Mitsubishi Heavy Industries FDC112KXEN6 Technical Manual page 310

Table of Contents

Advertisement

Code
Write contents
No.
37
FM01 Fan speed command
38
(Spare) FMo2 Fan speed
command
39
EEVH1 opening degree
40
EEVSC opening degree
41
Compressor target cooling low
pressure
42
Compressor target heating high
pressure
43
Outdoor EEVH target overheat
44
Outdoor EEVH initial learning
opeing position
45
Outdoor EEVSC target overheat
46
47
<PCB hardware input>
48
External input
49
Dip SW [SW3]
50
Dip SW [SW4]
51
Dip SW [SW5]
Record data
Unit of
Data write range
write
0 ~ 65535
10min-1
0 ~ 65535
10min-1
0 ~ 65535
1 pulse
0 ~ 65535
1 pulse
0.00 ~ 2.00
0.01MPa
0.00 ~ 4.15
0.01MPa
0 ~ 25.5
0.1°C
0 ~ 255
1 pulse
0 ~ 25.5
0.1°C
0 ~ 2550
10cc
0 ~ 255
3 min.
306
Number of
bytes
2
2
2
2
1
2
1
Actual range: 5°C – 11°C
1
1
1
1
1
Bit0
63H1
Bit1
(Spare) 63H1-R 0: Open, 1: Short-circuit
Bit2
CNS1
Bit3
(Spare) CNS2
Bit4
(Spare) CNG1
Bit5
(Spare) CNG2
Bit6
(Spare)
Bit7
(Spare)
1
Bit0
SW3-1
Bit1
SW3-2
Bit2
SW3-3
Bit3
SW3-4
Bit4
SW3-5
Bit5
SW3-6
Bit6
SW3-7
Bit7
SW3-8
1
Bit0
SW4-1
Bit1
SW4-2
Bit2
SW4-3
Bit3
SW4-4
Bit4
SW4-5
Bit5
SW4-6
Bit6
SW4-7
Bit7
SW4-8
1
Bit0
SW5-1
Bit1
SW5-2
Bit2
SW5-3
Bit3
SW5-4
Bit4
SW5-5
Bit5
SW5-6
Bit6
SW5-7
Bit7
SW5-8
Contents
0: Open, 1: Short-circuit
0: Open, 1: Short-circuit
0: Open, 1: Short-circuit
0: Open, 1: Short-circuit
0: Open, 1: Short-circuit
0: Open, 1: Short-circuit
0: Open, 1: Short-circuit
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON
0 : OFF, 1 : ON

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents