Models FDUM36KXE6, 45KXE6, 56KXE6
Item
1
Nominal cooling capacity*
2
Nominal heating capacity*
Power source
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
Refrigerant equipment
Heat exchanger
Refrigerant control
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air flow(Standard)
Available static pressure
( at Hi)
Outside air intake
Air filter, Q'ty
Shock & vibration absorber
Insulation (noise & heat)
Operation control
Operation switch
Room temperature control
Safety equipment
Installation data
Refrigerant piping size
Connecting method
Drain pump
Drain hose
Insulation for piping
Accessories
Notes
(1) The data are measured at the following conditions.
Item
Operation
1
Cooling*
2
Heating*
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 "UNITARY AIR-CONDITIONERS"
Models
FDUM36KXE6
kW
3.6
kW
4.0
dB(A)
Hi: 34 Me: 31 Lo: 28
mm
kg
W
CMM
Hi: 12 Me: 11 Lo: 10
Pa
mm(in)
Indoor air temperature
DB
WB
27
19
20
-
FDUM45KXE6
4.5
5.0
1 Phase 220-240V 50Hz/220V 60Hz
299
750
34
Louver fin & inner grooved tubing
Electronic expansion valve
Centrifugal fan 2
60 1
Direct line start
Standard:50/40, Hi speed:85/90
Possible
Installed on side
Rubber sleeve(for fan motor)
Polyurethane foam
Wired remote control switch (Optional:RC-E3)
Wireless kit (Optional:RCN-KIT3-E)
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Liquid line: 6.35(1/4"),Gas line: 12.7(1/2")
Flare piping
Built-in Drain pump
Connectable with VP20(I.D.20mm, O.D.26mm )
Necessary (both Liquid & Gas lines)
Drain hose
Outdoor air temperature
DB
35
7
25
-
FDUM56KXE6
5.6
6.3
Hi: 35 Me: 32 Lo: 29
635
Hi: 14 Me: 12 Lo: 11
Standards
WB
24
ISO-T1
6