Positioning And Restrictions; Boiler Room - RED LOGIKA 25-35 Installation Manual

Table of Contents

Advertisement

2-INSTALLATION INSTRUCTIONS

POSITIONING AND RESTRICTIONS

In the case of simultaneous installation with other heating appliances, provide appropriate air inlets for each one (according to the
instructions of each product).
The product cannot be installed (except for sealed or closed operation appliances with external ducted combustion
air intake):
in bedrooms or bathrooms;
in rooms where there are liquid fuel appliances with continuous or intermittent operation that draw the
combustion air from the room they are installed in;
in rooms where there are B-type gas heating appliances, with or without domestic hot water production and
interconnecting rooms;
where another heating appliance is installed without an independent air flow.
It is forbidden to place the product in an explosive atmosphere.
The air inlet must also:
be protected with a grid, metal mesh, etc. without reducing the net section.
Be positioned in such a way so as not to be obstructed.
Allow maintenance to be performed.
Be directly interconnected with the room where the product is installed.
In the case of ducting, up to 3.5 linear metres, increase the cross-section by about 5%, whereas for longer ducts, increase it by 15%.
Remember that the ventilation grilles always feature an indication of the useful cross-section in cm
When choosing the grille and size of the hole, check that the useful section of the grille is larger or equal to the
section required by the company for product operation.
IMPORTANT!
The air flow can also be drawn from an adjacent room to that of the room where the product is installed, provided
the air can flow freely through permanent openings interconnected with the outside; air inlets connected to thermal
units, garages, kitchens or bathrooms must be avoided.

BOILER ROOM

Check that the room meets the requirements and provisions of the standards in force. There must also be a flow of at least enough air in
the room for normal combustion. Vents must be installed in the walls of the room that meet the following requirements:
Increase the cross-section by at least 6 cm
than 100 cm The cross-section can also be calculated using the following equation:
S = K * Q ≥ 100 cm
2
Where "S" is in cm
, "Q" in kW, "K" = 6 cm
2
The opening must be located at the base of an external wall, preferably opposite the one with the outlet for combusted gases.
Heat-sensitive or flammable objects cannot be placed near the product. Keep such objects at a minimum distance of
80 cm from the outermost point of the product.
8
for each 1 kW The minimum cross-section of the opening must not, however, measure less
2
/kW
2
on one side.
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents