Mitsubishi Heavy Industries FDC112KXEN6 Technical Manual page 187

Table of Contents

Advertisement

7) A panel is hooked on two bolts (
A
8) Please rotate a hook, put in the slot on the panel, and carry out fixing the panel temporarily. [Figure 5]
9) Tighten the two bolts used for fixing the panel temporarily and the other two.
10) Please open the lid of a control box.
11) Like drain pump wiring, please band together by the clamp and put in louver motor wiring into a control box. [Figure 6]
12) Please connect a louver motor connector. [Figure 6]
13) Attach two chains to the air return grille with two screws. [Figure 7]
14) Replace the corner panels. Please also close a chain with a screw together then.
15) Close the air return grille.
mark A, B) [Figure 4]
A
[Figure 4]
Drain pump connector
Chain
[Figure 7]
B
Louver motor connector
Clamp
Wire intake
Louver motor wiring
Chain
183
-
-
[Figure 5]
[Figure 6]

Hide quick links: