19 • SCM-SM-281 (11) Timer operation (12) Silent operation (a) Comfort start-up (ON timer operation) (11) Timer operation When the silent operation is set, the unit operates by dropping the outdoor fan speed and the compressor speed. The unit starts the operation 5 to 60 minutes earlier so that the room can approach optimum temperature at ON timer. (a) Comfort start-up (ON timer operation) SCM50 SCM60...
  • Page 16: Display Brightness Adjustment

    '19 • SCM-SM-281 (15) Display brightness adjustment This function can be used when it is necessary to adjust the brightness of unit display. Brightness level Timer light Run light 100% 100% Note (1) When the unit displays self diagnosis or service mode, brightness level is always LV2. (16) AUTO OFF operation In order to prevent the air-conditioner from continuing to operate although the person(s) has already left the room, the air-conditioner automatically stops approximalely 1 hour (or 2 hours) after the sensor judges that there is no one in the room.
  • Page 17: Outline Of Automatic Operation

    12-50rps 12-58rps 12-74rps 12-86rps 12-110rps 12-34rps 12-38rps 12-54rps 12-70rps 12-90rps 12-30rps 12-34rps 12-42rps 12-50rps 12-66rps '19 • SCM-SM-281 12-30rps 12-30rps 12-30rps 12-30rps 12-30rps 12-34rps 12-38rps 12-54rps 12-70rps 12-90rps (18) Outline of automatic operation (a) Determination of operation mode (a) Determination of operation mode Operation mode is determined by indoor air temperature and outdoor air temperature as following.
  • Page 18 '09•SRK-DB-087D '09•SRK-DB-087D has elapsed '19 • SCM-SM-281 Current safe (b) Frost prevention control Purpose (b) Frost prevention control Operating conditions Operating conditions (Command speed) (ii) Detail of operation (Command speed) Compressor speed Compressor speed (ii) Detail of anti-frost operation Reduce (ii) Detail of anti-frost operation Indoor heat exchanger Reduce...
  • Page 19: Srk-Zs Series

    '19 • SCM-SM-281 1.1.2 SRK-ZS series (1) Operation control function by wireless remote control Transmission section Operation section ON/OFF (luminous) button Press to start operation, press again to stop. OPERATION MODE select button Each time the button is pressed, the FAN SPEED button mode changes.
  • Page 20: Unit On/Off Button

    '09•SRK-DB-087D '19 • SCM-SM-281 '09•SRK-DB-087D (2) Unit ON/OFF button (2) Unit ON/OFF button wireless wireless (a) Operation (a) Operation (b) Details of operation room (b) Details of operation whether to go into the COOL or HEAT modes. Function Room temperature Fan speed Flap/Louver Timer switch setting Operation mode...
  • Page 21: Selection Of The Annual Cooling Function

    '19 • SCM-SM-281 J1 用 J3 用 (5) Selection of the annual cooling function Jumper wire (J1) Jumper wire (J3) (a) The annual cooling control is valid from factory default setting. It is pos- sible to disable by cutting jumper wire (J3), or changing the setting of DIP switch (SW2-4) on the interface kit (option) PCB if it is connected.
  • Page 22: Economy Operation

    '19 • SCM-SM-281 (8) Economy operation Pressing the HI POWER/ECONOMY button initiate a soft operation with the power suppressed in order to avoid an excessive cooling or heating. The unit operate 1.5℃ higher than the setting temperature during cooling or 2.5℃ lower than that during heating.
  • Page 23: Auto Operation

    control display Left approx. 50° Left approx. 20° Center Right approx. 20° Right approx. 50° Center installation Right end installation Left approx. 50° Left approx. 45° Left approx. 30° Center Right approx. 20° '19 • SCM-SM-281 Left approx. 20° Center Right approx.
  • Page 24: Scm-Sm

    Cooling Heating '19 • SCM-SM-281 Flap Up/down swing Louver Center (Fixed) Cooling Heating Flap Horizontal blowing (Fixed) Slant forwardl blowing (Fixed) Louver Wide (Fixed) room Operation mode Air flow direction contorol < = < = Room temp. – Setting temp. 2°C 2°C <...
  • Page 25: Air Flow Range Setting

    The OFF timer can be set at a specific time (in 10-minute units) within a 24-hour period. (c) OFF timer operation The OFF timer can be set at a specific time (in 10-minute units) within a 24-hour period. (d) Weekly timer operation '19 •...
  • Page 26: Outline Of Dehumidifying (Dry) Operation

    '19 • SCM-SM-281 '09•SRK-DB-087D (16) Outline of dehumidifying (DRY) operation (d) Countermeasure for excessive temperature rise If it feels excessive temperature rise in heating operation, setting temperature can be lower. (a) Purpose of DRY mode The purpose is "Dehumidification", and not to control the humidity to the target condition. Indoor/outdoor unit control the operation condition to reduce the humidity, and also prevent over cooling.
  • Page 27: Protective Control Function

    Compressor overheat protection Purpose: '19 • SCM-SM-281 (ii) Detail of operation (18) Protective control function (Example) Fuzzy Dew prevention control [Cooling] Prevents dewing on the indoor unit. (i) Operating conditions When the following conditions have been satisfied for more than 30 minutes after starting operation Detected value of humidity is 68% or higher.
  • Page 28: Skm-Zsp Series

    '19 • SCM-SM-281 1.1.3 SKM-ZSP series (1) Operation control function by wireless remote control Remote control ◆ Operation section FAN SPEED button OPERATION MODE select button Each time the button is pressed, the fan Each time the button is pressed, the speed changes.
  • Page 29: Unit On/Off Button

    '19 • SCM-SM-281 (2) Unit ON/OFF button When the wireless remote control batteries become weak, or if the wireless remote control is lost or malfunctioning, this button may be used to turn the unit on and off. (a) Operation Push the button once to place the unit in the automatic mode. Push it once more to turn the unit off. (b) Details of operation The unit will go into the automatic mode in which it automatically determines, from room temperature (as detected by sensor), whether to go into the COOL, DRY or Heat modes.
  • Page 30: High Power Operation

    '19 • SCM-SM-281 (5) High power operation Pressing the HI POWER/ECONO button intensifies the operating power and initiates powerful cooling and heating operation for 15 minutes continuously. The wireless remote control displays HIGH POWER mark and the FAN SPEED display disappears. (a) During the HIGH POWER operation, the room temperature is not controlled.
  • Page 31: Timer Operation

