Battery Maintenance - Bosch B5512 Reference Manual

Hide thumbs Also See for B5512:
Table of Contents

Advertisement

30
en | Power supply
Figure 6.1: Non-power-limited wiring (B5512 shown)
Callout ᅳ Description
1 ᅳ Conduit required for use with external batteries
2 ᅳ To CX4010 UL Listed Class 2 Transformer 18 VAC 22 VA 60 Hz
3 ᅳ 0.25 in (6.4 mm) minimum
4 ᅳ Battery terminals. BAT- is non-power limited
5 ᅳ Battery wires
6 ᅳ 12 V sealed lead-acid rechargeable battery (D126/D1218)
7 ᅳ Sensor loop wires
Charge the battery
Connect the battery and then the transformer to allow the control panel to charge the battery
while you complete the installation.
6.2.2

Battery maintenance

Use 12 VDC sealed lead-acid rechargeable battery (7 Ah or 18 Ah). The control panel supports
up to 18 Ah of battery. If you use two batteries, they must have the same capacity and you
must connect them using the D122/D122L Dual Battery Harness.
Replace the batteries every 3 to 5 years. If you install two batteries, replace them both at the
same time.
Record the date of installation directly on the battery.
2015.07 | 12 | F.01U.287.180
2
1
Installation and System Reference Guide
COMMUNICATION MODULE 1
OUTPUT A
Jumper Under Cover
AUX PWR
COM
DRY
SDI2
OUTPUT A
Device Bus
R Y G B
AUX
18 VAC
BATTERY
OUTPUT A
- 12 V +
NO C NC
COM AUX
R
Y
18VAC
+ BAT -
OUTPUT A
PWR A
5
3
6
ETHERNET
100BASE-T
LINK
USB
ON-BOARD POINTS
Voltage Ranges
C
Open
3.7 - 5.0 VDC
OUTPUT
Normal
2.0 - 3.0 VDC
B
Short
0.0 - 1.3 VDC
1 k
End of Line Resistors
1 COM 2
3 COM 4 5 COM 6
7 COM 8
G
B
1
COM
2
3
COM
4
5
COM
6
7
COM
8
B COM
4
Bosch Security Systems, Inc.
Control Panel
7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for: