COMPRESSOR PROTECTION

The control protects the compressor by not
allowing a compressor restart for 3 minutes.
This delay will occur when moving through the
operating modes with the remote or keypad or
if there are rapid temperature changes at the
thermistor.
DE-ICE PROTECTION
A de-ice thermistor is mounted on the end of
the evaporator in a tube brazed to the tubing
loops. When the de-ice thermistor senses 25°F
(–4°C) for a continuous 30 seconds, the com-
pressor and condenser fan motors stop and
a buzzer sounds. When the de-ice thermistor
senses higher than 41°F (5°C), normal opera-
tion resumes.
FULL WATER WARNING
When the high water level switch closes, the
Water Full LED will flash and all operation will
cease. The consumer must manually drain the
sump by pulling the drain plug over a drain.
THERMISTOR FAILURE DEFAULT
To provide some cooling operation in the event
of a thermistor failure, the control will default
to the following settings if a thermistor is de-
termined to be shorted or open.
Room temp thermistor is shorted or open;
room temperature is set at 75°F (24°C).
De-ice thermistor shorted or open; assume
100°F (38°C).