    '19 • SCM-SM-281 (b) Swing Flap moves in upward and downward directions continuously. ◆ In HEAT operation ◆ In COOL, DRY, FAN operation Approx. 20° Approx. 35° Approx. 59° Approx. 65° (c) Memory flap When you press the AIR FLOW (UP/DOWN) button once while the flap is operating, it stops swinging at the position. Since this angle is memorized in the microcomputer, the flap will automatically be set at this angle when the next opera- tion is started.
  • Page 32: Outline Of Cooling Operation

    '19 • SCM-SM-281 (ii) Hot keep operation During the heating operation, the indoor fan speed can be controlled based on the temperature of the indoor heat ex- changer (Th2) to prevent blowing of cold air. (10) Outline of cooling operation (a) Operation of major functional components in cooling mode Cooling Thermostat ON...
  • Page 33: Protective Control Function

    '19 • SCM-SM-281 27.5 Cooling 25.5 Dehumidifying Indoor air temperature (˚C) 18.0 Heating Outdoor air temperature (˚C) (b) The unit checks the temperature every hour after the start of operation and, if the result of check is not same as the pre- vious operation mode, changes the operation mode.
  • Page 34: Srr Series

    '19 • SCM-SM-281 1.1.4 SRR series (1) Operation control function by wireless remote control Operation section Transmission section OPERATION MODE select button ON/OFF (luminous) button Each time the button is pressed, the mode changes. Press to start operation, press again to stop.
  • Page 35: Unit On/Off Button

    '19 • SCM-SM-281 (2) Unit ON/OFF button When the wireless remote control batteries become weak, or if the wireless remote control is lost or malfunctioning, this button may be used to turn the unit on and off. Operation Push the button once to place the unit in the automatic mode. Push it once more to turn the unit off. Details of operation The unit will go into the automatic mode in which it automatically determines, from indoor temperature (as detected by sensor), whether to go into COOL, DRY or HEAT modes.
  • Page 36: Installing Two Air-Conditioners In The Same Room

    '19 • SCM-SM-281 (4) Installing two air-conditioners in the same room (4) Installing two air-conditioners in the same room When two air-conditioners are installed in the room, use setting when the two air-conditioners are not operated with one When two air-conditioners are installed in the room, use setting when the two air-conditioners are not operated with one wireless remote control.
  • Page 37: High Power Operation

    '19 • SCM-SM-281 (b) Content of control (i) If the outdoor air temperature sensor (TH2 (Tho-A)) detects below 5°C, the indoor unit speed is switched to 9th step. (It is not possible to change.) (ii) If the outdoor air temperature sensor (TH2 (Tho-A)) detects higher than A°C, the indoor unit speed is changed to the normal control speed.
  • Page 38: Timer Operation

    '19 • SCM-SM-281 (8)   Timer operation Comfortable timer setting (ON timer) If the timer is set at ON when the operation select switch is set at the cooling or heating, or the cooling or heating in auto mode operation is selected, the comfortable timer starts and determines the starting time of next operation based on the initial value of 15 minutes and the relationship between the room temperature at the setting time and the set- ting temperature.
  • Page 39: Scm-Sm

    '19 • SCM-SM-281 (ii) Control B If the float switch detects any anomalous drain condition, the drain pump motor is turned ON for 5 minutes, and at 10 seconds after the drain pump motor OFF it checks the float switch. If it is normal, the unit is stopped under the normal mode or, if there is any anomalous condition, displayed by the flashing of display lights and the drain pump motor is turned ON.
  • Page 40: Operation Permission/Prohibition Control

    (ii) '19 • SCM-SM-281 (iii) Signals of wireless remote control (Display) ±0 –6 –5 –4 –3 –2 –1 Cooling Setting Dehumidifying temperature Heating (e) When the unit is operated automatically with the wired remote control connected, the cooling operation is controlled according to the display temperatures while the setting temperature is compensated by +1°C during dehumidifying or by +2°C during heating.
  • Page 41: Hot Keep Operation

    '19 • SCM-SM-281 (b) Control of input signal Control of input signal (switch input, timer input) connectors (CnT) are provided on the printed circuit board of indoor unit. However, when the operation of air-conditioner is under the “ CENTER ” mode, the wired remote control by CnT is invalid. Level input If the factory settings (Jumper wire J1 EXTERNAL INPUT on the PCB of indoor unit) are set, or “LEVEL IN- PUT”...
  • Page 42: Fdtc, Fdum And Fde Series

    '16 • PAC-T-251 '19 • SCM-SM-281 1.10 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER 1.2 FDTC, FDUM and FDE series 1.2.1 Wired remote control (Option parts) 1.10.1 Remote control Model RC-EX3A Wired remote control Model RC-EX3A ⑤ LCD (with backlight) ③ F2 switch ④...
  • Page 43 '19 • SCM-SM-281 Wired remote control Model RC-E5 Model RC-E5 The figure below shows the remote control with the cover opened. Note that all the items that may be displayed in the liquid crystal display area are shown in the figure for the sake of explanation. Characters displayed with dots in the liquid crystal display area are abbreviated.
  • Page 44: Operation Control Function By The Wired Remote Control

    '16 • PAC-T-251 '19 • SCM-SM-281 1.10.2 Operation control function by the wired remote control 1.2.2 Operation control function by the wired remote control ●Model RC-EX3A (1) Switching sequence of the operation mode switches of remote control (a) Tap the change operation mode button on the TOP screen. (b) When the change operation mode screen is displayed, tap the button of desired mode.
  • Page 45 '19 • SCM-SM-281 ●Content memorized with the power failure compensation are as follows. Note(1) Items (f) and (g) are memorized regardless whether the power failure compensation is effective or not while the setting of silent mode is cancelled regardless whether the power failure compensation is effective or not. At power failure –...
  • Page 46 '19 • SCM-SM-281 ● Model RC-E5 (1) Switching sequence of the operation mode switches of remote control COOL HEAT AUTO (2) CPU reset This functions when “CHECK” and “ESP” buttons on the remote control are pressed simultaneously. Operation is same as that of the power source reset.
  • Page 47: Operation Control Function By The Indoor Control

