3
. Functions
3-1
Specifications
Item
Source power requirement
Environmental condition
Dimensions
Weight
System condition
Number of control unit
User operating function

ON/OFF

Operation
mode
Fan speed
Operation
Air direction
and swing
operation
Temperature
setting
DC24V,0.02A(Maximum loading)
Power received from PAC-SC50KUA Power Supply Unit via M-NET transmission line.
Input voltage
DC12V,0.2A(Maximum loading)
Power is received from the PAC-SC50KUA Power Supply Unit via the DC power line.
Operating
Temperature
Non operating
30
Humidity
mm
120(H)
300(W)
in
4-3/4(H)
11-13/16(W)
Kg
1.0
lb
2-1/4
Indoor unit or independent OA processing unit or LOSSNAY
: 50 units maximum (50 groups maximum)
Number of units (indoor or independent OA processing unit or LOSSNAY) in one group
: 1-16 units
*Note
Indoor unit, independent OA processing unit and LOSSNAY can not
register to the same group.
Number of remote controllers in one group
*3
: 1-2
Number of system controllers in one group
: 0-4 (including the number of remote controller in one group)
: 0-3 for groups which have one remote controller.
Number of indoor units interlocked with one OA processing unit or LOSSNAY
: 0-16 (some types of OA processing unit can only be operated when inter-
The ON/OFF operation can be performed as a collective or per group.
The switch operation for the operation mode setting can be performed as a collective
or per group.
[ Selectable operation mode for the indoor unit ]
*1
Cool/Dry/Fan/Auto/Heat
[ Selectable operation mode for the independent ventilation ]
Heat recovery/By-pass/Auto
The switch operation to set the High and Low speed can be performed as a collective
*1
or per group.
( The 4 fan speed setting is available to the indoor that has 4 levels )
The air flow direction can be switched to 4 directions and swing operation as a collec-
tive or per group
*1
Temperature setting can be performed collectively or per group.
[Setting temperature range]
Cool (Dry) operation
Heat operation
Auto operation

Specification

0 ˚C
+40 ˚C / 32 ˚F
-20 ˚C
+60 ˚C / – 4 ˚F
90%RH (No condensation)
80[*19](D)
3-1/8[*3/4](D)
locked to a maximum of 9 units)
: 19
30 ˚C / 67
: 17
28 ˚C / 63
: 19
28 ˚C / 67
-4-
+104 ˚F
+140 ˚F
*[ ] : indicate the thickness from the
wall.
87 ˚F
83 ˚F
83 ˚F

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents