Si18-201
3.

System control

3.1

Outline of System Control

Power supply ON
Compressor / OFF
Unit stop (standby control)
· Warming-up function
· Cooling electrical switch box
Compressor / ON
Has
the previous
standby operation
completed?
Operation start
· Initial frequency (differ from cooling and heating)
· Decision of initial motorized valve opening.
(differ from cooling and heating)
Feedback control
Cooling SC control (Decision for EVL open/close)
EVL: Close
(Independent VRV control)
BP unit
SH control
Target discharge pipe temp. control
EVG
Target discharge pipe temp. control
<Excess refrigerant processing>:
Subcooling control in cooling
· Refrigerant is stored in the piping
before EV of BP unit.
Cooling capacity control
System protection control
· Gas shortage control
· Wet protection control
· Peak cut / Freeze protection control
Main Functions
ON command
NO
Start-up standby operation
YES
Cooling
EVL: Open
(Super-multi control)
BP unit
Gas pipe isothermal control
Target discharge pipe temp. control
EVG
· Discharge pipe temp. control
· Differential pressure securing fin control
· Year-round cooling
Heating
BP unit capacity control (Decision for EVG open/close)
(1 or 2 step control)
EVG: Close
EVG: Open
(Super-multi control)
(Independent VRV control)
BP unit
BP unit
SC control
SC control
Target discharge pipe temp. control
EVG
Reverse target discharge pipe control
EVG
EVL
Target discharge pipe control
EVL
<Excess refrigerant treatment>:
Reverse target discharge pipe temp. control in heating
· Firstly refrigerant is stored inside the piping
in the no-operation room unit.
· When overflow command is generated,
refrigerant is stored in the receiver.
Heating capacity control

System control

3-minutes standby
· Equalizing control
· Fan OFF delay
OFF command
(Before equalizing)
· Standby operation
ON
OFF
command
command
NO
YES
ON ?
Command
Completed
Defrost control
Heating
· Oil return control
YES
OFF control
Is
heating oil
return control
required?
Cooling
· Oil return control
ON control
· Input current control
· Compressor protection control
· High pressure control
NO
(M1003)
109