2-INSTALLATION INSTRUCTIONS
CONNECTIONS
CONNECTION TO THE CHIMNEY
The inside of the chimney should measure
no more than 20x20 cm or 20 cm in
diameter; in the case of a larger chimney,
or a chimney in poor condition (e.g. with
cracks, insufficient insulation, etc.), it is
advisable to insert a stainless steel pipe of
suitable width that extends from the base
to the very top of the chimney.
1
0,5 mt.
0,5 mt.
2
3
1) WINDPROOF CHIMNEYPOT
•
Use adequate instruments to verify that there is a minimum draught of 5 Pa.
•
Set-up an inspection hole at the bottom of the chimney to perform periodic checks and cleaning, which must
be done annually.
•
The connection to the chimney must be sealed and the fittings and pipes recommended by us must be used (CE
marked in accordance with EN1856-2 with the minimum requisites: T200 and P1).
•
You must ensure that a windproof chimneypot is installed in accordance with the regulations in force.
•
This type of connection guarantees smoke expulsion even in the event of a temporary power cut.
12
CONNECTION TO AN
EXTERNAL DUCT WITH INSULATED OR
DOUBLE-WALL PIPE
The inside of the external duct must
measure a minimum of 15x15 cm, or 15
cm in diameter, and a maximum of 20x20
cm, or 20 cm in diameter.
Only stainless steel insulated (double-
wall) pipes must be used, which are
smooth on the inside and fixed to the
wall. Flexible stainless steel pipes must
not be used.
1
1
0,5 mt.
0,5 mt.
2
2
3
3
2) CHIMNEY 3) INSPECTION
1
0,5 mt.
2
3
CONNECTION TO THE CHIMNEY
The connection between the product and
the chimney or the smoke duct must not
have an inclination that is less than 3% in
the horizontal sections, which must have
a maximum overall length of 2/3 m. The
vertical section between one T-fitting and
another (angle) must not be less than
1.5 m.
1
1
0,5 mt.
0,5 mt.
2 - 3 mt. MAX
2 - 3 mt. MAX
2
2
3-5 %
3
3
1
1
0,5 mt.
2 - 3 mt. MAX
2
2
3-5 %
3-5 %
3
3
1
3