[P03 error]
Is protective control such as
discharge temprelease control normal?
YES
Is charged refrigerant amount normal?
YES
Is not abnormal overload?
NO
Are characteristics of
TD sensor resistance value normal?
YES
[H01 error]
Is power voltage normal?
YES
Is not abnormal overload?
NO
Is the circuit detected by
current sensor normal?
YES
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
NO
Are connections of
cable/connector normal?
NO
YES
NO
* Refer to Characteristics-4.
NO
YES
NO
– 97 –
www.heronhill.co.uk
NO
YES
* For RAV-SM563AT-E, SM803AT-E, replace control P.C. board.
Check and correct circuit cables.
* For RAV-SM563AT-E, SM803AT-E, replace control P.C. board.
Revised : Mar. 2007
Correct the cabling and
connection of connector.
®
Check parts. Defect
Replace
Check and correct the charged
refrigerant amount.
Improve and delete the cause
Replace TD sensor.
®
Check CDB.
Defect
Replace
Improve power line.
Improve and delete the cause.
®
Check IPDU.
Defect
Replace