Supervision; Installation And Control Panel Wiring (B308) - Bosch B5512 Reference Manual

Hide thumbs Also See for B5512:
Table of Contents

Advertisement

Control Panel
Octo-output module number
05*
* Valid for the B5512 only.
Table 11.1: Octo-output module valid relay numbers
11.1.2

Supervision

The control panel enables supervision of B308 Octo-output Modules on the SDI2 bus when the
Output Source of an off-board output is set to Octo-output.
With any failure to receive an expected response from the module, all keypads show a system
fault. The control panel sends a module trouble report to the central station (if configured for
module trouble reports).
11.1.3

Installation and control panel wiring (B308)

Ensure that there is enough power for the module and other powered devices you want
connected to the system.
Refer to On-board outputs, page 58.
Caution!
Remove all power (AC and battery) before making any connections. Failure to do so might
!
result in personal injury and/or equipment damage.
Install the module
1.
2.
3.
Wire to the control panel
When you wire an SDI2 module to a control panel, you can use either the terminal strip
labeled with PWR, A, B, and COM to wire to corresponding terminals labeled PWR, A, B, and
COM on the control panel, or you can use the interconnect wiring connector and the included
interconnect cable.
For terminal wiring, use 18 AWG to 22 AWG (1.02 mm to 0.65 mm) wire.
Notice!
Use either the terminal strip wiring or interconnect wiring to the control panel. Do not use
both. When connecting multiple modules, you can combine terminal strip and interconnect
wiring connectors in series.
Bosch Security Systems, Inc.
Set the module address using the address switches before you install it in the enclosure.
Install the module in the enclosure with the control panel or in an adjacent enclosure that
is within the distances rated for the module: 400 ft (137 m) with 22 AWG (0.65 mm) wire
or 1000 ft (305 m) with 18 AWG (1.02 mm) wire.
Use the screws provided with the module to secure the module in the enclosure.
Installation and System Reference Guide
Off-board outputs | en
Supported outputs
51 – 58*
61
2015.07 | 12 | F.01U.287.180

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

B3512B5512eB4512eB3512eB4512

Table of Contents