2-INSTALLATION INSTRUCTIONS

CONNECTION TO THE CHIMNEY

The chimney is the fundamental element for smoke expulsion and must therefore comply with the following requirements:
be waterproof and thermally insulated.
Be made of suitable materials that resist mechanical stress over time, heat, the effects of the combustion products and any possible
condensation.
Have a vertical set-up with deviations from the axis of no more than 45° and free of bottlenecks.
Must be suitable for the specific operating conditions of the product and have the CE marking (EN1856-1, EN1443).
Must be adequately sized for the draught/smoke expulsion requirements that are necessary for the product to operate correctly
(EN13384-1).
The internal section is preferably circular.
In the case of a pre-existing product that has been used, it must be cleaned.
The chimney must not be shared with other appliances.
The chimney is fundamental for correct operation and safety of your product.
Below are certain rules on correct installation. Any alternative configurations must be suitably sized in accordance with the general
method of calculation of UNI EN 13384-1.