Programming Output Relays

Output Relay Displays
Enter Relay No.
(00 = Quit)
01
02
A EV ZL ZT
STT 0
0
0 00
02
A EV ZL ZT
STP –
0
00
02 Relay Action
No Response
0
02 Start Event
Not Used
0
02 Start:
Zn List
No List
0
If a relay is energized before a 4-wire smoke detector is
reset, the relay will be stopped by the interruption of Aux.
Power that resets the smoke detector. If this is not desired,
the power to the relay unit should be supplied from another
12V power source (e.g., the same source that is powering ex-
ternal equipment through the relay contacts).
1. With at least one 2-line Alpha keypad (5137AD or 6139) connected to the
keypad terminals on the control, power up the system temporarily. If you
had previously connected the AC transformer to the control panel, you
need only plug in the transformer (to 120VAC outlet) to power up the
system.
2. Enter the programming mode by keying the following on the Alpha keypad:
INSTALLER code (4 1 1 1) + 8 + 0.
Field 25 OUTPUT MODULE must have been programmed for a 4204 module
(enter "3").
3
Press 80. Note that this is an interactive menu programming mode. It is
used to program all output relays used in the system (4204 Relay
modules). Refer to the Programming Form worksheet in the separate
PROGRAMMING GUIDE for 80 Interactive Mode.
Upon pressing 80, this screen will appear. Enter the Relay Number 01, 02,
03, or 04 for a 4204 (or 00 to end these entries). Press the [ ] key to
continue.
The [ ] key is used to accept an entry and advance to the next prompt. The
[#] key is used to revert back to the last question to check or change an
entry. Press [ ] to go forward again.
This screen displays a summary of the current Relay START programming
(for this example, relay 02 has been selected).
Press the [ ] key to continue.
This screen displays a summary of the current Relay STOP programming.
Press the [ ] key to continue.
Enter the desired relay action as listed below. Press the [ ] key to continue.
0 = No response
1 = Close for 2 seconds
Enter the event to START the relay:
0 = Not used; 2 = Fault; 1 = Alarm; 3 = Trouble
A zone list must be used in conjunction with an event. If a zone type/system
operation is to be used instead of an event, enter 0.
Press the [ ] key to continue.
If a zone list will be used to START the relay action, enter the zone list number
(to be programmed in field 81): 1, 2, or 3. If not used, enter 0. Press the [ ]
key to continue.
7 –4
2 = Close and Stay Closed
3 = Continuous Pulse on & off
( 1 sec ON, 1 sec OFF)