12 - TROUBLESHOOTING

CHECKING THE INTERNAL COMPONENTS
ATTENTION:
All operations that require repairs must be carried out solely by a specialist technician with the boiler extinguished,
cold and with the power cord unplugged.
ANOMALY
The pellets are not fed into the
combustion chamber.
The fire goes out or the boiler stops
automatically.
34
POSSIBLE CAUSES
The pellet hopper is empty
Sawdust has blocked the feed screw
Faulty gear motor
Faulty electronic board
The pellet hopper is empty
The pellets are not fed
The pellet temperature safety probe has
been triggered
The door is not closed properly or the
gaskets are worn
Unsuitable pellets
Low pellet supply
The combustion chamber is dirty
Clogged outlet
Faulty smoke extraction motor
Pressure switch broken or defective.
SOLUTIONS
Fill the hopper with pellets
Empty the hopper and remove the sawdust
from the feed screw by hand
Replace the gear motor
Replace the circuit board
Fill the hopper with pellets
See the previous anomaly
Let the boiler cool down, restore
the thermostat until the problem is
resolved and switch the boiler back on.
If the problem persists contact Technical
Assistance.
Close the door and replace the gaskets
with original ones
Change the type of pellets with those
recommended by the manufacturer
Check the flow of fuel following the
instructions in the booklet.
Clean the combustion chamber, following
instructions in the manual
Clean the smoke duct
Check the motor and replace it, if neces-
sary
Replace the pressure switch.