    '19 • SCM-SM-281 1.2.3 Operation control function by the indoor control (1) Auto operation (a) If “Auto” mode is selected by the remote control, the heating and the cooling are automatically switched according to the difference between outdoor air temperature and setting temperature and the difference between setting temperature and return air temperature.
  • Page 48: Operations Of Functional Items During Cooling/Heating

    '19 • SCM-SM-281 (ii) Regardless of the setting temperature, the cooling or heating operation mode is judged according to the "Judgment based on (ii) Regardless of the setting temperature, the cooling or heating operation mode is judged according to the “Judgment Room temperature/Cooling or Heating and Outdoor temperature/Cooling or Heating".
  • Page 49: Timer Operation

    '19 • SCM-SM-281 (4) Timer operation (a) RC-EX3A (i) Sleep timer Set the time from the start to stop of operation. The time can be selected in the range from 30 to 240 minutes (in the unit of 10-minute). Note (1) Enable the “Sleep timer” setting from the remote control. If the setting is enabled, the timer operates at every time. (ii) Set OFF timer by hour Set the time to stop the unit after operation, in the range from 1 to 12 hours (in the unit of hour).
  • Page 50: Hot Start (Cold Draft Prevention At Heating)

    '19 • SCM-SM-281 (5) Hot start (Cold draft prevention at heating) (a) Operating conditions When either one of following conditions is satisfied, the hot start control is performed. (i) From stop to heating operation (ii) From cooling to heating operation (iii) Form heating thermostat OFF to ON (iv) After completing the defrost operation (only on units with thermostat ON) (b) Contents of operation...
  • Page 51: Auto Swing Control (Fdtc And Fde Only)

    '19 • SCM-SM-281 (7) Auto swing control (FDTC and FDE only) Note Even if [Auto Swing] is selected, the louver position with anti draft function is fixed to position 1. (a) RC-EX3A (i) Louver control 1) To operate the swing louver when the air-conditioner is operating, press the “Direction” button on the TOP screen of remote control.
  • Page 52: Thermostat Operation

    '19 • SCM-SM-281 (8) Thermostat operation (a) Cooling (i) Thermostat is operated with the room temperature control. (ii) Thermostat is turned ON or OFF relative to the set room temperature as shown below. Thermostat ON Temperature drop Thermostat OFF Temperature rise Set room temperature (iii) Thermostat is turned ON when the room temperature is in the range of -1 <...
  • Page 53: Filter Sign

    '19 • SCM-SM-281 (d) Fan control during cooling thermostat OFF (i) Following fan controls during the cooling thermostat OFF can be selected with the indoor function setting of the wired remote control. ① Low fanspeed, ② Set fan speed (Factory default), ③ Intermittence, ④ Fan OFF (ii) When the “Low fan speed”...
  • Page 54: Drain Pump Control

    '19 • SCM-SM-281 (11) Drain pump control (a) This control is operated when the inverter frequency is other than 0 Hz during the cooling operation and automatic cooling and dehumidifying operations. (b) Drain pump ON condition continues for 5 minutes even when it enters the OFF range according to (i) above after turning the drain pump ON, and then stops.
  • Page 55: Cooling, Dehumidifying Frost Protection

    '19 • SCM-SM-281 (c) Operation check mode There is no communication with the outdoor unit but it allows performing operation in respective modes by operating the remote control. (d) Drain pump test run mode As the drain pump test run is established, the drain pump only operates and during the operation protective functions by the microcomputer of indoor unit become ineffective.
  • Page 56: Plural Unit Control - Control Of 16 Units Group By One Remote Control

    '19 • SCM-SM-281 (17) Plural unit control – Control of 16 units group by one remote control (a) Function One remote control can control a group of multiple number of unit (Max. 16 indoor units). “Operation mode” which is set by the remote control can operate or stop all units in the group one after another in the order of unit. No. Thermostat and protective function of each unit function independently.
  • Page 57: Abnormal Temperature Sensor (Return Air/Indoor Heat Exchanger) Broken Wire/Short-Circuit Detection

    '19 • SCM-SM-281 (19) Abnormal temperature sensor (return air/indoor heat exchanger) broken wire/short-circuit detection (a) Broken wire detection When the return air temperature sensor detects -55°C or lower or the heat exchanger temperature sensor detect -55°C or lower for 5 seconds continuously, the compressor stops. After a 3-minute delay, the compressor restarts but, if it is detected again within 60 minutes after the initial detection for 6 minutes continuously, stops again (the return air temperature sensor: E7, the heat exchanger temperature sensor: E6).
  • Page 58 '19 • SCM-SM-281 (b) Input for external control The external input for the indoor unit can be selected from the following input. Input name Content 1 Run/Stop Refer to [(20) (c) Remote operation input] 2 Premission/Prohibition Refer to [(21) Operation permission/prohibition] 3 Cooling/Heating Refer to [(23) Selection of cooling/heating external input function] 4 Emergency stop...
  • Page 59: Operation Permission/Prohibition

    '19 • SCM-SM-281 Individual operation (Factory default) All units operation (Local setting) Only the unit Only the unit All units in one All units in one directly connected CnT-6 or directly connected remote control remote control to the remote CnTA to the remote control system can be system can be...
  • Page 60 '19 • SCM-SM-281 (a) In case of CnT ① Operation stop level > CnTA ③ Operation permission/prohibition level Operation Operation Operation Stop Stop Stop Level input Operation permission Operation permission CnTA Operation prohibition Operation permission/ prohibition setting Operation Operation( ) Operation Stop Stop...
  • Page 61: Temporary Stop Input

    '19 • SCM-SM-281 (22) Temporary stop input In case of temporary stop, operation lamp of remote control lights, but indoor/outdoor unit stop the operation. (a) In case of “level input” setting (Factory default) Input signal to CnT-6 or CnTA is OFF → ON : Temporary stop Input signal to CnT-6 or CnTA is OFF →...
  • Page 62: Scm-Sm

    '19 • SCM-SM-281 (24) Fan control at heating startup (a) Starting conditions At the start of heating operation, if the difference of setting temperature and return air temperature is 5°C or higher after the end of hot start control, this control is performed. (b) Contents of control (i) Sampling is made at each minute and, when the indoor heat exchanger temperature (detected with Thi-R) is 37°C or higher, present number of revolutions of indoor fan speed is increased by 10min...
  • Page 63: Fan Circulator Operation (Rc-Ex3A Only)

