Mitsubishi Heavy Industries FDTC50ZHXV Technical Manual page 322

Hide thumbs Also See for FDTC50ZHXV:
Table of Contents

Advertisement

Error code
Remote controller:
E48
1. Applicable model
Model FDC 71 – 250
2. Error detection method
Detected by rotation speed of
outdoor fan motor
3. Condition of Error displayed
When actual rotation speed of
outdoor fan motor (FMo1, 2)
drops to 100min
or lower
-1
for 30 minutes continuously,
the compressor and the
outdoor fan motor stop. After
3-minutes delay, it starts
again automatically, but if this
anomaly occurs 5 times within
60 minutes after the initial
detection.
4. Presumable cause
• Defective outdoor control
PCB
• Foreign material at rotational
area of fan propeller
• Defective fan motor
• Dust on control PCB
• Blow fuse
• External noise, surge
Note: When E48 error occurs, in almost cases F2 fuse (4A) on the outdoor control PCB [Model 71: F3 fuse (2A)] is blown. There are a lot of cases
that fuse is blown and E48 occurs due to defective fan motor. And even though only the outdoor control PCB ( or fuse) is replaced,, another
trouble (*1) could occur. Therefore when fuse is blown, check whether the fan motor is OK or not.
After confirming the fan motor normal, check by power ON. (Don't power ON without confirming the fan motor normal.)
*1 The error which does not seem to relate E48 may occur like as "
communication error (E45) and etc.
LED
Green
Red
Keeps flashing Stays Off
Indoor
Keeps flashing 1 time flash
Outdoor
5. Troubleshooting
Diagnosis
Does any foreign
material intervene in rotational area
of fan propeller?
NO
Does the
fan rotate smoothly when turned
by hand?
YES
Is DC280V
detected between (CNFAN �
(red)-� (blue)) of fan motor
connector?
YES
Power supply reset
Is normal state restored?
312
Content
Outdoor DC fan motor error
(Model FDC71 - 250)
YES
NO
NO
(1)
Is F2 fuse blown?
YES
Note (1) Fuse of Model 71 is F3.
NO
YES
", Stay OFF of LED on outdoor control PCB, inverter
WAIT
Countermeasure
Remove foreign material.
Replace fan motor.
If resistance between ➀
(Vm):red - ➃ (GND):blue is
detected 1kΩ or lower, it is
faulty.
Check power supply
NO
voltage.
Replace faulty fan motor
and control PCB.
Replace fan motor (If
anomaly persists after
replacing fan motor,
replace control PCB.)
Malfunction by temporary
noise