Disconnect power before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.
ROOM TEMP & DE-ICE
THERMISTORS
Refer to page 4-11 for the procedure for ac-
cessing the room temp and de-ice thermistors.
NOTE: The two thermistors are replaced as
an assembly.
1.
Unplug air conditioner or disconnect power.
2.
Disconnect the room temp & de-ice
thermistor connector from the control
board terminals.
3.
Set the ohmmeter to the R x 1 scale.
4.
Touch the ohmmeter test leads to plug
terminals 1 & 2 (room temp), and 3 & 4
(de-ice). The meter should indicate the
same resistance for either thermistor, as
shown in the following chart.
Temp. °F, (°C)
32 (0)
72 (22)
75 (24)
77 (25)
84 (29)
Electrical Shock Hazard
Resistance, ±3%
50900
17210
15700
15000
12530
WATER PUMP MOTOR
Refer to page 4-14 for the procedure for ac-
cessing the water pump motor.
1.
Unplug air conditioner or disconnect power.
2.
Disconnect the water pump motor wires
from the control board terminals.
3.
Set the ohmmeter to the R x 1 scale.
4.
Touch the ohmmeter test leads to the
wire terminals. The meter should indicate
between 15 and 35 Ω.
5-4