    '19 • SCM-SM-281 (32) Fan circulator operation (RC-EX3A only) When the fan is used for circulation, the unit is operated as follows depending on the setting with the remote control. (a) If the invalid is selected with the remote control, the fan is operated continuously during the fan operation. (normal fan mode) (b) If the valid is selected with the remote control, the fan is operated or stopped when on the difference of the remote control temperature sensor and the return air temperature sensor becomes bigger than 3°C.
  • Page 64: Motion Sensor Control (Rc-Ex3A And Rcn-E2 Only)

    '19 • SCM-SM-281 (37) Motion sensor control (RC-EX3A and RCN-E2 only) The sensor determines the presence of people and the amount of activity, and the following controls are done by the motion sensor. Following settings are necessary to activate motion sensor control. (a) Infrared (motion) sensor setting: Installation setting of remote control RC-EX3A The indoor unit which is set to “Enable”...
  • Page 65 '19 • SCM-SM-281 (i) Power saving / comfort control The set temperature is adjusted according to the presence of people and their amount of activity detected by the infrared (motion) sensor. MODE:AUTO/COOL/HEAT mode operation Heat Source & Activity High None Normal When the extent of human 33ºC...
  • Page 66: Outdoor Units

    1.3 Outdoor units 1.3.1 Outline of heating operation (1) Summary (a) Capacity control (i) Indoor unit SRK ** ZSX models only Model SCM50ZS-W SCM60ZS-W Capacity 1.0 7.5 kW 1.0 7.8 kW (ii) Indoor unit except SRK ** ZSX models Model...
  • Page 67: Defrost Operation

    '19 • SCM-SM-281 (3) Defrost operation (a) Starting conditions satisfied (ii) finish (iii) Tho-R1 − or less (iv) The difference between the outdoor air sensor temperature (Tho-A) and outdoor heat exchanger sensor temperature (Tho-R1) is as following. Accumulated compressor operation time Accumulated compressor operation time : After 150 minutes : After 150 minutes...
  • Page 68: Outline Of Cooling Operation

    '19 • SCM-SM-281 1.3.2 Outline of cooling operation (1) Summary (a) Capacity control (i) Indoor unit SRK ** ZSX models only Model SCM50ZS-W SCM60ZS-W Capacity 1.7 7.1 kW 1.7 7.5 kW (ii) Indoor unit except SRK ** ZSX models Model...
  • Page 69: Protective Control Function

    '19 • SCM-SM-281 1.3.3 Protective control function 1.3.3 Protective control function (1) Cooling overload protective control (a) Operating conditions Tho-A 41°C or more (ON1) 47°C or more (ON2) Outdoor air temperature 30 rps 30 rps Lower limit speed Outdoor air temperature ( °...
  • Page 70: Cooling Low Outdoor Temperature Protective Control

    '19 • SCM-SM-281 (3) Cooling low outdoor temperature protective control (a) Operating conditions When the outdoor air temperature (Tho-A) is 22°C or lower continues for 20 seconds while compressor command speed is other than 0 rps. (b) Detail of operation (i) The lower limit of compressor command speed is set to B or D rps and even if the speed becomes lower than B or D rps, the speed is kept to B or D rps.
  • Page 71: Heating Overload Protective Control

    '19 • SCM-SM-281 (5) Heating overload protective control (a) Operating conditions Tho-A (b) Detail of operation A or C B or D (ii) B or D when the thermostat OFF, the speed is (iii) B or D. (c) Reset conditions Tho-A Upper limit C Lower limit D...
  • Page 72: Refrigeration Cycle System Protective Control

    '19 • SCM-SM-281 (7) Refrigeration cycle system protective control (a) Starting condition This control starts when the following conditions are satisfied. (i)   When it has elapsed 30 minutes after the compressor was changed from OFF to ON in the cooling operation mode for more than 5 minutes.
  • Page 73: Compressor Overheat Protection

    '19 • SCM-SM-281 (9) Compressor overheat protection Purpose (b) Detail of operation Tho-D (Example) Fuzzy 3 minutes 3 minutes 3 minutes Discharge pipe temperature (˚C) 105 115 95 105 3 minutes 95 105 3 minutes Cooling Heating Lower limit speed 20 rps 20 rps (ii)
  • Page 74: Current Cut

    '19 • SCM-SM-281 Jumper wire (J1) Jumper wire (J2) (ii) Control value Unit: A Current safe ① Current safe ② Current safe ③ Cooling Heating Cooling Heating Cooling Heating 10.0 12.0 10.0 10.0 (11) Current cut (a) Purpose (b) Detail of operation (12) Outdoor unit failure compressor command (13) Discharge pipe temperature sensor disconnection protection control...
  • Page 75: Scm-Sm

    '19 • SCM-SM-281 (b) Once the unit is stopped by this function, it is not restarted. • Values of A, B Model SCM50ZS-W SCM60ZS-W 20 rps 60 rps Note (1) When the jumper wire (J32) on the outdoor unit sub-PCB is short-circuited (factory default), this control is performed only at initial operation after turning the power source on.
  • Page 76: Outdoor Fan Control At Overload

    Lower Lower Lower limit speed Lower limit speed '19 • SCM-SM-281 Outdoor air temperature > 16˚C Outdoor air temperature > 16˚C Outdoor air temperature < = 16˚C Outdoor air temperature < = 16˚C Tho-R2 Tho-R2 45°C 45°C temperature temperature Tho-R2 Tho-R2 45°C 45°C...
  • Page 77: Limit Of The Number Of Compressor Starts

    '19 • SCM-SM-281 (20) Limit of the number of compressor starts Maximum number of compressor starts is limited to 6 times per hour by cutting jumper wire (JA31) on the outdoor unit sub PCB. JA33 JA34 JA32 JA35 JA31 JA36 Jumper wire JA31...
  • Page 78: Maintenance Data

    '19 • SCM-SM-281 2. MAINTENANCE DATA 2.1 SRK, SKM and SRR series (1) Cautions (1) Cautions (2) Items to check before troubleshooting (2) Items to check before troubleshooting source source (3) Troubleshooting procedure (If the air-conditioner does not run at all) (3) Troubleshooting procedure (If the air-conditioner does not run at all) satisfied satisfied...
  • Page 79: Troubleshooting Procedure (If The Air-Conditioner Runs)

    '19 • SCM-SM-281 (4) Troubleshooting procedure (If the air-conditioner runs) 79−85. 79−85.
  • Page 80: Self-Diagnosis Table

