Error code
Remote controller:
WAIT
1. Applicable model
Model SRC40 – 60
When the fuse is blown, the
method to inspect inverter
before replacing the power
supply fuse
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Blown fuse
• Faulty noise filter
• Connection between PCB's
• Blown fuse on single phase
model
• Faulty indoor control PCB
• Defective remote controller
• Breakage of remote controller
wire
• Faulty outdoor control PCB
Note:
LED
Green
Red
Keeps flashing Stays Off
Indoor
Keeps flashing 2 times flash
Outdoor
5. Troubleshooting
Isn't there
a short-circuit between phases of
noise filter?
YES
Aren't there
cracks or burning on the power
ransistor module or diode
stack?
YES
Isn't reactor the anomalous?
YES
279
Content
WAIT
(Model SRC40 - 60)
Diagnosis
NO
Replace the noise
filter.
NO
Replace the
control PCB.
NO
Replace the
reactor.
(2/3)
Countermeasure
Replace fuse.