Code
Contents of data display
No.
C56 Target Fk
C57 Inverter 1 operation frequency command
(Spare) Inverter 2 operation frequency
C58
command
C59 FMo1 Fan Speed command
C60 (Spare) FMo2 Fan Speed command
<Control status>
C61 Control status
C62 Control status
C63 Control status
C64 (Spare)
C65 Protection control status
C66 Protection control status
C67 (Spare)
C68 Compressor stop cause
C69 (Spare)
Minimum
Data display range
unit
0 ~ 999
1Hz
0 ~ 130
1Hz
0 ~ 130
1Hz
0 ~ 999
10min-1
0 ~ 999
10min-1
0,1
(0: Close, 1: Open)
0,1
(0: Close, 1: Open)
0,1
(0: Close, 1: Open)
0,1
(0: Close, 1: Open)
0,1
(0: Close, 1: Open)
0,1
(0: Close, 1: Open)
0,1
(0: Close, 1: Open)
0 ~ 127
1
0,1
(0: Close, 1: Open)
300
Remarks
Order of 100: Oil return control ON
Order of 10: Defrosting ON
Order of 1: (Spare)
Order of 100: Test run control ON
Order of 10: Demand control ON
Order of 1: Silent mode control ON
Order of 100: Capacity measurement mode ON
Order of 10: (Spare)
Order of 1: (Spare)
Order of 100:
Order of 10:
Order of 1:
Order of 100: HP control by compressor speed
down control ON
Order of 10: LP control by compressor
speed down control ON
Order of 1: Td control by compressor
speed down control ON
Order of 100: Compression ratio control by
compressor speed down control
ON
Order of 10: CS control by compressor
speed down control ON
Order of 1: PT control by compressor
speed down control ON
Order of 100: Tc control by compressor speed
down control ON
Order of 10: (Spare)
Order of 1: (Spare)
 *1
Order of 100:
Order of 10:
Order of 1