Programming Options Defined; Figure 11: 4229 Connections To Control - ADEMCO VIA-30Pse Installation Instructions Manual

Hide thumbs Also See for VIA-30Pse:
Table of Contents

Advertisement

RELAY
CONNECTOR
}
}
RLY
RLY
REED
2
1
(TAMPER)
RELAYS
SWITCH
"OFF"

Programming Options Defined

RELAY
DIP SWITCH
2
FOR SETTING ADDRESS
AND ZONE "A" RESPONSE
RELAY
1
NO C NC
TAMPER JUMPER POSITION
4229 IN CABINET
(NOT TAMPERED)
4229 REMOTE
(TAMPER PROTECTED)
1
2
3
4
5
6
1K
A
B
C
D
ZONES:
Figure 11. 4229 Connections to Control
The following will help you understand the programming of OUTPUT RELAYS
when using 80 and 81 interactive menu modes. The options used to start
and stop relays are described below, followed by the actual screen prompts
and available entries.
The letter(s) in parentheses after each function described below, such as (A)
after ACTION, are those that appear in the various summary displays of
programmed data during programming.
ACTION (A)
The "ACTION" of the relay is how the relay will respond
when it is activated by the "START" programming. You may
want the relay to activate momentarily, to pulse on and off
continuously, or to remain activated until some other event
occurs to stop it. There are four different choices of actions:
• ACTIVATE for 2 SECONDS and then reset.
• ACTIVATE and REMAIN ACTIVATED until stopped by
some other event.
• PULSE ON and OFF until stopped by some other event.
• NOT USED when the relay is not used.
START (STT)
The "START" programming determines when and under what
conditions the relay will be activated. The following START
options are available :
A) 1. EVENT (EV) is the condition (Alarm, Fault, Trouble) that must
occur to a zone or group of zones (zone list) in order to
activate the relay. These conditions apply only when a zone
list is used. The different choices for "EVENT" are listed
below and in the "Programming Output Relays" section that
follows.
• ALARM
• FAULT
• TROUBLE
• NOT USED
7 –2
4229
4229
EITHER OR BOTH CAN BE USED
TB2
4-PIN CONSOLE PLUG
4
3
2
TB1
1
7
8
9
10 11 12
TERMINATE EACH
PROGRAMMED ZONE
WITH 1000 OHM (1K)
END-OF-LINE RESISTOR
(EACH ZONE'S MAX.
LOOP RESISTANCE:
300 OHMS + E.O.L.)
E
F
G
H
Relay action begins upon any alarm in an
assigned zone in the zone list.
Relay action begins upon any opening or
short in an assigned zone in the zone list.
Relay action begins upon any trouble
condition in an assigned zone in the zone list.
Relay action is not dependent upon one of
the above events.
TERMINALS ON
CONTROL PANEL
GRN DATA OUT
4
(TERM 6)
TO CONTROL
BLK
3
(–) GROUND
(TERM 4)
RED
(+) 12V
(TERM 5)
2
YEL DATA IN
1
FROM
(TERM 7)
CONTROL