Mitsubishi Heavy Industries FDC112KXEN6 Technical Manual page 331

Table of Contents

Advertisement

Error code
Remote controller:
WAIT
7-segment display:
1. Applicable model
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Faulty setting of remotr
controller
• Mistake in auto address
setting procedure
• Faulty wiring
• Faulty indoor PCB
• Faulty remote controller
Note:
LED
Green
Red
Keeps flashing Stays Off
Indoor
Keeps flashing Stays Off
Outdoor
5. Troubleshooting
Diagnosis
Is the
voltage>15V
between X-Y terminals of
remote
controller?
Remove the wires of
remote controller
1
Is the Votage>15?
YES
Is the number
of remote controllers
≤2?
YES
Is any wrong
connection of superlink
signal wires?
YES
Is any
poor connection of remote
controller?
327
Content
WAIT
NO
AC Transformer
FDT
Is the
voltage between
�-� CNW2
DC18V?
Is the
voltage>AC20V
between brown-brown
terminals of
NO
transformer?
Is supply power
voltage OK ?
YES
NO
NO
YES
NO
(1)
Countermeasure
NO
Replace power PCB
YES
Replace contol PCB
NO
Check the power supply
YES
Replace AC transformer
Replace indoor PCB
Correct wiring
Correct wiring
Correct wiring
Replace remote controller