Toshiba RAV-SM563UT-E Service Manual/Integration page 53

Air-conditioner split type
Hide thumbs Also See for RAV-SM563UT-E:
Table of Contents

Advertisement

c) Insertion of Flare Nut
d) Flare Processing
Make certain that a clamp bar and copper pipe have been cleaned.
By means of the clamp bar, perform the flare processing correctly.
Use either a flare tool for R410A or conventional flare tool.
Flare processing dimensions differ according
to the type of flare tool.
When using a conventional flare tool, be sure
to secure "dimension A" by using a gauge for
size adjustment.
Table 7-2-3 Dimensions related to flare processing for R410A
Outer
Nominal
diameter
diameter
(mm)
1/4
6.4
3/8
9.5
1/2
12.7
5/8
15.9
Table 7-2-4 Dimensions related to flare processing for R22
Outer
Nominal
diameter
diameter
(mm)
1/4
6.4
3/8
9.5
1/2
12.7
5/8
15.9
Table 7-2-5 Flare and flare nut dimensions for R410A
Nominal
Outer diameter
diameter
(mm)
1/4
6.4
3/8
9.5
1/2
12.7
5/8
15.9
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
Thickness
Flare tool for
(mm)
R410A clutch type
0.8
0.8
0.8
1.0
Thickness
Flare tool for
(mm)
R22 clutch type
0.8
0.8
0.8
1.0
Thickness
(mm)
A
0.8
9.1
0.8
13.2
0.8
16.6
1.0
19.7
– 53 –
www.heronhill.co.uk
Fig. 7-2-1 Flare processing dimensions
A (mm)
Conventional flare tool
Clutch type
0 to 0.5
1.0 to 1.5
0 to 0.5
1.0 to 1.5
0 to 0.5
1.0 to 1.5
0 to 0.5
1.0 to 1.5
A (mm)
Conventional flare tool
Clutch type
0 to 0.5
0.5 to 1.0
0 to 0.5
0.5 to 1.0
0 to 0.5
0.5 to 1.0
0 to 0.5
0.5 to 1.0
Dimension (mm)
B
C
9.2
6.5
13.5
9.7
16.0
12.9
19.0
16.0
ØD
A
Wing nut type
1.5 to 2.0
1.5 to 2.0
2.0 to 2.5
2.0 to 2.5
Wing nut type
1.0 to 1.5
1.0 to 1.5
1.5 to 2.0
1.5 to 2.0
Flare nut
width (mm)
D
13
17
20
22
23
26
25
29
Fax: 01823 665807