    '19 • SCM-SM-281 (5) Self-diagnosis table Wired Indoor unit display panel remote Description Cause Display (flashing) condition control TIMER of trouble display light light • Broken heat exchanger When a heat exchanger temperature sensor 1 wire disconnection is Heat exchanger 1-time temperature sensor 1 wire, detected while operation is stopped.
  • Page 81: Service Mode (Trouble Mode Access Function)

    '19 • SCM-SM-281 (6) Service mode (Trouble mode access function) (a) Explanation of terms Explanation Term The service mode is the mode where service data are displayed by flashing of the display lights Service mode when the operations in item (b) below are performed with the indoor control. These are the contents of error displays and protective stops which occurred in the past in the air- conditioner system.
  • Page 82 '09•SRK-DB-087D '19 • SCM-SM-281 4-time flash 2-time flash. wireless mode mode Self-diagnosis data data? wireless mode mode Wireless remote control setting Contents of output data Operation mode Fan speed mode wireless Indicates the number of Wireless remote control setting occasions previous to the present Temperature setting the error display data are from.
  • Page 83 '09•SRK-DB-087D '19 • SCM-SM-281 (Example) Wireless remote control setting Operation Displayed data Fan speed Temperature mode mode setting Displays the reason for the stop (error code) the previous time an error was displayed. 21ºC Displays the reason for the stop (error code) 2 times previous when an error was displayed. 22ºC Cooling 23ºC...
  • Page 84 '19 • SCM-SM-281 (c) Error code, stop code table Number of flashes when in service mode Stop coad Error Auto TIMER Error content Cause Occurrence conditions display recovery light light Error coad (10's digit) (1's digit) Normal The wired remote control wire Y is open. The wired remote Error of wired remote control Broken wired remote control wire, 1-time...
  • Page 85 '09•SRK-DB-087D '19 • SCM-SM-281 4-time flash 2-time flash. (d) Operation mode, Fan speed mode information tables (ii) mode mode Display pattern when Display pattern when Fan speed in service mode in service mode Operation mode mode when when there is an there is an RUN light TIMER light...
  • Page 86 '09•SRK-DB-087D '19 • SCM-SM-281 (e) Temperature information Room temperature sensor, indoor heat exchanger temperature sensor, outdoor air temperature sensor, outdoor heat exchanger temperature sensor temperature Unit: °C TIMER light (1’s digit) RUN light (10’s digit) Buzzer sound (sounds for 0.1 second) (does not sound) temperature information Sensor value displayed when the error code is normal...
  • Page 87 '09•SRK-DB-087D '19 • SCM-SM-281 (ii) Discharge pipe temperature sensor temperature Unit: °C TIMER light (1’s digit) RUN light (10’s digit) Buzzer sound (sounds for 0.1 second) (does not sound) temperature information Sensor value displayed when the error code is normal -64ºC temperature data...
  • Page 88 '09•SRK-DB-087D '19 • SCM-SM-281 Service data record form Wireless r Operation mode Fan speed mode temperature Wireless r temperature temperature temperature temperature Wireless r temperature temperature temperature temperature Wireless r temperature temperature temperature temperature Wireless r temperature temperature temperature temperature Wireless r temperature temperature...
  • Page 89: Inspection Procedures Corresponding To Detail Of Trouble

    '19 • SCM-SM-281 (7) Inspection procedures corresponding to detail of trouble Sensor error Broken sensor wire, connector poor connection Discharge pipe and power transistor sensor Sensor temperature characteristics Room temperature, indoor heat exchanger tempe- temperature characteristics rature, outdoor heat exchanger temperature, outdoor air temperature outdoor suction pipe temperature - 10...
  • Page 90 '19 • SCM-SM-281 Limit switch anomaly (SRK20, 25, 35, 50, 60ZSX-W only) Defective limit switch, defective indoor unit control PCB, Defective air inlet panel set Is the air inlet panel set correctly? Correction, re-set Are limit switch OK ? Defective limit switch Note(1) Check if the limit switch functions properly or not by seeing whether the lamp continues to blink or can be reset by pressing the limit swit- ch by hand while the air inlet panel is removed.
  • Page 91 '19 • SCM-SM-281 Over heat of compressor Gas shortage, defective discharge pipe temperature sensor temperature temperature unit main Error of signal transmission Wiring error including power cable, defective indoor/ outdoor unit PCB ② ③ indoor unit ② ③ indoor unit ①...
  • Page 92 '19 • SCM-SM-281 Trouble of outdoor unit Insufficient refregerant amount, Faulty power transistor, Broken compressor wire Service valve close, Defective EEV, Defective outdoor unit PCB source source source source − − − unit sub ◆  unit (1)  main     operation  ...
  • Page 93 '19 • SCM-SM-281 Rotor lock Defective compressor, defective outdoor unit PCB unit main See page 88. Drain abnormality (SRR only) [Drain piping defective,pump defect, float switch, indoor unit PCB] Indoor unit PCB Has an overflow developed? Is the float switch operating? is defective.
  • Page 94: Phenomenon Observed After Short-Circuit, Wire Breakage On Sensor

    '19 • SCM-SM-281 (8) Phenomenon observed after short-circuit, wire breakage on sensor (a) Indoor unit Phenomenon Operation Sensor mode Short-circuit Disconnected wire Cooling Room temperature sensor Heating Freezing cycle system protection trips and stops the compressor. Cooling Heat exchanger temperature sensor Heating Cooling Humidity sensor...
  • Page 95: Checking The Indoor Electrical Equipment

    Cooling Heat exchanger sensor Heating Defrosting is performed for 10 minutes at approx. 40 minutes. Cooling Ourdoor air '19 • SCM-SM-281 temperature sensor Defrosting is performed for 10 minutes at approx. 40 minutes. Heating Discharge pipe All modes sensor (9) Checking the indoor electrical equipment (a) Indoor unit PCB check procedure Is there voltage between terminal Inspect power source...
  • Page 96: How To Make Sure Of Wireless Remote Control

    Operation SW ON Measure in this section '19 • SCM-SM-281 (10) How to make sure of wireless remote control wireless wireless wireless wireless wireless wireless   Simplified check method of wireless remote control It is normal if the signal transmission section of the wireless remote control emits a whitish light at each transmission on the monitor of digital camera.
  • Page 97: Outdoor Unit Inspection Points

