Fan Motor & Compressor Motor Capacitor; Transformer - Whirlpool ACP102PR Manual

10,000 btu portable room air conditioner
Table of Contents

Advertisement

Disconnect power before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.
FAN MOTOR & COMPRESSOR
MOTOR CAPACITOR
Fan Motor Capacitor
Refer to page 4-7 for the procedure for ac-
cessing a fan motor or compressor motor ca-
pacitor.
1.
Unplug air conditioner or disconnect power.
2.
Discharge the capacitor by touching
the leads of a 20,000 Ω resistor to the
terminals.
3.
Disconnect the wires from the capacitor
terminals.
4.
Set the ohmmeter to the R x 1K scale.
5.
Touch one of the ohmmeter test leads to
the capacitor terminals. The meter should
indicate several ohms, and gradually re-
turn to infinity.
Electrical Shock Hazard
Compressor Motor
Capacitor

TRANSFORMER

Refer to page 4-7 for the procedure for access-
ing the transformer.
1.
Unplug air conditioner or disconnect power.
2.
Disconnect the transformer wires from
the control board terminals.
3.
Set the ohmmeter to the R x 1 scale.
4.
Touch the ohmmeter test leads to the
plug terminals with the primary (red)
transformer wires. The meter should in-
dicate between 110 and 140 Ω.
5.
Touch the ohmmeter test leads to the
plug terminals with the secondary (white)
transformer wires. The meter should indi-
cate approximately 2 Ω.
5-2
Secondary
(White)
Primary
(Red)