Model FDT125V
Item
Nominal cooling capacity
( 1)
( 1)
Nominal heating capacity
Power source
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
Refrigerant equipment
Heat exchanger
Refrigerant control
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air flow(Standard)
Outside air intake
Air filter, Q'ty
Shock & vibration absorber
Operation control
Operation switch
Room temperature control
Safety equipment
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
Notes
(1) The data are measured at the following conditions.
Item
Operation
Cooling
Heating
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 "UNITARY AIR-CONDITIONERS"
Decorative Panel model or Wireless kit (Optional)
Model
FDT125V
Model
kW
kW
dB(A)
mm
kg
W
CMM
mm(in)
Indoor air temperature
DB
WB
27
19
20
Item
Panel Part No.
T-PSA-36W-E
-
FDT125V
12.5
14.0
1 Phase, 220-240V 50Hz / 220V 60Hz
Hi: 42 Me: 40 Lo: 37
Unit:298
840
Panel:35
950
32.5 (Unit:27 Panel:5.5)
Louver fin & inner grooved tubing
Turbo fan 1
140 1
Direct line start
Hi: 30 Me: 27 Lo: 23
Possible
Pocket plastic net
Rubber sleeve (for fan motor)
Wired remote control switch (Optional: RC-E3)
Wireless kit (Optional )
Thermostat by electronics
Overload protection for fan motor.
Frost protection thermostat.
Liquid line: 9.52 (3/8")
Gas line: 15.88 (5/8")
Flare piping
Connectable with VP20 (I.D.20 mm, O.D.26 mm)
Necessary (both Liquid & Gas line)
Mounting kit. Drain hose
Decorative Panel
Outdoor air temperature
DB
35
7
329
-
840
950
1 (Washable)
Standards
WB
24
ISO-T1
6
Wireless kit
RCN-T-36W-E