    '19 • SCM-SM-281 (12) Outdoor unit inspection points Models SCM50ZS-W,60ZS-W Color marks Mark Color Black CAUTION- HIGH VOLTAGE ◆Power source and serial signal inspection Blue ① to ②: AC 220/230/240V Brown High voltage is produced in the control box. Don't touch ②...
  • Page 98 '19 • SCM-SM-281 (a) Inspection of electronic expansion valve   (ii) (iii) unit sub (iv) • Inspection of electronic expansion valve as a separate unit Measuring point Resistance when normal (b) Outdoor fan motor check procedure main (i) Outdoor unit main PCB output check   ...
  • Page 99: Fdtc, Fdum And Fde Series

    '19 • SCM-SM-281 2.2 FDTC, FDUM and FDE series 2.2.1 Diagnosing of microcomputer circuit Selfdiagnosis function (a) Check indicator table Whether a failure exists or not on the indoor unit and outdoor unit can be know by the contents of remote control error code, indoor/outdoor unit green LED (power pilot lamp and microcomputer normality pilot lamp) or red LED (check pilot lamp).
  • Page 100 '19 • SCM-SM-281 (ii) Outdoor unit Remote control Indoor control PCB Reference Location of trouble Description of trouble Repair method page Error code Red LED Red LED Green LED Installation, operation status • Higher outdoor heat exchanger temperature Repair Replacement, repair Outdoor heat exchanger Keeps •...
  • Page 101 '19 • SCM-SM-281 (iii) Display sequence of error codes or inspection indicator lamps ■ Occurrence of one kind of error Displays are shown respectively according to errors. ■ Occurrence of plural kinds of error Section Category of display Error code on remote control •...
  • Page 102: Troubleshooting Procedure

    '19 • SCM-SM-281 ■ Error log and reset Error indicator Memorized error log Reset Remote control display • Higher priority error is memorized. • Stop the unit by pressing the ON/OFF switch of remote control. Red LED on indoor unit control PCB •...
  • Page 103 '19 • SCM-SM-281 FDTC series PSC012D050 Replace and set up the PCB according to this instruction. 1) Set to an appropriate address and function using switch on PCB. Select the same setting with the removed PCB. Item Switch Content of control Address Plural indoor units control by 1 remote control Normal...
  • Page 104 '19 • SCM-SM-281 (ii) Models FDUM, FDE series 1) Control PCB PSB012D990B Replace and set up the PCB according to this instruction. a) Set to an appropriate address and function using switch on PCB. Select the same setting with the removed PCB. item switch Content of control...
  • Page 105 '19 • SCM-SM-281 2) Power PCB This PCB is a general PCB. Replace the PCB according to this instruction. a) Replace the PCB ① Unscrew terminal of the wiring(yellow/green) connected to terminal block (CNWO) from the box. ② Replace the PCB only after all the wirings connected to the connector are removed. ③...
  • Page 106: Troubleshooting At The Outdoor Unit

    '19 • SCM-SM-281 Troubleshooting at the outdoor unit When troubleshooting the outdoor unit, firstly assess the overview of malfunction and try to presume the cause and the faulty part by checking the error code dispalyed on the remote control and then proceed further inspection and remedy Self-diagnosis system by microcomputer on indoor unit PCB can assist to find the cause of malfunction smoothly by making a diagnosis of not only the anomaly of microcomputer, but also the anomaly in power source system, installation space, overload resulting from improper charging amount of refrigerant and etc.
  • Page 107: Check Of Anomalous Operation Data With The Remote Control

    '19 • SCM-SM-281 (5) Check of anomalous operation data with the remote control (a) In case of RC-EX3A remote control [Operating procedure] ➀ On the TOP screen, touch the buttons in the order of “Menu” ➝ “Service setting” ➝ “Service & Maintenance” ➝ “Service password”...
  • Page 108 '19 • SCM-SM-281 (b) In case of RC-E5 remote control Data Item Number Operation data can be checked with remote control unit operation. (Operation Mode) (Set Temperature) ➀ Press the button. (Return Air Temperature) The display change “ ” (Remote Control Temperature) ➁...
  • Page 109: Inverter Checker For Diagnosis Of Inverter Output

    '19 • SCM-SM-281 Inverter checker for diagnosis of inverter output   ●Checking method (a) Setup procedure of checker. Power OFF (Turn off the breaker). (ii) Remove the terminal cover of compressor and disconnect the wires (U, V, W) from compressor. (iii) Connect the wires U (Red) , V (White) and W (Black) of the checker to the terminal of disconnected wires (U, V, W) from compressor respectively.
  • Page 110: Troubleshooting Flow

    '19 • SCM-SM-281 2.2.2 Troubleshooting flow (1) List of troubles Remote control display Description of trouble Reference page None Operates but does not cool None Operates but does not heat None Earth leakage breaker activated None Excessive noise/vibration 112−114 None Louver motor failure (FDTC and FDE only) None Power source system error (Power source to indoor unit control PCB) None...
  • Page 111: Applicable Model

