There must be no leakage of smoke through the structure of
the chimney during or after the smoke pellet test and it is
important to check inside upstairs rooms adjacent to the chimney /
flue. Check the chimney pot / terminal and general condition of the
brickwork or masonry. If the chimney or flue is in poor condition or if
there is no up-draught do not proceed with the installation. If there is a
history of down-draught conditions with the chimney / flue, a tested and
certificated flue terminal or cowl suitable for the relevant flue type should
be considered.
6.
A spillage test must always be carried out during commissioning of
the appliance.
1.6
CHIMNEY OPENING AND CATCHMENT SPACE
The front opening of the chimney must be between 610mm and 650mm wide, and
between 510mm and 525mm high. If the opening exceeds these dimensions then
an opening must be constructed from suitable non-combustible material to
produce a correct size opening. Any opening must be suitably sealed to prevent
leakage. See below in fig.1
Fig. 1
510mm Minimum
525mm Maximum
NOTE :
Please ensure that an additional vertical clearance of 100mm is
available above the opening height of the chimney for the
collection hood or spigot outlet hood. The collection hood or
spigot outlet hood are removable from within the product as
shown in section 2.5 / 2.6 on pages 12 & 13.
630mm Minimum
Fire Opening
Minimum Flat
Sealing Area
10mm all round
610mm Minimum
650mm Maximum
6
530mm
Minimum