Mitsubishi Heavy Industries FDTC50ZHXV Technical Manual page 107

Hide thumbs Also See for FDTC50ZHXV:
Table of Contents

Advertisement

Models FDC100VN, 125VN, 140VN
100VS, 125VS, 140VS
Holes for anchor bolt
(M10×3 pcs.)
60
Opening for
electric wiring
40
Opening for piping
15
50
and electric wiring
VIEW A
Liquid piping
Terminal block
Opening for piping
and electric wiring
970
190
580
60
262
388
Minimum installation space
L2
Air
inlet
Service
space
Notes
(1) It must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts. An anchor bolt must not protrude
(3) Where the unit is subject to strong winds, lay it in sucha direction that
(4) Leave 1m or more space above the unit.
(5) A wall in front of the blower outlet must not exceed the units height.
(6) The model name label is attached on the lower right corner of the front.
-
Gas piping
40
100
Gas piping :ø15.88(5/8")
(Flare connecting)
Liquid piping :ø9.52(3/8")
(Flare connecting)
Opening for
electric wiring
55
50
15
200
60
15
Opening for piping
and electric wiring
Holes for drain
(ø20 × 3 pcs.)
L3
Air inlet
L4
L1
Air outlet
more the 15mm.
the blower outlet faces perpendicularly to the dominant wind direction.
106
-
Opening for piping
and electric wiring
52
27
50
Insallation
type
I
II
III
Mark
L1
Open
Open
500
L2
300
5
Open
L3
150
300
150
L4
5
5
Unit: mm
A
5