    '19 • SCM-SM-281 (2) Troubleshooting Green Error code Content Remote control: None Operates but does not cool Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Check the indoor fan operation. Check the temperature differnce between return and supply air.
  • Page 112 '19 • SCM-SM-281 Green Error code Content Remote control: None Operates but does not heat Indoor Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Check the indoor fan operation. Check the temperature differnce between return and supply air. It is normal.
  • Page 113 '19 • SCM-SM-281 Green Error code Content Remote control: None Earth leakage breaker activated Indoor Stays OFF Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Are OK the insulation resistance and Replace compressor. resistance between terminals(1) of compressor? (1)See page142.
  • Page 114 '19 • SCM-SM-281 Green Error code Content Remote control: None Excessive noise/vibration (1/3) – – Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure If excessive noise/vibration persists when sufficient Does time has elapsed after noise/vibration stopping the unit, it is occur during or soon after stopping operation considered that the air-...
  • Page 115 '19 • SCM-SM-281 Green Error code Content Remote control: None Excessive noise/vibration (2/3) – – Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure From previous page Rearrange the piping to Are the pipes avoid contact with the contacting the casing.
  • Page 116 '19 • SCM-SM-281 Green Error code Content Remote control: None Excessive noise/vibration (3/3) – – Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure From previous page If insufficient cooling/ Adjustment heating problem happens during commissioning due to anomalous operating Does noise/vibration occur when the conditions at cooling/ cooling/heating operation is in...
  • Page 117 '19 • SCM-SM-281 Green Louver motor failure Error code Content Remote control: None (FDTC and FDE only) Indoor Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model FDTC and FDE series only Diagnosis Countermeasure ▲ Check at the indoor unit side. Operate after waiting for more than 1 minute.
  • Page 118 '19 • SCM-SM-281 Green Error code Content Power source system error Remote control: None (Power source to indoor unit control PCB) Indoor Stays OFF Stays OFF 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure AC220/240V detected between on the terminal block of indoor unit? AC220/240V...
  • Page 119 '19 • SCM-SM-281 Green Error code Content Power source system error Remote control: None (Power source to remote control) Indoor Keeps flashing 3-time flash Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Is the connection of the Correct. ➞ Insert connector remote control's wiring OK? securely.
  • Page 120 '19 • SCM-SM-281 Green Error code Content INSPECT I/U Remote control: INSPECT I/U Indoor Keeps flashing Stays OFF Indoor (When 1 or 2 remote controls are connected) 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Are 2 units of remote control connected? ⑴,...
  • Page 121 '19 • SCM-SM-281 Green Error code Content INSPECT I/U Remote control: INSPECT I/U Indoor Keeps flashing Stays OFF Indoor (Connection of 3 units or more remote controls) 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Are more than Reduce to 2 units or less. 3 units of remote control connected? Does remote...
  • Page 122 '19 • SCM-SM-281 Green Error code Content Communication error at Remote control: WAIT initial operation (1/3) Indoor Keeps flashing Stays OFF 5. Troubleshooting 1. Applicable model All Models Diagnosis Countermeasure When the remote control LCD displays “ ” 2 WAIT minutes after the power on.
  • Page 123 '19 • SCM-SM-281 Green Error code Content Communication error at Remote control: WAIT initial operation (2/3) Indoor Keeps flashing Stays OFF 5. Troubleshooting 1. Applicable model All Models Diagnosis Countermeasure When the fuse is blown, the method to inspect outdoor sub PCB before replacing the power Is there source fuse...
  • Page 124 '19 • SCM-SM-281 Green Error code Content Communication error at Remote control: WAIT initial operation (3/3) Indoor Keeps flashing Stays OFF 5. Troubleshooting 1. Applicable model All Models Diagnosis Countermeasure When the remote control display is extinguished after the power on. Remote control display is extinguished after the power on.
  • Page 125 '19 • SCM-SM-281 Green Error code Content No display Remote control: None Indoor Stays OFF Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Remote control does not display anything after the power on. Is DC10V or Defective remote control.
  • Page 126 '19 • SCM-SM-281 Green Error code Content Remote control Remote control: Indoor Keeps flashing Stays OFF Indoor communication circuit error 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Is it possible to Malfunction by noise reset normally by the power reset? Check peripheral environment.
  • Page 127 '19 • SCM-SM-281 Green Error code Content Remote control: Communication error during operation Indoor Keeps flashing 2-time flash Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Note (1) Inspect faulty connections (disconnection, looseness) on the outdoor unit terminal block. Is the connection of signal Repair signal wires.
  • Page 128: When The Temperature Sensor Detects -50°C Or Lower For 5 Seconds Continuously

    '19 • SCM-SM-281 Green Error code Content Indoor heat exchanger Remote control: temperature sensor anomaly Indoor Keeps flashing 1-time flash Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Is the connection of indoor heat Correct. ➞ Insert connector exchanger temperature sensor securely.
  • Page 129 '19 • SCM-SM-281 Green Error code Content Return air temperature Remote control: sensor anomaly Indoor Keeps flashing 1-time flash Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Is the connection of return Correct. ➞ Connect air temperature sensor connector.
  • Page 130 '19 • SCM-SM-281 Green Error code Content Remote control: Heating overload operation Indoor Keeps flashing 1-time flash Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Is the air filter clogged? Wash. 2. Error detection method Is the indoor heat exchanger Defective indoor heat temperature sensor exchanger temperature...
  • Page 131 '19 • SCM-SM-281 Green Error code Content Drain trouble Remote control: Indoor Keeps flashing 1-time flash (FDTC and FDUM only) Indoor 5. Troubleshooting 1. Applicable model FDTC and FDUM series only Diagnosis Countermeasure Check the error data in the remote control. Is there any overflow? Is DC12V at CNI connector.
  • Page 132 '19 • SCM-SM-281 Excessive number of connected Green Error code Content indoor units (more than 17 units) Remote control: Indoor Keeps flashing Stays OFF Indoor by controlling with one remote control 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Aren't more than 17 Defective remote control indoor units connected to one...
  • Page 133 '19 • SCM-SM-281 Green Error code Content Address setting error of Remote control: indoor units Indoor Keeps flashing Keeps flashing Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure E11 occurs Is “Master IU address set” function of remote 2.
  • Page 134 '19 • SCM-SM-281 Green Error code Content Indoor fan motor anomaly Remote control: Indoor Keeps flashing 1-time flash Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Does any foreign material Remove foreign material. intervene in rotational area of fan propeller? Does the fan 2.
  • Page 135 '19 • SCM-SM-281 Green Error code Content Indoor unit operation check, Remote control: drain pump moter check setting error Indoor Keeps flashing 1-time flash Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure E19 occurs when the power ON Is SW7-1 Defective indoor unit on the indoor unit control...
  • Page 136 '19 • SCM-SM-281 Green Error code Content Indoor fan motor rotation Remote control: speed anomaly Indoor Keeps flashing 1-time flash 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Does any foreign material Remove foreign material. intervene in rotational area of fan propeller? Does the fan 2.
  • Page 137: Temperature (°C)

    '19 • SCM-SM-281 Green Error code Content Remote control Remote control: temperature sensor anomaly Indoor Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Is the remote Correct. control temperature sensor connected properly? 2. Error detection method Are the characteristics of Is the remote...
  • Page 138: Remote Control

    '19 • SCM-SM-281 Green Green Error code Error code Content Content Cooling high pressure operation Remote control: Remote control: Keeps flashing Stays OFF Indoor Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure * For the characteristics of outdoor heat exchanger temperature Are normal sensor, refer to E37.
  • Page 139 '19 • SCM-SM-281 Green Error code Content Discharge pipe temperature error Remote control: Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure * For the characteristics of discharge Are the pipe temperature, refer to E39. characteristics of Replace discharge pipe discharge pipe temperature...
  • Page 140: Temperature Sensor Anomaly

