Mitsubishi Heavy Industries FDTC50ZHXV Technical Manual page 350

Hide thumbs Also See for FDTC50ZHXV:
Table of Contents

Advertisement

Models FDC200VS, 250VS
Item
Power source
Nominal cooling capacity
( 1)
Nominal heating capacity
( 1)
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
Refrigerant equipment
compressor type & Q' ty
Starting method
Crankcase heater
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
Defrost control
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air flow(Standard)
Shock & vibration absorber
Safety equipment
Installation data
Refrigerant piping size
Connecting method
Drain
Insulation for piping
Accessories
Notes
(1) The cooling and heating capabilities imply the values when the indoor unit of rated capacity is connected under the condition specified in ISO-T1.
(2) The refrigerant quantity in the connecting pipe is not included. Charge it additionally at the site.
(3) Values in [
~
] show the minimum and maximum capacities.
Model
kW
20.0 [7.0~22.4]
kW
22.4 [7.6~25.0]
dB(A)
mm
1300
kg
W
kg
(Pre-charged up to the piping length of 30m)
W
CMM
Liquid line: 9.52 (3/8")
mm(in)
Gas line: 22.22 (7/8")
-
FDC200VS
3 Phase, 380-415V 50Hz/380V 60Hz
57
970
370
122
GTC5150ND70K 1
Direct line start
33
Straight fin & inner grooved tubing
Electronic expansion valve
R410A
5.4
1.45 (M-MA32R)
Microcomputer controlled de-icer
Propeller fan 2
86
Direct line start
Cooling: 150, Heating: 145
Rubber sleeve (for compressor)
Internal thermostat for fan motor.
Anomalous discharge temperature protection.
Liquid line: Flare piping, Gas line: Brazing
Hole size 20 3pcs.
Necessary (both Liquid & Gas lines)
Reducer kit (Please see 1.5.3), Accessory pipe (Please see 1.5.3)
340
-
FDC250VS
25.0 [10.6~28.0]
28.0 [9.5~31.5]
Cooling: 57, Heating: 58
1505
970
370
140
7.2
(Pre-charged up to the piping length of 30m)
2
Liquid line: 12.7 (1/2")
Gas line: 22.22 (7/8")

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents