4) Wiring route.
a) Wire from the wiring hole through the rear side of the control box to the terminal block.
b) Any suplus wires should be tied up with a cable tie.
(l)
Floor standing (without casing) hidden type (FDFU)
Model: All models
(i)
Selection of installation hidden location
1) A place where good air circulation and delivery can be obtained.
● Cold air throw
Models
Air throw
[Conditions]
(1) Fan speed: Hi
(2) Location: Free space without obstacles
(3) Distance of reach indicates the horizontal distance after the wind touched down the floor.
(4) Air velocity at the throw: 0.5 (m/sec.)
2) Where there is no obstacle around the Air inlet port or Air outlet port.
3) Where a sufficient space can be reserved for the service of air filter and the attachment/removal of panels.
4) Places exposed to oil splashes or steam (e.g. kitchens and machine plants).
Installation and use at such places will incur deteriorations in the performance or corrosion with the heat exchanger or
damage in molded synthetic resin parts.
5) Where pipes and wires can be arranged conveniently.
6) On the solid floor
7) Where the unit is not exposed directly to sun light.
8) Places where corrosive gas (such as sulfurous acid gas) or inflammable gas ( thinner, gasoline, etc.) is generated or remains.
Installation and use at such place will cause corrosion in the heat exchanger and damage in molded synthtic resin parts.
9) Where a complete draining can be assured.
10) Where a sufficient space can be reserved for service.
Floor standing installation
• Floor fixation
Cable tip
All models
4
Peri cover
100
100
Remote controller
installation section
Control box
Front Side
Unit : m
• Wall fixation
Peri cover
600
234
-
-
Unit : mm
Floor