    '19 • SCM-SM-281 Green Error code Content Outdoor heat exchanger Remote control: temperature sensor anomaly Indoor Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Is the outdoor heat exchanger temperature Correct connector. sensor connector connected properly? 2.
  • Page 141 '19 • SCM-SM-281 Green Error code Content Outdoor air temperature Remote control: sensor anomaly Indoor Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure the outdoor air Correct connector. temperature sensor connector connected properly? For the characteristics of outdoor air temperature sensor, see the following graph.
  • Page 142 '19 • SCM-SM-281 Green Error code Content Discharge pipe Remote control: temperature sensor anomaly Indoor Keeps flashing Stays OFF 5. Troubleshooting 1. Applicable model Diagnosis Countermeasure All models Is the discharge pipe temperature sensor Correct connector. connector connected properly? 2. Error detection method For the characteristics of discharge pipe Are the temperature sensor, see the following graph.
  • Page 143 '19 • SCM-SM-281 Green Error code Content Service valve (gas side) closing operation Remote control: Indoor Keeps flashing Stays OFF 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Are the Open the service valve. service valve (gas side) opened? 2.
  • Page 144 '19 • SCM-SM-281 Green Error code Content Current cut (1/2) Remote control: Indoor Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Is the Power source Check power source. voltage OK? 2. Error detection method Are the Open the valves.
  • Page 145: Applicable Model

    inverter PCB 1-time flash '19 • SCM-SM-281 Green Error code Content Current cut (2/2) Remote control: Indoor Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure From previous page Is the checked result of power Defective outdoor unit transistor module main PCB ➞...
  • Page 146 '19 • SCM-SM-281 Green Error code Content Outdoor unit sub PCB Remote control: communication error Indoor Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Is the connector connection between the outdoor unit Correct connector. main PCB and the outdoor sub PCB OK? 2.
  • Page 147 '19 • SCM-SM-281 Green Error code Content Remote control: Active filter voltage error Indoor Keeps flashing Stays OFF 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Restore normal condition. Is the power source normal? 2. Error detection method Is voltage Restore normal condition.
  • Page 148 '19 • SCM-SM-281 Green Error code Content Outdoor fan motor anomaly Remote control: Indoor Keeps flashing Stays OFF 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Does any foreign material intervene Remove foreign matter. in rotational area of fan propeller? Does the 2.
  • Page 149 '19 • SCM-SM-281 Green Green Error code Error code Content Content Power transistor error Power transistor anomaly Remote controller: E51 Remote control: Indoor Keeps flashing Stays OFF Keeps flashing Stays Off Indoor (Models SRC50, 60) 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure...
  • Page 150 '19 • SCM-SM-281 Green Error code Content Suction pipe temperature Remote control: sensor anomaly Indoor Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure the suction pipe Correct connector. temperature sensor connector connected properly? For the characteristics of suction pipe temperature sensor, see the following graph.
  • Page 151 '19 • SCM-SM-281 Green Error code Content Insufficient refrigerant amount Remote control: or detection of service valve closure Indoor Keeps flashing Stays OFF 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Is the Open fully. service valve fully opened? Are the connections of indoor heat exchanger and/or return air...
  • Page 152: Replace Compressor

    '19 • SCM-SM-281 Green Error code Green Content Error code Content Current safe stop Current safe stop Keeps flashing Stays Off Indoor Remote controller: E58 Remote control: Indoor Keeps flashing Stays OFF (Model SRC50, 60) 3 time flash Outdoor ― 5.
  • Page 153 '19 • SCM-SM-281 Green Error code Content Compressor startup failure Remote control: Indoor Keeps flashing Stays OFF 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Disconnect the outdoor fan motor Compressor does not start at all. connector and try to startup Neither noise nor vibration cannot be heard Does Replace outdoor fan motor.
  • Page 154 '19 • SCM-SM-281 Green Error code Content Compressor rotor lock error Remote control: Indoor Keeps flashing Stays OFF 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Is the Check and correct the power source voltage power source voltage. Reset the power source and restart operation. 2.
  • Page 155: Electrical Wiring

    '19 • SCM-SM-281 3. ELECTRICAL WIRING (1) Outdoor units Models SCM50ZS-W, 60ZS-W RWC000Z333...
  • Page 156 '19 • SCM-SM-281 (2) Indoor units (a)   Wall mounted type (SRK, SKM) (i) Models SRK20ZSX-W, 25ZSX-W, 35ZSX-W, 50ZSX-W, 60ZSX-W SRK20ZSX-WB, 25ZSX-WB, 35ZSX-WB, 50ZSX-WB, 60ZSX-WB SRK20ZSX-WT, 25ZSX-WT, 35ZSX-WT, 50ZSX-WT, 60ZSX-WT RWA000Z413...
  • Page 157 '19 • SCM-SM-281 (ii) Models SRK20ZS-W, 25ZS-W, 35ZS-W, 50ZS-W SRK20ZS-WB, 25ZS-WB, 35ZS-WB, 50ZS-WB SRK20ZS-WT, 25ZS-WT, 35ZS-WT, 50ZS-WT RWA000Z416...
  • Page 158 '19 • SCM-SM-281 (iIi) Models SKM20ZSP-W, 25ZSP-W, 35ZSP-W RLC000Z110...
  • Page 159 '19 • SCM-SM-281 (b) Ceiling concealed type (SRR)   Models SRR25ZM-W, 35ZM-W, 50ZS-W, 60ZS-W RJJ000Z003...
  • Page 160 '19 • SCM-SM-281 (c) 4-way ceiling cassette type (FDTC)   Models FDTC25VH, 35VH, 50VH, 60VH PJF000Z516...
  • Page 161 '19 • SCM-SM-281 (d) Duct connected-Low / Middle static pressure type (FDUM)   Model FDUM50VH PJG000Z488...
  • Page 162 '19 • SCM-SM-281 (e) Ceiling suspended type (FDE)   Model FDE50VH PFA004Z087...
  • Page 163: Piping System

    '19 • SCM-SM-281 4. PIPING SYSTEM Models SCM50ZS-W, 60ZS-W...
  • Page 164 Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice. Copyright MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice.

Table of Contents